background image

 

18 

 

6. Specifications 

 

CAPACITY* 

1000 VA / 800 W  1500 VA / 1200 W  2000 VA / 1600 W  3000 VA / 2400 W 

INPUT 

Voltage 
Range 

Low Line Transfer 

160 VAC / 140 VAC / 120 VAC / 110 VAC ±  5 % or 80 VAC / 70 VAC / 60 VAC / 50 

VAC ±  5 %   

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

Low Line Comeback 

  175 VAC ±  5 % or 85 VAC ±  5 %   

High Line Transfer 

  300 VAC ±  5 % or 150 VAC ±  5 %   

High Line Comeback 

  290 VAC ±  5 % or 145 VAC ±  5 %   

Frequency Range 

40Hz ~ 70 Hz 

Phase 

Single phase with ground 

Power Factor 

 0.99 @ 220-230 VAC (input voltage) 

OUTPUT 

Output voltage 

208/220/230/240VAC or 110/115/120/127 VAC 

AC Voltage Regulation   

±  3% (Batt. Mode) 

Frequency Range   

(Synchronized Range) 

47 ~ 53 Hz or 57 ~ 63 Hz 

Frequency Range (Batt. Mode) 

50 Hz ±  0.25 Hz or 60Hz ±  0.3 Hz 

Overload 

100%~110%: audible warning 

110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass 

mode when the utility is normal. 

>130%: UPS shuts down immediately at battery mode or transfer to bypass mode 

when the utility is normal. 

Current Crest Ratio 

3:1 

Harmonic Distortion 

 3 % THD (Linear Load)                 

 6 % THD (Non-linear Load) 

 4 % THD (Linear Load)                                                                                                                                                                                             

 7 % THD (Non-linear Load) 

Transfer 
Time 

AC Mode to Batt. Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

~ 85% 

~ 88% 

Battery Mode 

~ 83% 

BATTERY 

Standard 

Model 

Battery Type 

12 V / 7 AH 

12 V / 9 AH 

12 V / 7 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% capacity (Typical) 

Charging Current   

1.0 A(max.) 

Charging Voltage   

41.0 VDC ±  1%   

82.1 VDC ± 1%   

Long-run 

Model 

Battery Type & 

Numbers 

Depending on the capacity of external batteries 

Charging Current   

4.0 A or 8.0 A(max.) 

Charging Voltage 

41.0 VDC ±  1%   

82.1 VDC ± 1%   

PHYSICAL 

Tower 

Case 

Dimension, D X W X H   

397 X 145 X 220 (mm) 

421 X 190 X 318 (mm) 

Net Weight (kgs) 

13 

14 

26 

13 

28 

13 

Rack 

Case 

Dimension, D X W X H   

420x438x88[2U] (mm) 

580x438x133[3U] (mm) 

Net Weight (kgs) 

16 

10 

17 

10 

29 

17 

31 

17 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 45dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008/7, Linux, Unix and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 

208VAC. 

Summary of Contents for 1.5K

Page 1: ...1K 1 5K 2K 3K Online UPS Uninterruptible Power Supply System User Manual ...

Page 2: ...s 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 6 3 Operations 8 3 1 Button operation 8 3 2 LCD Panel 8 3 3 Audible Alarm 10 3 4 LCD display wordings index 10 3 5 UPS Setting 10 3 6 Operating Mode Description 13 3 7 Faults Reference Code 13 3 8 Warning indicator 14 4 Troubleshooting 15 5 Storage and Maintenance 17 6 Specifications 18 ...

Page 3: ...ver them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the buil...

Page 4: ...s must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any...

Page 5: ... are two different types of online UPS standard and long run models Please refer to the following model table Model Type Model Type 1K Standard 1KL Long run 1 5K 1 5KL 2K 2KL 3K 3KL 2 1 Rear panel view 1K L 1 5K L TOWER IEC Type Schuko Type India Type Africa Type NEMA Type 2K L TOWER IEC Type Schuko Type India Type Africa Type NEMA Type 3K L TOWER IEC Type Schuko Type India Type Africa Type NEMA T...

Page 6: ...ica Type Africa Type NEMA Type NEMA Type NEMA Type UK Type UK Type UK Type 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communication port ...

Page 7: ...eral outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon comple...

Page 8: ...ng this initial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower...

Page 9: ...de UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to def...

Page 10: ...tery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is work...

Page 11: ...ding Bypass Mode Sounding every 10 seconds 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives There are 9 programs to set up Refer to below table Paramete...

Page 12: ...uency setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Interface Setting Pa...

Page 13: ...0 240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac For 110 115 120 127 VAC models 85 115 setting the low voltage poi...

Page 14: ...ery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but still...

Page 15: ...econd Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over temperature Sounding every second Charger failure Sounding every second Out of bypass voltage range Sounding every second ...

Page 16: ...nd the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icon and is flashing on LCD display and alarm is sounding twice every second U...

Page 17: ... directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD...

Page 18: ...dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months 1 2 hours Be sure to deliver the spent battery to a recycling facility or ship it to your dealer i...

Page 19: ... Load 6 THD Non linear Load 4 THD Linear Load 7 THD Non linear Load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 85 88 Battery Mode 83 BATTERY Standard Model Battery Type 12 V 7 AH 12 V 9 AH 12 V 7 AH 12 V 9 AH Numbers 3 3 6 6 Recharge Time 4 hours recover to 90 capacity Typical Charging Current 1 0 A max Charging Volta...

Reviews: