8-3
8.1.2 Three-phase 400 V class series (
= A, C, E or U)
Item
Specifications
Type
(FRN_ _ _ _ C2S-4
)
0002
0004
0005
0007
0011
0013
0018
0024
0030
Applicable motor rating
(kW)
*1
0.4
0.75
1.5
2.2
3.7
(4.0)*
5.5
7.5
11
15
Applicable motor rating
(HP)
*1
1/2
1
2
3
5
7.5
10
15
20
Output Ratings
Rated capacity (kVA)
*2
1.3
2.3
3.2
4.8
8.0
9.9
13
18
22
Rated voltage (V)
*3
Three-phase, 380 to 480 V (with AVR function)
Rated current (A)
1.8
(1.5)
*4
3.1
(2.5)
*4
4.3
(3.7)
*4
6.3
(5.5)
*4
10.5
(9.0)
*4
13.0
18.0
24.0
30.0
Overload capability
150% of rated current for 1 min.
150% of rated current for 1 min or
200% of rated current
for 0.5 s (for the rated current given in
parentheses)
150% of rated current for 1 min
or
200% of rated current for 0.5 s
Rated frequency
(Hz)
50/60 Hz
Input Ratings
Phases, voltage,
frequency
Three-phase, 380 to 480 V, 50/60 Hz
Voltage and
frequency variations
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6
,
Frequency: +5 to -5%
Rated
current (A)
*7
(w/
DCR)
0.85
1.6
3.0
4.4
7.3
10.6
14.4
21.1
28.8
(w/o
DCR)
1.7
3.1
5.9
8.2
13.0
17.3
23.2
33.0
43.8
Required power
supply capacity
(kVA)
*8
0.6
1.1
2.0
2.9
4.9
7.4
10
15
20
Braking
Torque (%)
*9
100
50
30
20
DC braking
Starting frequency
*10
: 0.0 to 60.0 Hz,
Braking time: 0.0 to 30.0 s, Braking level: 0 to 100%
Braking transistor
Built-in
Applicable safety
standards
UL508C, EN 61800-5-1
Enclosure
IP20 (IEC 60529), UL open type (UL50)
Cooling method
Natural cooling
Fan cooling
Mass (kg)
1.2
1.3
1.7
1.7
1.9
3.1
3.1
4.5
4.5
Mass (lbs)
2.6
2.9
3.7
3.7
4.2
6.8
6.8
9.9
9.9
* 4.0 kW for the EU. The inverter type is FRN0011C2S-4E.
*1 Fuji 4-pole standard motors
*2 Assuming the rated output voltage as 440 V for three-phase 400 V series.
*3 Output voltages cannot exceed the power supply voltage.
*4 The load shall be reduced so that the continuous operating current is the rated current in parenthesis or less if
the carrier frequency is set to 3kHz or above or ambient temperature exceeds 40°C (104°F).
*6
2004)
:
3
-
61800
IEC
to
(Refer
67
(V)
voltage
average
phase
-
3
(V)
e
Min.voltag
-
(V)
voltage
Max.
(%)
unbalance
voltage
Interphase
If this value is 2 to 3%, use an optional AC reactor (ACR).
*7 Estimated value to apply when the power supply capacity is 500 kVA (inverter capacity x 10 when the inverter
capacity exceeds 50 kVA) and the inverter is connected to the %X = 5% power supply.
*8 Values to apply when a DC reactor (DCR) is used.
*9 Average braking torque to apply when the motor running alone decelerates from 60 Hz with the AVR control
being OFF. (It varies with the efficiency of the motor.)
*10 Available only for induction motor drive.