9-2
Name of
peripheral
equipment
Function and application
Main p
eriphe
ral e
quipme
nt
Molded case
circuit breaker
(MCCB)
Residual-current-
operated
protective device
(RCD)
/Earth leakage
circuit breaker
(ELCB)*
*
with overcurrent
protection
■
HP rating
Power
supply
voltage
Applicable
motor
rating
(HP)
Inverter type
Recommended rated current (A) of
MCCB and RCD/ELCB
w/ DC reactor
w/o DC reactor
Three-
phase
200 V
1/8
FRN0001C2S-2U
5
5
1/4
FRN0002C2S-2U
1/2
FRN0004C2S-2U
1
FRN0006C2S-2U
10
2
FRN0010C2S-2U
10
15
3
FRN0012C2S-2U
20
5
FRN0020C2S-2U
20
30
7.5
FRN0025C2S-2U
30
50
10
FRN0033C2S-2U
40
75
15
FRN0047C2S-2U
50
100
20
FRN0060C2S-2U
75
125
Three-
phase
400 V
1/2
FRN0002C2S-4U
5
5
1
FRN0004C2S-4U
2
FRN0005C2S-4U
10
3
FRN0007C2S-4U
15
5
FRN0011C2S-4U
10
20
7.5
FRN0013C2S-4U
15
30
10
FRN0018C2S-4U
20
40
15
FRN0024C2S-4U
30
50
20
FRN0030C2S-4U
40
60
Single-
phase
200 V
1/8
FRN0001C2S-7U
5
5
1/4
FRN0002C2S-7U
1/2
FRN0004C2S-7U
10
1
FRN0006C2S-7U
10
15
2
FRN0010C2S-7U
15
20
3
FRN0012C2S-7U
20
30
Single-
phase
100 V
1/8
FRN0001C2S-6U
5
5
1/4
FRN0002C2S-6U
10
1/2
FRN0003C2S-6U
10
15
1
FRN0005C2S-6U
15
20