Technical data
Technical data
Modbus transmission speed:
9600 baud
Parity bit:
none
Software version:
-
Fronius Datamanager 2.0 (from version 3.16.1 onwards)
-
Fronius Symo Hybrid (from version 1.16.1 onwards)
Measuring input
Three-phase nominal voltage
Operating range
400 - 480 V
320 - 552 V (-20% to +15%)
Single-phase nominal voltage
Operating range
230 - 277 V
184 - 318 V (-20% to +15%)
Voltage transformer ratio (kVT)
1 - 1000
e. g. VT 20000/400V kVT = 50
for direct connection: kVT = 1
Self-consumption - voltage path
(max. voltage)
10 VA
Nominal frequency
Tolerance
50 - 60 Hz
45 - 65 Hz
Nominal current, l
b
1 A + 5 A
Maximum current, I
max
6 A
Starting current
10 mA
Current transformer ratio (kCT)
1 - 1000
e. g. TC 800/5A kCT = 160
for direct connection: kCT = 1
Short-time overload
(EN IEC 62053-21, EN IEC 62053-23)
5 l
max
/ 0.5 s
Self-consumption - current path (max. cur-
rent)
0.3 W per phase
Maximum value kVT x kCT
1000 (CT/5A)
Current distortion factor
in acc. with EN IEC 62053-21
Power factor
Operating range
(EN IEC 62053-21, EN IEC 62053-23)
active cosφ 0.5 ind - 0.8 cap,
reactive sinφ 0.5 ind - 0.5 cap
Energy
Max. display
As per table
Resolution
As per table
LED indicator
1 pulse / 0.1 Wh
Active energy accuracy
(EN IEC 62053-21)
Class 1
Reactive energy accuracy
(EN IEC 62053-23)
Class 2
38
Summary of Contents for Smart Meter TS 5kA-3
Page 2: ......
Page 4: ...4 ...
Page 5: ...Safety rules 5 ...
Page 6: ...6 ...
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 15: ...Installation 15 ...
Page 16: ...16 ...
Page 19: ...1N1E 3 2E 1 3 3 2E 1 3 3 3E 19 EN ...
Page 30: ...30 ...
Page 31: ...Start up 31 ...
Page 32: ...32 ...
Page 41: ...41 EN ...
Page 42: ...42 ...
Page 43: ...43 EN ...