Safety caution
This manual contains important instructions that
should be followed during installation and
maintenance of the UPS and batteries.
•
This UPS utilizes voltage that may be hazardous. Do not attempt
to disassemble the unit. The unit contains no user replaceable
parts. Only factory service personnel may perform repairs.
•
This pluggable type A equipment with battery already installed by
the supplier is operator installable and m ay be operated by
laymen.
•
The mains socket outlet that supplies the UPS shall be installed
near the UPS and shall be easily accessible.
•
During the installation of this equipment it should be assured that
the sum of the leakage currents of the UPS and the c onnected
loads does not exceed 3.5mA.
•
Connection to any other type of receptacle other than a two-pole,
three-wire grounded receptacle may result in shock hazard as
well as violate local electrical codes.
•
In the event of an emergency, press the "OFF" button and
disconnect the power cord from the AC power supply to properly
disable the UPS.
•
Do not allow any liquids or any foreign object to enter the UPS.
•
Do not place beverages or any other liquid-containing vessels on
or near the unit.
•
This unit intended for installation in a controlled environment
(temperature controlled, indoor area free of conductive
contaminants). Avoid installing the UPS in locations where there
is standing or running water, or excessive humidity.
•
Do not plug the UPS input into its own output.
•
Do not attach a power strip or surge suppressor to the UPS.
•
Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS.
•
Do not dispose of batteries in a fire as they may e xplode.
•
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or
disconnecting batteries terminal.
6)
Remove battery grounds during installation and maintenance to
reduce likelihood of shock.
•
Internal battery voltage is 12VDC.Sealed, lead -acid, 6-cell battery.
•
Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from batteries.
•
When replacing batteries, replace with the same number and type
of sealed lead-acid battery.
•
Do not open or mutilate the battery or batteries. Release
electrolyte is harmful to the skin and eyes. It may be toxic.
•
Attention, hazardous through electric shock. Also with dis-
connection of this unit from the mains, hazardous voltage still may
be accessible through supply from battery. The battery supply
should be therefore disconnected in the plus and minus pole at
the connectors of the battery when maintenance or service work
inside the UPS is necessary.
•
To reduce the risk of overheating the UPS, do not cover the UPS'
cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as space
heater or furnaces.
•
Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
Troubleshooting
Problem
Possible Cause
Solutions
LED not lit.
The UPS is not
on.
Press the power switch again to
turn on the UPS.
Battery voltage
is too low.
Charge the battery at least 6
hours.
Battery fault.
Replace the battery.
The UPS
always on
battery mode.
Power cord
loose.
Re-plug the power cord.
The UPS
continuously
beeps.
Please check
the fault code
for the details.
Please check the fault code for
the details.
Backup time
too short.
Battery voltage
is too low.
Charge the battery at least 6
hours.
Overload.
Remove some unnecessary
loads. Before reconnecting
equipment, please verify that the
load matches the UPS capability
specified in the specs.
Battery defect.
Replace the battery.
If any abnormal situations occur that are not listed above, please
call for service immediately.
Specification
400VA/600VA/800VA
Model
400
600
800
Capacity
400VA/
240W
600VA/
360W
800VA/
480W
Input voltage
220/230/240 Vac
Input Voltage
Range
162-290 Vac
Output Voltage
Regulation
±
10%(bat mode)
Transfer Time
Typical 2-6 ms
Waveform
Simulated Sinewave
Battery Type
12V/4.5Ah
12V/5Ah
12V/5Ah
Battery Number
1
1
1
Charging Time
4 hours recover to 90% capacity
Dimension(mm)
245 x 163 x 90
Net Weight (kgs)
3.5
4.0
4.5
Humidity
0-90% RH @ 0-40°C non-condensing)
Noise Level
Less than 40dB
*Specifications are subject to change without notice.
Placement & Storage
Placement:
Install the UPS in a protected area that is free of excessive dust
and has adequate air flow. Place the UPS away from other units at least
20 cm to avoid interference. For best performance, keep the indoor
temperature between 0°C and 40°C.
Storage:
All connected equipment should be turned off, then disconnect from
the UPS to avoid battery drain. Unplug the UPS from the wall outlet.
Then turn off the UPS for storage. Store the UPS unit covered and
upright in environments where the ambient temperature is -20°C to 50°C
with its battery fully charged.
FSP Manual Guide
Line-interactive UPS
ECO 400VA~800VA