background image

 

– 9 – 

 

6-8

 

Alarm (Ch8)

 

Sets the detect conditions for each type of alarm.

 

6-9

 

Communication (Ch9)

 

Sets the communication conditions towards the host computer.

 

6-10

 

PFB (Ch10)

 

Changes settings to use valve control.

 

"

 

di1

 

" (di1)

DI-1 function 
selection

Sets the 
function of 
DI-1

0 (No function)

 

1 (Switchover between STBY ON/OFF)
2 (Switchover between Auto/Manual)
3 (Switchover between Local/Remote)

 

4 (No function)
5 (No function)
6 (Start AT (standard))
7 (Start AT (low PV))
8 (No function)
9 (No function)
10 (Ramp SV ON/OFF)
11 (Ramp SV HOLD)
12 (Ramp soak OFF)
13 (Ramp soak RUN/HOLD)
14 (No function)
15 (Latch release (all))
16 (Latch release (DO1))
17 (Latch release (DO2))
18 (Latch release (DO3))
19 (Latch release (DO4))
20 (Latch release (DO5))
21 (Start timer (DO1))
22 (Start timer (DO2))
23 (Start timer (DO3))
24 (Start timer (DO4))
25 (Start timer (DO5))
26 (SV No. + 1)
27 (SV No. + 2)
28 (SV No. + 4)
29 (PID No. + 1)
30 (PID No. + 2)
31 (PID No. + 4)
32 (No function)
33 (No function)
34 (No function)
35 (SV No.+1, PID No.+1)
36 (SV No.+2, PID No.+2)
37 (SV No.+4, PID No.+4)
38 (Pattern No.+1) 
39 (Pattern No.+2) 
40 (Pattern No.+4) 
41 (Soft start)
42 (Ramp soak RUN)
43 (Ramp soak HOLD)
44 

 

(Ramp soak RUN at DO1 startup)

 

45 

 

(Ramp soak RUN at DO2 startup)

 

46 

 

(Ramp soak RUN at DO3 startup)

 

47 

 

(Ramp soak RUN at DO4 startup)

 

48 

 

(Ramp soak RUN at DO5 startup)

 

0

 

(Note11)

 

"

 

di5

" (di5)

DI-5 function 
selection

Sets the 
function of 
DI-5

0 to 48

0

"

do1t

" (do1T)

Sets the DO1 
output event 
type

Sets the 
function of 
DO1

0 to 102

0

"

doP1

" (doP1)

Sets DO1 
option function

Assigns the 
four types of 
option 
functions in 
bit units

0000 to 1111

0000

(Note3)

"

do5t

" (do5T)

Sets the DO5 
output event 
type

Sets the 
function of 
DO5

0 to 102

0

"

doP5

" (doP5)

Sets DO5 
option function

Assigns the 
four types of 
option 
functions in 
bit units

0000 to 1111

0000

"

rmP

" (rMP)

ramp SV 
ON/OFF

Sets the 
ramp SV 
ON/OFF

oFF (ramp SV OFF)
on (ramp SV ON)

on

"

rmPL

" (rMPL)

Ramp SV- 
Decline

Sets the slope 
for a falling SV 
during ramp 
SV operations

0 to 100% FS

0°C

"

rmPh

" (rMPH)

Ramp SV- 
Incline

Sets the slope 
for a rising SV 
during ramp 
SV operations

0 to 100% FS

0°C

"

rmPU

" (rMPU)

Ramp SV- 
slope units of 
time

Sets the unit 
of time for the 
slope during 
ramp SV 
operations

hoUr (slope temperature/hour)
Min (slope temperature/min)

hoUr

"

Svt

" (SvT)

Ramp SV - SV 
display mode 
selection

Displays the 
SV during 
ramp 
operations or 
the SV goal 
value on the 
SV display

rMP (SV during ramp)
TrG (target SV)

rMP

"

[trL

" (CTrL)

Control 
methods

Allows you to 
select the 
control 
method.

Pid (PID control)
FUZY (Fuzzy PID control)
SELF (Self-tuning control)
Pid2 (PID2 control)

Pid

Sections 
5-1 to
5-8
(Note19)

Parameter
display symbol

Parameter 
name

Function

Setting range

Initial 
value

Remarks

RST

bit0 : output latch function
bit1 : error alarm function
bit2 : non-excitation output

 alarm function

bit3 : hold reset function

□□□□ 

RST

□□□□ 

bit0 : output latch function

bit1 :  error alarm function

bit2 : non-excitation 

output alarm function

bit3 : hold reset function

RST

"

PrCS

" (PrCS)

Control target

Allows you to 
select the 
control target.

