background image

 

 

Diagram 11: 10KR(L) Rear Panel                                      Diagram 12:10KR(L) Input/ 

Output Terminal 

             

 

Diagram 13: 15KR(L)/20KR(L) Rear Panel                  Diagram 14: 15KR(L)/20K(L) 

Input/Output Terminal 

   

Diagram 15: Battery pack rear panel 

1.

 

RS-232 communication port   

2.

 

USB communication port   

3.

 

Emergency power off function connector (EPO connector) 

4.

 

Share current port (only available for parallel model) 

5.

 

Parallel port (only available for parallel model) 

6.

 

Intelligent slot 

7.

 

Maintenance bypass switch 

8.

 

External maintenance bypass switch port 

9.

 

Line input circuit breaker 

10.

 

Output circuit breaker for receptacles   

11.

 

Output receptacles: connect to mission-critical loads 

12.

 

Input/Output terminal (Refer to Diagram 4, 5,6, 7,10, 12 and 14 for the details) 

13.

 

Output terminal: connect to mission-critical loads 

14.

 

Programmable output terminal: connect to non-critical loads   

Summary of Contents for Proline 3/1 10K

Page 1: ...FSP Proline 3 1 3 1 10K 30K Online UPS Uninterruptible Power Supply System Version 1 6 User Manual ...

Page 2: ... the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One share current cable only available for parallel model One battery cable only available for 10KL NOTE Before installation please inspect the unit Be sure that nothing inside the pac...

Page 3: ...5 Diagram 3 15K 20K Rear Panel Diagram 5 15KL 20KL Input Output Terminal Diagram 6 15K 20K Input Output Terminal Diagram 7 15K 20K Grounding Terminal Diagram 4 10K 10KL Input Output Terminal ...

Page 4: ...6 Diagram 8 30KL rear panel Diagram 9 30K rear panel Diagram 10 30K L input output terminal ...

Page 5: ...current port only available for parallel model 5 Parallel port only available for parallel model 6 Intelligent slot 7 Maintenance bypass switch 8 External maintenance bypass switch port 9 Line input circuit breaker 10 Output circuit breaker for receptacles 11 Output receptacles connect to mission critical loads 12 Input Output terminal Refer to Diagram 4 5 6 7 10 12 and 14 for the details 13 Outpu...

Page 6: ...table Model Wiring spec AWG Input Output Battery Ground 10K 8 8 8 10KL 8 8 8 8 15K 6 6 6 15KL 6 6 6 6 20K 6 6 6 20KL 6 6 6 6 30K 4 4 4 30KL 4 4 4 4 NOTE 1 The cable for 10K 10KL should be able to withstand over 63A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 2 The cable for 15K 15KL should be able to withstand over 75A current It is recommended to use 6AWG ...

Page 7: ...9 Terminal Block wiring diagram of 10K 10KL Terminal Block wiring diagram of 15KL 20KL Terminal Block wiring diagram of 15K 20K ...

Page 8: ...rminal Please connect non critical devices to the programmable terminal and critical devices to the output terminal outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices NOTE 3 Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protectiv...

Page 9: ...terminal block and make sure the correct battery polarity is connected Wrong connection may cause permanent damage of the UPS Make sure the protective earth ground wiring is correct The wire current spec color position connection and conductance reliability should be checked carefully Make sure the utility input output wiring is correct The wire current spec color position connection and conductan...

Page 10: ...12 Wiring diagram of parallel system for 10K 10KL ...

Page 11: ...13 Wiring diagram of parallel system for 15K L 20K L ...

Page 12: ...14 Wiring diagram of parallel system for 30K ...

Page 13: ...lel system for 15KR L 20KR L S h a r e c u r r e n t c a b l e c o n n e c t i o n P a r a l l e l c o m m u n i c a t i o n p o r t c o n n e c t i o n S h a r e c u r r e n t c a b l e c o n n e c t i o n P a r a l l e l c o m m u n i c a t i o n p o r t c o n n e c t i o n ...

Page 14: ...stable 2 x 20 18 20 adjustable 2 x 20 18 20 adjustable 3 x 20 18 20 adjustable Recharge Time 9 hours recover to 90 capacity Charging Current 1 0 A 10 max 2 0 A 10 max 2 0 A 10 max 4 0 A 10 max Charging Voltage 273 V 1 Based on 20pcs batteries Long run Model Type Depending on applications Numbers 18 20 Charging Current 4 0 A 10 max 8 0 A 10 max 8 0 A 10 max 12 0 A 10 max Charging Voltage 273 V 1 Ba...

Page 15: ...able Recharge Time 9 hours recover to 90 capacity Charging Current 1 0 A 10 max 2 0 A 10 max 2 0 A 10 max Charging Voltage 273 V 1 Based on 20pcs batteries Long run Model Type Depending on applications Numbers 18 20 Charging Current 4 0 A 10 max 4 0 A 10 max 4 0 A 10 max Charging Voltage 273 V 1 Based on 20pcs batteries PHYSICAL Standard Model Dimension D X W X H UPS 668 x 438 x 133 3U Battery pac...