The CF4.0 CONTROL PANEL
Basic Operation:
On power up, unit will go to standby mode, indicated by green LED flashing at slow rate.
To start run cycle, press and release reset button. (Note: Reset button should be pressed for approximately one sec-
ond until green LED flashes at fast rate, then released.) During run cycle, green LED will be lit continuously. Yellow
LED will be lit when pump is energized (6 hours on, 18 hours off).
When a fault occurs, pump is de
-
energized, green and yellow LEDs are off and the red LED corresponding to the fault
will flash. To reset unit, press and release reset button. Reset can also be performed by turning off power to unit.
Note: Flow switch faults are ignored during the first ten seconds of each cycle after the pump starts.
To reset unit during run cycle (pump may be on or off), press and release reset button. Unit will go to standby mode
with green LED flashing at slow rate. Press and release reset button again and unit will start at beginning of cycle.
To operate pump manually press Jog Pump button. Pump may be operated manually during normal run mode,
standby mode or fault mode.