Field Wiring Torque and Wire Size Values for 

FRENIC-EcoPAK

 208/230V 

 

HP

Circuit Breaker

Fusible Disconnect

Terminal Blocks

'CB'

'FUSDISC'

'CTB'

2

n/a

17 in.lb.

4.5 in.lb.

18-8 AWG

22-12 AWG

3

n/a

17 in.lb.

4.5 in.lb.

18-8 AWG

22-12 AWG

5

n/a

17 in.lb.

4.5 in.lb.

18-8 AWG

22-12 AWG

7.5

62 in.lb.

17 in.lb.

4.5 in.lb.

14-1 AWG

18-8 AWG

22-12 AWG

10

62 in.lb.

30 in.lb.

4.5 in.lb.

14-1 AWG

14-4 AWG

22-12 AWG

15

62 in.lb.

30 in.lb.

4.5 in.lb.

14-1 AWG

14-4 AWG

22-12 AWG

20

62 in.lb.

120 in.lb.

4.5 in.lb.

14-1 AWG

14-2/0 AWG

22-12 AWG

25

88 in.lb.

120 in.lb.

4.5 in.lb.

14 AWG to 300kcm

14-2/0 AWG

22-12 AWG

30

88 in.lb.

275 in.lb.

4.5 in.lb.

14 AWG to 300kcm

4 AWG to 300kcm

22-12 AWG

40

88 in.lb.

275 in.lb.

4.5 in.lb.

14 AWG to 300kcm

4 AWG to 300kcm

22-12 AWG

50

88 in.lb.

275 in.lb.

4.5 in.lb.

14 AWG to 300kcm

4 AWG to 300kcm

22-12 AWG

60

221 in.lb.

500 in.lb.

4.5 in.lb.

6 AWG to 500kcm

2 AWG to 600kcm

22-12 AWG

 

 

Note:   Wire ranges provided indicate conductor sizes that the device terminal or lug will 

accept. Follow local and national codes for proper conductor sizing. 

 

  

 

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Summary of Contents for FRENIC-EcoPAK

Page 1: ...tric Corp of America FECA IN 106 122010 Information subject to change without notice Instruction Manual Non Bypass Panels FRENIC EcoPAK Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 2: ...al INR SI47 1225 E for further safety information Safety precautions are classified into the following two categories in this manual WARNING Failure to heed the information indicated by this symbol may lead to dangerous conditions possibly resulting in death or serious bodily injuries CAUTION Failure to heed the information indicated by this symbol may lead to dangerous conditions possibly resulti...

Page 3: ... minimize harmonics and provide transient voltage protection for the drive Control power transformer with primary secondary fusing Door mounted drive keypad with backlit LCD and LED displays for drive set up troubleshooting local operation control maintenance indication and operational indication Damper Control Output Contacts Built in communications user selectable between Modbus RTU Metasys N2 o...

Page 4: ...ed door on the enclosure CAUTION Refer to the nameplate label to determine the panel input voltage and current requirements prior to installation and wiring Refer to the nameplate label for the correct wiring diagram Elementary Drawing Sizing of field wiring conductors should be based upon the current ratings listed on the nameplate label Buy www ValinOnline com Phone 844 385 3099 Email CustomerSe...

Page 5: ... Away from direct sunlight Where the ambient temperature will remain between 10 C 14 F and 40 C 104 F Wall mount panels must be mounted on a non flammable heat resistant surface that is capable of supporting the weight of the panel Refer to the dimensional drawing that shipped with the panel for required clearances Routing of field wiring should be planned in coordination with choosing a mounting ...

Page 6: ...um insulation rating of 75 C Sizing of field wiring conductors should be based upon the current ratings listed on the nameplate label in accordance with local and national codes Refer to the wiring diagram that shipped with this panel and the torque table in this instruction manual Refer to the diagrams on the following pages for general component layout and for general routing of power input powe...

Page 7: ...Page 7 of 22 Wiring Overview cont d UL NEMA Type 1 UL NEMA Type 1 2 10Hp 208 230V 15 20Hp 208 230V 2 20Hp 460V 25 40Hp 460V Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 8: ...age 8 of 22 Wiring Overview cont d NEMA 12 Ventilated NEMA 12 Ventilated 2 30Hp 208 230V 40Hp 208 230V 2 40Hp 460V 50 75Hp 460V Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 9: ...ew cont d UL NEMA Type 1 UL NEMA Type 1 25 30Hp 208 230V 40 60Hp 208 230V 50 75Hp 460V 100 200Hp 460V NEMA 12 Ventilated 50 60Hp 208 230V 100 200Hp 460V Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 10: ...ns Damper Control output DMPRLY o CTB 1 2 o Used to control the position of a damper valve in coordination with drive operation Programmable Relay 1 output PRLY1 o CTB 3 4 for NO contacts rated for 1A 230VAC o Provides drive output signal Y2 which is user selectable Programmable Relay 2 output PRLY2 o CTB 5 6 for NO contacts rated for 1A 230VAC o Provides drive output signal Y3 which is user selec...

