Energy
Response time after switch-on
(EN IEC 62053-21, EN IEC 62053-23)
< 5 s
kCT x kVT
Maximum display
Resolution
1 - 9.9
9 9 9 9 9 9 . 9 9 kWh / kvarh
10 Wh / varh
10 - 99.9
9 9 9 9 9 9 9 . 9 kWh / kvarh
100 Wh / varh
100 - 999.9
9 9 9 9 9 9 9 9 kWh / kvarh
1 kWh / varh
≥ 1000
9 9 9 9 9 9 . 9 9 MWh / kvarh
10 kWh / varh
Average power
Measured variable
Effective power
Calculation
Average value over set period of time
Integration time
5 / 8 / 10 / 15 / 20 / 30 / 60 minutes
Output
RS485 communication
Electrically isolated from input and auxiliary voltage
Standard
RS485 - 3 conductors
Transmission
Serial, asynchronous
Protocol
Modbus RTU
Addresses
1 - 255
Number of bits
8
Stop bit
1
Parity bit
None - even - odd
Baud rate
9600, 19200, 38400 bit/s
Response time
≤ 200 ms
Insulation (EN IEC 62052-11, EN IEC 62053-21)
Installation category
III
Degree of pollution
2
Insulation voltage
4 kV RMS
Impulse withstand voltage
Test circuit
4 kV 1.2/60 µs
Voltage input, current input, pulse output,
communication
Test voltage
Test circuit
2.75 kV RMS. 50 Hz/1 min
Voltage input, current input, pulse output,
communication
Test voltage
Test circuit
4 kV RMS. 50 Hz/1 min
All circuits and earth
Electromagnetic compatibility
Test in acc. with EN IEC 62052-11
39
EN
Summary of Contents for Smart Meter TS 5kA-3
Page 2: ......
Page 4: ...4 ...
Page 5: ...Safety rules 5 ...
Page 6: ...6 ...
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 15: ...Installation 15 ...
Page 16: ...16 ...
Page 19: ...1N1E 3 2E 1 3 3 2E 1 3 3 3E 19 EN ...
Page 30: ...30 ...
Page 31: ...Start up 31 ...
Page 32: ...32 ...
Page 41: ...41 EN ...
Page 42: ...42 ...
Page 43: ...43 EN ...