40
SMS / Relay
-
Event Delay:
For entering the delay time from when an SMS is sent or from when the relay should
switch
900–86400 seconds
-
Event Counter:
For entering the number of errors following which an SMS is sent or the relay should
switch:
10–255
Insulation settings
-
Insulation warning:
to activate and deactivate the insulation monitoring with display of a warning without
interrupting feed-in in the event of an insulation error
ON / OFF (depends on the country setup)
-
Threshold warning:
to set an insulation threshold below which the inverter displays a warning (without
interrupting feed-in)
depends on the country setup set
-
Threshold error:
to set an insulation threshold under which the inverter displays an error message
and interrupts feed-in
depends on the country setup
Temperature warning
to activate / deactivate the overtemperature warning for an event;
the overtemperature warning is sent and shown on the display.
ON / OFF
TOTAL Reset
resets the max. and min. voltage values and the max. power of feeding in in the LOG
menu item to zero.
Once you have reset the values, this cannot be undone.
To reset the values to zero, press the "Enter" key.
"CONFIRM" is displayed.
Press the "Enter" key again.
The values are reset and the menu is displayed.