3-20
Basic key operation
Before checking the running status on the drive monitor, set function code E52 to "2" (full-menu
mode).
(1) When the inverter is powered on, it automatically enters Running mode. In Running mode,
press the
key to enter Programming mode. The menu for function selection will be dis-
played.
(2) With the menu displayed, use the
and
keys to select "Drive monitoring" (
QRG
).
(3) Press
the key to display the desired code in the monitoring item list (e.g.
A
).
(4) Use
the and
keys to select the desired monitoring item, then press the
key.
The running status information for the selected item will appear.
(5) Press the key to return to the monitoring item list. Press the
key again to return to the
menu.
Table 3.11 Drive Monitoring Display Items
LED
monitor
shows:
Contents Unit
Description
A
Output
frequency
Hz
Output frequency before slip compensation
A
Output
frequency
Hz
Output frequency after slip compensation
A
Output
current
A Output
current
A
Output
voltage
V Output
voltage
A
Reference
frequency
Hz Reference
frequency
A
Running
direction
N/A
Displays the running direction currently being outputted.
F: forward; R: reverse, – – – –: stop
A
Running
status
N/A
Displays the running status in hex. format. Refer to "
Displaying
running status
" on the next page.
A
Load shaft
speed
(line speed)
r/min
(m/min)
The unit for load shaft speed is r/min and that for line speed is
m/min.
Display value = (Output frequency Hz before slip compensation)
u
(Function code E50)
appears for 10000 (r/min or m/min) or more. When
appears, decrease function code E52 data so that the LED
monitor displays 9999 or below, referring to the above equation.
A
PID process
command
N/A
The command is displayed through the use of function code E40
and E41 data (PID display coefficients A and B).
Display value = (PID process command)
u
(Coefficient A - B) + B
If PID control is disabled, "– – – –" appears.
A
PID feedback
amount
N/A
This value is displayed through the use of function code E40
data and function code E41 data (PID display coefficients A and
B).
Display value = (PID feedback amount)
u
(Coefficient A - B) + B
If PID control is disabled, "– – – –" appears.
Summary of Contents for Frenic Mini FRN001C1E-2U
Page 85: ...5 4 ...
Page 88: ...5 7 ...
Page 89: ...5 8 C codes Control Functions of Frequency ...
Page 92: ...5 11 J codes Application Functions y codes Link Functions ...
Page 167: ...8 6 8 3 Common Specifications ...
Page 168: ...8 7 ...
Page 171: ...8 10 8 5 External Dimensions 8 5 1 Standard models ...
Page 172: ...8 11 ...
Page 173: ...8 12 8 5 2 Models available on order EMC filter built in type ...
Page 174: ...8 13 ...
Page 192: ...MEMO ...
Page 193: ...MEMO ...
Page 194: ...MEMO ...
Page 196: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 06 F07 F07 00CM ...