3-4
2. Power Supply Cable Connection
Power Supply Cable Connection
•
The power source must be within the allowable voltage fluctuation.
•
Use a power source with low noise between the cables or between the ground and the cable.
•
Use the thickest power supply cable possible to minimize drops in voltage, and twist.
•
Keep power supply cables away from high-voltage, large-current carrying cables.
Grounding
•
An independent earth pole must be used for the TS Series.
•
Use AWG20 to AWG14 size wiring for the grounding cable.
•
Set the grounding point near the TS Series to shorten the distance of grounding cables.
DANGER
Avoid applying excessive force to the power supply cable. This may lead to
unintentional disconnection of the cable and cause serious accidents such as electric
shock.
CAUTION
Be sure to establish a ground of the TS Series.
(The level of grounding resistance should be less than 100
Ω
.)
TS unit
Other
equipment
TS unit
Other
equipment
TS unit
Other
equipment
Independent grounding (best)
Shared grounding (good)
Cross grounding (prohibited)
D class grounding (ground
resistance of 100
Ω
or less)
D class grounding
(ground resistance
of 100
Ω
or less)
Summary of Contents for MONITOUCH TS Series
Page 1: ......
Page 10: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Product Outline ...
Page 43: ...2 26 6 LAN Connector TS1100i TS1070i Only Please use this page freely ...
Page 44: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation ...
Page 49: ...41 Coin type Lithium Battery 2 DIP Switches Handling of TS Series Components ...
Page 57: ...4 8 2 DIP Switches Please use this page freely ...
Page 58: ...51 Before Operation 2 Main Menu Screen 3 System Menu TS Series Operations ...
Page 102: ...5 44 3 System Menu Please use this page freely ...
Page 103: ...61 Error Messages 2 Troubleshooting Error Handling ...
Page 110: ...71 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance ...
Page 114: ...7 4 2 Warranty Policy Please use this page freely ...