SRV1 (Servo control 1)
SRV2 (Servo control 2)
PFB (Position feedback
control)

PFb/
Srv1 
(with 
PFB/
without 
PFB)

(Note16)

"

Stmd

" (STMd)

Start mode

Sets the 
operation 
mode when 
starting up

Auto (auto mode startup)
Man (manual mode startup)
Rem (remote mode startup)
STby (standby make startup)

AUTo

Parameter
display symbol

Parameter name

Function

Setting range

Initial 
value

Remarks

"

A1hY

" (A1hy)

ALM1 hysteresis

Sets the hysteresis 
for alarm output 1 
ON/OFF

0 to 50% FS

1°C

(Note3)

"

dLY1

" (dLY1)

ALM1 delay

Sets the delay 
before detecting  
alarm output 1

0 to 9999 [sec/min]

0(sec/
min)

"

dL1U

" (dL1U)

ALM1 delay time 
units

Sets the delay time 
units for alarm 
output 1

sec (second)
Min (minute)

sec

"

A5hY

" (A5hy)

ALM5 hysteresis

Sets the hysteresis 
for alarm output 3 
ON/OFF

0 to 50% FS

1°C

"

dLY5

" (dLY5)

ALM5 delay

Sets the delay  
detecting for alarm 
output 3

0 to 9999 [sec/min]

0(sec/
min)

"

dL5U

" (dL5U)

ALM5 delay time 
units

Sets the delay time 
units for alarm 
output 3

sec (second)
Min (minute)

sec

"

hb1

" (hb1)

HB alarm set value 
for CT

Sets the heater 
burnout alarm 
detection value for 
CT

0.0 to 50.0A

0.0A

(Note10)
(Note13)

"

hb1h

" (hb1h)

HB alarm 
hysteresis for CT

Sets the heater 
burnout alarm ON/
OFF hysteresis for 
CT

0.0 to 50.0A

0,5A

(Note10)
(Note13)

"

hS1

"

Load short-circuit 
alarm setting value 
for CT

Sets the heater 
load short-circuit 
alarm setting value 
for CT.

0.0 to 50.0A

0.0A

(Note10)
(Note13)

"

hS1h

"

Load short-circuit 
alarm hysteresis 
for CT

Sets the heater 
load short-circuit 
alarm ON/OFF 
hysteresis for CT.

0.0 to 50.0A

0.5A

(Note10)
(Note13)

"

lbTm

" (LbTM)

Loop break 
detection time

Sets the time 
before detecting a 
broken loop

0 to 9999 sec

0 sec

"

LbAb

" (LbAb)

Loop break 
detection range 
(°C)

Sets the 
temperature range 
before detecting a 
broken loop

0 to 100% FS

10°C

Parameter
display symbol

Parameter name

Function

Setting range

Initial 
value

Remarks

"

Stno

" (Stno)

ST No. setting

Sets the station 
number.

0 to 255 (0: 
unresponsive 
communication)

1

(Note17)

"

CoM

" (CoM)

baud rate/parity 
setting

Sets the baud 
rate and parity 
check

96od (9600 bps/odd)
96Ev (9600 bps/even)
96no (9600 bps/none)
19od (19200 bps/odd)
19Ev (19200 bps/even)
19no (19200 bps/none)

96od

(Note17)

"

S[[

" (SCC)

Communication 
permissions

Sets whether or 
not overwriting is 
possible from the 
master side (PC, 
etc.)

r (read only permission)
rW (read and overwrite 
permission)

rW

(Note17)

Parameter
display symbol

Parameter name

Function

Setting range

Initial 
value

Remarks

"

PGAP

" (PGAP)

PFB dead band

Sets the PFB dead 
band

0.0 to 100.0%

5%

(Note16)

"

trvL

" (TrvL)

Valve stroke time

Sets the full stroke 
time for the valve

5 to 180 sec

30 sec

(Note16)

"

[AL

" (CAL)

PFB input 
adjustment 
command

Adjusts the zero/
span for PFB input

0 (none/forcibly termination)
1 (zero adjustment)
2 (span adjustment)
3 (automatic adjustment)

-

(Note8)

Parameter
display symbol

Parameter 
name

Function

Setting range

Initial 
value

Remarks

RST

RST

Summary of Contents for PXG5

Page 1: ...errors or failures may be caused Periodic maintenance is recommended for continuous and safe use of this equipment Some parts installed on this equipment have a limited life and or may deteriorate with age The warranty period for this unit including accessories is one year if the product is used properly 2 Caution 2 1 Cautions when Installing Please avoid installing in the following locations Loca...

Page 2: ... relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportionate cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equip ment etc as relay output equipment are connected use of Z trap manufactured by Fuji Electric Device Technology Co Ltd is recommended in order to pr...

Page 3: ...orque of about 0 8 N m Do not attach anything to unused terminals Do not use relay terminals PC loader interface PXG9 TOP TOP 13 24 37 48 61 72 49 60 1 12 25 36 waterproof packing panel terminal screw M3 96 96 79 5 10 2 91 5 115 5 MAX t 6 2 31 32 33 34 35 36 7 8 9 1 2 3 4 5 6 10 11 12 mounting fixture fastening torque 0 15 N m 25 26 27 28 29 30 Panel thickness 1 to 8 mm PC loader interface 25 36 1...

Page 4: ...ance bulb input 33 34 35 36 Current voltage input Voltage mV input 33 34 35 36 Measurement value input 29 30 29 30 RSV2 input CT2 input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 DIO COM DI3 DI5 DI4 Digital input 25 26 27 28 29 30 DIO COM DI3 DI5 DI4 DO4 DO5 Digital input output 5 6 Power supply Note 3 Note 1 Note 2 50 60Hz 31 32 DI COM DI1 3 4 3 4 3 4 5 6 1 2 DI COM DI1 3 4 1 2 RS4...

