Page 21 of 22
Maintenance
(cont’d)
Fuses
The
FRENIC-EcoPAK
panel has labels, located on the inside of the hinged door, which
list the correct size and type of fuses to be used for that panel. In the event that these
labels are damaged or missing, please refer to the tables below for replacement fuse
type and sizing:
208/230V
MAIN
CPT
CPT
POWER
PRIMARY SECONDARY
HP
Class J
Class CC
Glass
2
10
1
8/10
3
15
1
8/10
5
25
1
8/10
7.5
30
1
8/10
10
45
1
8/10
15
60
1
8/10
20
80
1
8/10
25
100
1
1 6/10
30
125
1 8/10
1 6/10
40
175
3 1/2
3 2/10
50
200
3 1/2
3 2/10
60
250
9
8
460V
MAIN
CPT
CPT
POWER
PRIMARY SECONDARY
HP
Class J
Class CC
Glass
2
6
4/10
8/10
3
8
4/10
8/10
5
12
4/10
8/10
7.5
15
4/10
8/10
10
25
4/10
8/10
15
30
4/10
8/10
20
40
4/10
8/10
25
50
4/10
8/10
30
60
4/10
8/10
40
70
4/10
8/10
50
90
8/10
1 6/10
60
100
8/10
1 6/10
75
150
8/10
1 6/10
100
175
1 6/10
3 2/10
125
200
1 6/10
3 2/10
150
250
4
8
200
350
4
8
Fuse Reference - Ferraz Shawmut series (type)
Main Power: AJT (Time-delay Class J)
CPT Primary: ATQR (Time-delay Class CC)
CPT Secondary: GGC (Fast Acting Glass)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com