INSTALLATION INSTRUCTIONS (CONTINUED)
The 120 volt, 15 amp units can be operated on a 120 volt 15 amp circuit under the following conditions:
1. No other electrical appliances or lights are connected to the same branch circuit.
2. Voltage is 120 Volts.
3. Circuit is equipped with a 15 amp circuit breaker or a 15 amp slow blow fuse type T (For Canada use Type
D).
4. The length of copper wire between the outlet and circuit breaker is not longer than 40 feet of
14 AWG or 70 feet of 12 AWG.
Amp
Rating
Range
Voltage
Cord Length in Feet
120V
25 ft.
50 ft.
100 ft.
150 ft.
200 ft.
250 ft.
300 ft.
400 ft.
500 ft.
240V
50 ft.
100 ft.
200 ft.
300 ft.
400 ft.
500 ft.
600 ft.
800 ft.
500 ft.
8 - 10
14
10
8
6
6
6
4
4
2
10 - 12
12
10
8
6
6
4
4
2
2
12 - 14
12
8
8
6
6
4
4
2
0
14 - 16
12
8
8
4
4
4
2
2
0
ASSEMBL
Y
/
INST
ALLA
TION
Ground
Pin
Grounded
Outlet
Outlet - 120V / 15A
Outlet - 120V / 20A
Figure 2 - 120V
Grounded
Outlet
Ground
Pin
Outlet - 240V
Figure 3 - 240V