9-1
Chapter 9 LIST OF PERIPHERAL EQUIPMENT AND OPTIONS
The table below lists the main peripheral equipment and options that are connected to the
FRENIC-Mini. Use them in accordance with your system requirements.
For details, refer to the FRENIC-Mini User's Manual (24A7-E-0023), Chapter 6 "SELECTING
PERIPHERAL EQUIPMENT."
Name of
peripheral
equipment
Function and application
Main p
eriphe
ral e
quipme
nt
Molded case
circuit breaker
(MCCB)
Residual-current-
operated
protective device
(RCD)
/Earth leakage
circuit breaker
(ELCB)*
*
with overcurrent
protection
MCCBs are designed to protect the power circuits between the power control
board and inverter’s main terminals (L1/R, L2/S and L3/T for three-phase
power, L1/L and L2/N for single-phase power) from overload or short-circuit
which in turn prevents secondary disasters caused by the inverter
malfunctioning.
RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and
RCDs/ELCBs that satisfy the recommended rated current listed below.
■
kW rating
Power
supply
voltage
Applicable
motor
rating
(kW)
Inverter type
Recommended rated current (A) of
MCCB and RCD/ELCB
w/ DC reactor
w/o DC reactor
Three-
phase
200 V
0.1
FRN0001C2S-2A
5
5
0.2
FRN0002C2S-2A
0.4
FRN0004C2S-2A
0.75
FRN0006C2S-2A
10
1.5
FRN0010C2S-2A
10
15
2.2
FRN0012C2S-2A
20
3.7
FRN0020C2S-2A
20
30
5.5
FRN0025C2S-2A
30
50
7.5
FRN0033C2S-2A
40
75
11
FRN0047C2S-2A
50
100
15
FRN0060C2S-2A
75
125
Three-
phase
400 V
0.4
FRN0002C2
■
-4
5
5
0.75
FRN0004C2
■
-4
1.5
FRN0005C2
■
-4
10
2.2
FRN0007C2
■
-4
15
3.7
(4.0)*
FRN0011C2
■
-4
10
20
5.5
FRN0013C2
■
-4
15
30
7.5
FRN0018C2
■
-4
20
40
11
FRN0024C2
■
-4
30
50
15
FRN0030C2
■
-4
40
60
Single-
phase
200 V
0.1
FRN0001C2
■
-7
5
5
0.2
FRN0002C2
■
-7
0.4
FRN0004C2
■
-7
10
0.75
FRN0006C2
■
-7
10
15
1.5
FRN0010C2
■
-7
15
20
2.2
FRN0012C2
■
-7
20
30
Note 1) A box (
■
) in the above table replaces S (Basic type) or E (EMC filter
built-in type) depending on the enclosure
2) A box (
) in the above table replaces A, C, or E depending on the
shipping destination.
*4.0 kW for the EU. The inverter type is FRN0011C2S-4E.