38
it returns to the
“
Manual Bypass
”
item.
・When a utility input deviates from the Bypass Available, the transition of On-Line
-> On-Bypass have cutting time of output of about 10ms .
・On manual Bypass, when this setting is invalided, if a utility input deviates from
the Bypass Available, there is no transition of On-Bypass -> On-Line.
6-1-15 Voltage range of HE mode
Figure 6-16 Voltage range of HE mode
It changes into the
“
Voltage range of HE mode
”
display in pushing the
SET button. Push、
▲
button/
▼
button when you change the content
display. The content is changed when the SET button is pushed by the
content that changes and it moves to the next item display. Push the ESC
button when it returns to the
“
Voltage range of HE mode
”
item.
・When a utility input deviates from this setting range
HE mode : UPS transfer to On-Battery with output cut of moment.
Intelligent mode : UPS transfers to On-Battery with output cut of moment.
And if possible On-Line , UPS transfers to On-Line.
C O N F I G U R A T I O N
H E V O L T R A N G E
H E V O L T R A N G E
±
5 %
H E V O L T R A N G E
±
1 0 %
H E V O L T R A N G E
±
1 5 %
Factory
Setting
〆