46
7-4-3 Tower type EBM exchange
Attention
・Do the clearing work by the person who has experience and knowledge of
electric work. There is possible of the breakdown and the electric shock when
doing by the methods other than the following procedures.
Exchange EBM according to the following procedure.
1. Do the EBM exchange in the mode other than the On-Battery.
2. The breaker on the rear of EBM is turned off.
3. The battery cable on the rear of EBM is removed.
4. EBM is detached.
5. New EBM is fixed. The cable from UPS/EBM removed in rear of
new EBM is connected with the connector of new EBM.
6. The breaker on the rear of EBM is turned on.
7. When EBM is added, it is more similar. Above-mentioned the cable
from UPS becomes a cable from EBM.
The exchange of EBM becomes an exchange of not the internal battery
exchange but EBM units.
Figure 7-4 Tower type EBM exchange
・When EBM is exchanged or EBM is added, already exchange all EBM and an
internal battery under use. When a new battery and an old battery are
combined and used, The longevity of the battery is influenced by an old battery,
and the expected life of a new battery shortens.
・Make the UPS side a full charge about the exchange of EBM.
Caution
・Do not short-circuited, and do not take the battery apart. There is a possibility
of the electric shock, and injuring the burn etc.
・When the electrobath of the battery touches the skin and eyes, it is dangerous.
Flush it when having touched.
UPS
BATTERY CABLE
CONNECTOR COVER
EBM
BREAKER(EBM)
!
!