20
・It transfers to the On-Bypass once, when the load is near less than 100%
after detecting the overload.
・When the input deviates from the range of bypass available, if manual bypass is
set, the UPS transfer Bypass with output cut within 10ms.
・The output of UPS might decrease when the big inrush current is connected.
4-1-2 On-HE
It is a mode that supplies a utility input to the load side through UPS.
MODE LED is turned off, and " On-HE " is displayed in LCD for this period.
Other states can be displayed with the ▲ button/▼ button. When the
power failure occurs, UPS transfers the On-Battery mode.
When the UPS load exceeds 100%, it is shown for ALARM LED to light,
and to have exceeded the UPS capacity.
・UPS transfers On-Battery when the utility input deviates from the HE input
range, when the HE mode. (When Input power is cut , the output cut by the
transition of On-HE ⇔ On-Battery is about 10ms.)
HE input range
Input voltage :Rated voltage±5%(Default)
Input frequenvy:±1Hz(Default)
* Input voltage/Input frequency range is possible to change by setting of
Chapter6
・When the load is over 110%, the output is cut after transition to On-Bypass.
・When the load is over 150%, the output is cut.
・If overload/internal abnormality occurs, the UPS transfer Bypass.
・It transfers to the On-Bypass once, when the load is near less than 100%
after detecting the overload.
4-1-3 On-Battery
When an abnormal input occured, UPS transfers On-Battery that does
the backup operation. UPS sounds an intermittent alarm for 2 seconds.
MODE LED blinks 0.5 seconds, and " On-Battery " is displayed in LCD for
this period. Other states can be displayed with the ▲ button/▼ button.
UPS returns to an On-Line mode or On-HE when the utility input power
returns.
Blinking BATTERY LED of UPS shows the low-battery warning. In
addition, the shutdown warning of 0.5 seconds blinking is generated
when advancing. UPS shuts down after it warns of the shutdown, and
the output is stopped.
・If overload/internal abnormality occurs, the output is cut.
・ In the case of the deterioration battery, UPS might shut down by not the
electrical discharge shutdown but the alarm. In this case, Autostart cann
’
t be
done after UTL return.
4-1-4 On-Bypass
When the overload is generated or the internal abnormality occurs, UPS
becomes On-Bypass. The alarm sounding and MODE LED blink every 2
seconds. Other states can be displayed with the ▲ button/▼ button.