65
EN-US
Fronius Symo
24.0-3 480
Input Data
MPP voltage range
500–800 V DC
Input voltage range (at 1000 W/m² / 14°F in an open circuit)
200–1000 V DC
Max. input current (MPP1/MPP2)
(MPP1 + MPP2)
33.0/25.0 A
51 A
Max. short circuit current of solar modules (I
SC PV
) (MPP1/MPP2)
49.5/37.5 A
Max. recovery current
4)
49.5/37.5 A (RMS)
5)
Output Data
Nominal output power (P
nom
)
23995 W
Max. output power (+104°F)
23995 W
Max. output power (+122°F)
at 480 V
14800 W
Phases
3 ~ NPE
Nominal grid voltage
at 480 V
277 V/480 V
Operating range AC voltage
-12 +10%
Grid voltage setting range
127–322 V/220–558 V
Nominal output current
at 480 V
28.9 A
Maximum output current
at 480 V
32.8 A
Max. output residual current per duration
64 A/2.34 ms
Nominal frequency
50/60 Hz
1)
Total harmonic distortion
< 1%
Power factor (cos phi)
0 - 1 ind./cap.
2)
General Data
Maximum efficiency
98.00%
CEC efficiency
at 480 V
97.50%
Cooling
Controlled forced-air ventilation
Protection class
NEMA 4X
Dimensions h x w x d
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
Weight (full/lite version)
95.7 / 95.0 lbs. (43.4 / 43.1 kg)
Permissible ambient temperature
-40°F to +140°F (-40°C to +60°C)
Permissible storage temperature
-40°F to +158°F (-40°C to +70°C)
Permissible humidity
0–100%
Noise emission
65 dB(A) (ref. 1pW)
Protection Devices
Reverse polarity protection
Integrated
Stand-alone operation protection
Integrated
Arc detection/interruption
Integrated
Photovoltaic insulation monitoring
Integrated
Overtemperature
Operating point shift/
active cooling