48 - 70
71130/11E/0318
Command KY
<id>KY<para5>
Access mode (Key).
Access:
Query mode.
Description:
When editing the parameters of the WEATHER STATION access authorisations are
required for most commands. This prevents any accidental change in parameters.
Access consists of three levels:
•
Query mode
"0"
•
User mode
"1"
•
Configuration mode
"4711"
Parameter description:
0:
Query mode
Parameters which have no access restrictions are those not stored in the
EEPROM, e.g. cyclic telegram enquiry or output of system status.
1:
User mode (USER ACCESS)
The user key protects parameters, which influence the behaviour of the
WEATHER STATION, e.g. averaging period and baud rate. The user can
change these parameters but should realise that this will modify the behaviour
of the WEATHER STATION.
Before any change it is recommended using the command SS to output and
then save the current configuration.
4711: Configuration mode (ADMIN ACCESS)
Parameters protected with this key are only available to the administrator. They were
set as defaults at the factory.
If the user switches from a higher access mode to the query mode by command, e.g.:
with "00KY0", the edited parameters will be permanently stored in the EEPROM.
Query mode is always switched on after a restart.
Value range:
0,1,4711
Initial value
0
Command MC
<id>MC<para5>
Magnetic compass correction optional.
Access:
Configuration mode (ADMIN).
Description:
With the magnetic compass correction a constant angle is added to the measured
direction of the magnetic compass.
The parameter serves for compensating a magnetic variation. The direction of the
magnetic compass can be used for automatic north correction of wind direction and
direction of brightness. See also
command NC
.
Value range:
0..359 [°]
Initial value:
0