Page 11: ... 20 62 in lb 120 in lb 4 5 in lb 14 1 AWG 14 2 0 AWG 22 12 AWG 25 88 in lb 120 in lb 4 5 in lb 14 AWG to 300kcm 14 2 0 AWG 22 12 AWG 30 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG to 300kcm 22 12 AWG 40 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG to 300kcm 22 12 AWG 50 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG to 300kcm 22 12 AWG 60 221 in lb 500 in lb 4 5 in lb 6 AWG to ...

Page 12: ...12 AWG 40 62 in lb 120 in lb 4 5 in lb 14 1 AWG 14 2 0 AWG 22 12 AWG 50 62 in lb 120 in lb 4 5 in lb 14 1 AWG 14 2 0 AWG 22 12 AWG 60 62 in lb 120 in lb 4 5 in lb 14 1 AWG 14 2 0 AWG 22 12 AWG 75 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG to 300kcm 22 12 AWG 100 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG to 300kcm 22 12 AWG 125 88 in lb 275 in lb 4 5 in lb 14 AWG to 300kcm 4 AWG ...

Page 13: ...OC button on the drive keypad 3 Push the FWD button on the keypad to energize the drive Use the Up Down keys to change the drive speed as necessary 4 Check that the motor rotates in the correct direction To change refer to the Troubleshooting section in this manual 5 Measure and record motor FLA if required Allow motor to run at full speed for a sufficient time to insure panel mounted overloads ar...

Page 14: ...to a building automation system and controlled by remote signals If these signals are not available the panel can be set up to be operated locally Follow these steps to set the panel up for local operation 1 Set drive function code F01 to 0 2 Set drive function code F02 to 2 3 Set drive function code H96 to 3 The panel can now be operated directly using the drive keypad Buy www ValinOnline com Pho...

Page 15: ... panel to be operational If for some reason the drive parameters are reinitialized these parameters must be reset for correct panel operation Drive function codes F01 3 F02 1 F05 230 for 230V panels only default otherwise F11 nameplate output current F16 3 E01 1007 E02 1007 E03 1009 E20 55 E21 0 E22 0 E24 0 H09 4 H96 0 Drive Switches SW1 set to SINK SW5 set to V2 Buy www ValinOnline com Phone 844 ...

Page 16: ...2 Programming the FRENIC Eco Drive Also refer to Chapter 3 in the FRENIC Eco drive instruction manual INR SI47 1225 E for more information Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 17: ...ypad Pressing FUNC DATA saves the changes while pressing RESET discards the changes and both return to the previous menu The most frequently modified parameters can be accessed in the Quick Set menu item 0 on the programming menu screen All parameters can be accessed in the Data Set menu item 1 on the programming menu screen Recommended user set drive parameters These parameters are all in the FRE...

Page 18: ... Main power disconnect Drive keypad The FRENIC EcoPAK panel includes the following controls for remote operation and monitoring Analog speed reference input Analog monitor output Run input Enable input Drive Fault output Drive Run output Damper control output Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 19: ...eplacement fans out of warranty period and filter media refer to the following tables Filter Fan Size Manufacturer Part Number Manufacturer Part Number A Qualtek Fan S 09450 M 30 Orion OP109AP 11 1TB B Qualtek Fan S 09650 M 30 Orion OA172AP 11 1TB 208 230V NEMA 1 NEMA 12 HP Fan Size QTY Filter Size s QTY Fan Size QTY Filter Size s QTY 2 A 1 A 2 A 1 A 2 3 A 1 A 2 A 1 A 2 5 A 1 A 2 A 1 A 2 7 5 A 1 A...

Page 20: ...1 A 2 7 5 A 1 A 2 A 1 A 2 10 A 1 A 2 B 1 B 2 15 A 1 A 2 B 1 B 2 20 A 1 A 2 B 1 B 2 25 A 1 A 2 B 1 B 2 30 A 1 A 2 B 1 B 2 40 A 1 A 2 B 1 B 2 50 A 2 A 4 B 2 B 4 60 A 2 A 4 B 2 B 4 75 A 2 A 4 B 2 B 4 100 A 3 A 7 B 3 B 7 125 A 3 A 7 B 3 B 7 150 B 4 A B 8 4 B 4 A B 8 4 200 B 4 A B 8 4 B 4 A B 8 4 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Page 21: ...1 8 10 25 100 1 1 6 10 30 125 1 8 10 1 6 10 40 175 3 1 2 3 2 10 50 200 3 1 2 3 2 10 60 250 9 8 460V MAIN CPT CPT POWER PRIMARY SECONDARY HP Class J Class CC Glass 2 6 4 10 8 10 3 8 4 10 8 10 5 12 4 10 8 10 7 5 15 4 10 8 10 10 25 4 10 8 10 15 30 4 10 8 10 20 40 4 10 8 10 25 50 4 10 8 10 30 60 4 10 8 10 40 70 4 10 8 10 50 90 8 10 1 6 10 60 100 8 10 1 6 10 75 150 8 10 1 6 10 100 175 1 6 10 3 2 10 125...

Page 22: ...issues refer to the FRENIC Eco drive instruction manual INR SI47 1225 E Motor Rotation Problem Motor turns incorrect direction Solution Swap two of the three motor output connections Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com ...

Reviews: