INSTALLATION AND MAINTENANCE MANUAL
TRANSLATION OF THE
ORIGINAL DOCUMENT
For additional copies visit:
www.frost‐trol.com
WALEN SOLID
LINES
D008586
Versión:
1
-16-
To adjust the reheating remove the cap from the thermostatic expansion valve
reheating screw and turn it anti-clockwise to lower the reheating, or clockwise to
increase the reheating.
Turn the screw in no more than quarter turn movements at a time and wait 15
minutes between each adjustment so that the system can stabilize. Once an
adequate reheating value has been obtained, replace the cap on the thermostatic
expansion valve reheating screw and close its lid.
2.8.
ELECTRICAL CONNECTION
The assembly, installation and connection of these cabinets must be
carried out by a certified technician.
Before obtaining access to terminals, all supply circuits must be
disconnected.
Consult the circuit diagrams that are supplied with each cabinet when carrying out
the electrical connections and observe all of your country’s safety regulations in
full.
For the electrical connection it is mandatory to incorporate a switch
disconnector in accordance with installation regulation. This switch has
to be directly connected to supply terminals and has to be able to
provide full disconnection in all poles under overvoltage Category III
conditions.