91
EN
Service codes
Safety
General
These service codes help to localise and - where possible - rectify faults with the device
directly on site. The individual service codes are subdivided into service classes.
The following information is given for every service code:
-
the reason the service code is being displayed
-
the relevant troubleshooting measure
Displaying status
codes
The inverter performs a system self diagnosis that automatically detects many faults that
may occur and shows them on the display. This means you are promptly made aware of
malfunctions in the inverter and the photovoltaic system, or of any installation or operating
faults.
If the system self diagnosis has detected a specific fault, the associated status code will be
shown on the display.
Total failure of the
display
If the display fails to come on some time after sunrise:
-
Check the AC voltage ON the inverter connections:
the AC voltage must be 230 V (+ 10 % / - 5 %)*.
*
The mains voltage tolerance depends on the country setup
Class 1 service
codes
Class 1 status codes generally only arise momentarily and are caused by the public grid.
The initial response of the inverter in this case is to disconnect itself from the grid. The grid
is subsequently checked for the stipulated monitoring period. If no further problem has
been detected by the end of this period, then the inverter will resume feeding energy into
the grid.
WARNING!
An electric shock can be fatal. Before opening the device:
-
If applicable, turn the mains switch to the -O- position
-
Unplug the device from the mains
-
Disconnect the inverter from the DC side
-
Using a suitable measuring instrument, ensure that electrically charged parts
(e.g. capacitors) are fully discharged
-
Restrict access to the working area
-
Take steps to ensure the metallic surfaces of the device cannot be touched
-
Suitable protective clothing and equipment must be worn when carrying out
the test or the repair
IMPORTANT!
Software may only be updated after consulting the Solar Electronics hotline.
The need for the update will be clarified in advance depending on the serial number and
firmware version.
IMPORTANT!
Status codes may sometimes appear briefly as a result of the inverter's con-
trol response. If the inverter then continues working with no sign of any problem, this
means that there was no fault.
Summary of Contents for Primo 3.0-1
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 32: ...32 ...
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 54: ...54 DC Trenner auf ON stellen 6 ...
Page 65: ...Sicherheitstechnische Überprüfung ...
Page 66: ......
Page 78: ...78 ...
Page 81: ...General information ...
Page 82: ......
Page 89: ...Error location aid ...
Page 90: ......
Page 108: ...108 ...
Page 109: ...Changing components ...
Page 110: ......
Page 130: ...130 Set the DC disconnector to ON 6 ...
Page 141: ...Safety Inspections ...
Page 142: ......
Page 154: ...154 ...
Page 155: ...Appendix ...
Page 158: ...158 ...
Page 159: ...159 ...