INSTALLING A FUELTEC MODEL CF4.0 SYSTEM
WARNING: Read and understand all instructions. Failure to follow all instructions listed be-
low may result in explosion, fire ,serious injury, and/or death.
1.
Select a location close to the fuel storage tank that you will be servicing.
2.
Mount the system on a wall, mounting post, or use a Fueltec
“
tank mounting kit
”
3.
Install the fuel supply suction tube in the fuel storage tank access port so that the
suction tube nozzle is within 1/8 inch of the tank bottom. This will insure that even small
droplets of water are removed from the tank.
4.
Install an anti
-
siphon valve above the fluid level on above ground fuel storage tanks.
5.
Provide for thermal expansion on all system piping.
6.
Install the clean fuel return to tank piping to a second tank access port, or use a Fueltec
tank flange kit with a telescopic fluid pickup tube and return tee, all in one access port.
7.
Use one
(1”)
inch black iron pipe for supply and return piping if the polishing system is
within 30 feet of the above ground fuel storage tank. If run is longer than 30 feet, size
piping adequately for fuel flow.
8.
Large underground fuel storage tanks may require a submersible piston pump. To avoid
cavation and emulsification, gear, vane, and turbine pumps are not to be used.
9.
A standard household 20 amp fused electric circuit is required.
10.
The fuel storage tank and fuel polishing system shall be grounded with a low impedance
ground.
11.
Test all piping for leaks after installation.
12.
CAUTION: PRIME THE PUMP AND SYSTEM BEFORE OPERATING.
Summary of Contents for 100186