37
EN-US
Technical Data
Input data
Output data
(to the inver-
ter)
Max. continuous DC current
250 A
Admissible cable cross section for DC cables ‘OUT’
cable outlet from below
250 MCM
cable outlet from side
350 MCM
Copper
solid and stranded conductors
Number of DC+ output terminals
1
Number of DC- output terminals
1
Number of grounding terminals
1
Connection possibilities per output pole or
2 x M12 (0.47 in.)
grounding terminal
Max. number of cables per output pole or
2
grounding terminal
Cable lugs for output poles or
single hole cable lug
grounding terminal
or 2-hole cable lug
DC input voltage range
0 - 600 V
Max. input voltage
600 V
(at 1000 W/m² / 14°F in open circuit operation)
Max. array short circuit current
12.5 A
per string (1.25 * Imax)
Max. number of strings (with solar module fuse)
25
Admissible cable cross section
min. AWG 12 - max. AWG 8
(for DC cable ‘IN’)
Copper
solid and stranded conductors
Number of measuring channels
5
Max. current per measuring channel
50 A
Max. input current per fuse holder
20 A
Max. fuse size (10 x 38 class CC fuse)
20 A, 600 V
Number of grounding terminals
25
Admissible cable cross section
min. AWG 12 - max. AWG 6
for grounding cables
Copper
solid and stranded conductors