Class 3 service
codes
Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.
108
Stand-alone operation de-
tected
1. Stand-alone operation de-
tected
1. Automatic correction
2. Serious fault in public grid
2. Automatic correction
3. Poor contact: wall bracket <-
-> filter PC board
3. Check fixing screws in the
DATCOM area
4. Grid impedance is outside
permissible range
4. Contact energy supplier
5. Poor AC connection
5. Check AC connection
6. Ripple control signals
6. Report to Fronius Technical
Support specialists
7. Measurement fault on filter
PC board
7. Replace filter PC board
Code
Description
Behaviour
Remedy
Code
Description
Behaviour
Remedy
301
Current peaks detected in
grid
1. Voltage drop in the public
grid
1. Automatic correction
2. Grid impedance is outside
the permissible values
2. Contact energy supplier
3. Poor contact: wall bracket <-
-> inverter
3. Check fixing screws in the
DATCOM area
4. Measurement fault on filter
PC board
4. Replace filter PC board
5. Incorrect power limit on de-
vice
5. Replace power stage set
302
Current peaks detected in
PV generator
1. Poor contact: wall bracket <-
-> inverter
1. Check fixing screws in the
DATCOM area
2. Voltage drop in the public
grid
2. Automatic correction
3. Measurement fault on power
stage set
3. Replace AC PC board. Oth-
erwise, replace DC PC board
303
Heat sink temperature too
high
1. Ventilation opening blocked
1. Clean openings
2. Ambient temperature too
high
2. Change installation site
3. Internal or external fan not
connected
3. Connect fan cable
4. Faulty internal or external
fan
4. Replace the fan
5. Poor contact: power stage
set <--> heat sink
5. Check phase change paste
6. Measurement fault on power
stage set
6. Replace AC PC board
7. Faulty fan output on Recer-
bo
7. Replace Recerbo
Summary of Contents for Primo 3.0-1
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 32: ...32 ...
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 54: ...54 DC Trenner auf ON stellen 6 ...
Page 65: ...Sicherheitstechnische Überprüfung ...
Page 66: ......
Page 78: ...78 ...
Page 81: ...General information ...
Page 82: ......
Page 89: ...Error location aid ...
Page 90: ......
Page 108: ...108 ...
Page 109: ...Changing components ...
Page 110: ......
Page 130: ...130 Set the DC disconnector to ON 6 ...
Page 141: ...Safety Inspections ...
Page 142: ......
Page 154: ...154 ...
Page 155: ...Appendix ...
Page 158: ...158 ...
Page 159: ...159 ...