Page 5: ...e SV display shows the input output values For more details on PASS PASS see 5 6 Key Lock and Password page 6 For more details on Note in the Remarks column see 6 Parameter List page 6 5 3 Basic Operations Pressing the key or the key switches between modes Pressing in monitor mode or setup mode allows you to choose menu items Changing SV set values Changing MV control output values 5 4 Operations ...

Page 6: ...channel and the authority of passwords 1 to 3 Note When FEFE FEFE is entered as PASS PASS all of the channels OPE ch to DSP ch can be displayed and set This super password function is useful when you forget the set passwords oPE ch PAS1 permissions PASS PAS1 PAS2 permissions PASS PAS2 PAS3 permissions PASS PAS3 Pid ch PLT ch PrG ch Mon ch SET ch SyS ch ALM ch CoM ch PFb ch PAS ch dSP ch Password l...

Page 7: ... Sets the integration time 0 to 3200 sec 240 sec d7 d7 Differential time 7 Sets the differential time 0 0 to 999 9 sec 60 0 sec hyS7 hyS7 ON OFF control hysteresis 7 Sets the hysteresis when using the ON OFF control 0 to 50 FS 1 C oL7 CoL7 Cooling proportional band 7 Sets the cooling proportional band 0 0 to 100 0 1 0 Note4 Parameter display symbol Parameter name Function Setting range Initial val...

Page 8: ...SV input filter Sets the time constant for the RSV input filter 0 0 to 120 0 sec 0 0 sec Note1 fixed at 0 8bit PV input underflow 9bit PV input overflow 10bit underrange 11bit overrange 12bit RSV underrange 13bit RSV overrange 14bit range setting error 15bit EEPROM error 0bit PFB input underflow 1bit PFB input overflow RST RST RST RST 1r C1r OUT1 range Sets the range of the control output OUT1 0 5...

Page 9: ...r alarm function bit2 non excitation output alarm function bit3 hold reset function RST PrCS PrCS Control target Allows you to select the control target SRV1 Servo control 1 SRV2 Servo control 2 PFB Position feedback control PFb Srv1 with PFB without PFB Note16 Stmd STMd Start mode Sets the operation mode when starting up Auto auto mode startup Man manual mode startup Rem remote mode startup STby ...

Page 10: ...ou will need to run auto tuning to set the PID parameter when using fuzzy control Setting fuzzy PID control Display Parameter name Function Setting range Initial value Remarks PAS1 PAS1 Password1 setup Sets password 1 0000 to FFFF 0000 PAS2 PAS2 Password2 setup Sets password 2 0000 to FFFF 0000 PAS3 PAS3 Password3 setup Sets password 3 0000 to FFFF 0000 Display Parameter name Function Setting rang...

Page 11: ...re changing back to self tuning 1 Display the system menu SYS Ch 7 2 Display the control parameter CTrL and choose PID2 Pid2 3 Press the key to set the value dead time t process value tuning SV lag time suppress overshoot ON OFF control equipment power t SV process value control loop close close open PV At set value Behavior Function oFF Stop Finish Stops or finishes auto tuning on Normal type The...

Page 12: ...et CAL to 3 in step 3 above This setting will automatically open and close the valve to adjust it auto matically Caution To manually adjust the valve carry out step 1 through step 7 as written above If the valve is not connected or connected incorrectly it can still be adjusted but will not achieve accurate results There is no open circuit judgment function for the valve opening feed back signal C...

Page 13: ...SV 1 2nd ramp 3rd ramp 4th ramp SV 2 SV 3 SV 4 Dis play Function Name Behavior ON OFF Judgment conditio n 0 No function Nothing happen 1 Switchover between standby ON OFF Switches between standby on and off Standby Standby Cancel Edge 2 Switchover between auto manual Switches between auto and manual control output Manual Auto Edge 3 Switchover between local remote Switches between local and remote...

Page 14: ...ting DO1 to DO5 Function Wire burnout circuit alarm 41 Loop break alarm 1 44 Heater burnout alarm 1 Wire break short circuit alarm 47 Load short circuit alarm Dis play Function Name Behavior ON OFF Judgment conditio n Settings complete Using them as alarms 1 to 31 Using them as events 35 to 102 or timers 32 to 34 1 Setting the System Menu 2 Setting the Alarm Menu 3 Setting the alarm menu page 14 D...

Page 15: ...2 Display hysteresis 1 A1hY and set the hysteresis 3 Display delay time 1 dLY1 and set the delay 4 Display delay time units 1 dL1U and set the units to minutes or seconds 5 Set the values for alarm 2 to alarm 5 as necessary 6 Press the key to set the value 1 Display the operation menu oPE Ch1 2 Set the alarm 1 set value AL1 or AL1L and AL1H The parameters displayed will vary according to the type ...

Page 16: ...time SFTM and set the time 4 Press the key to set the value 5 Turn off the power once and then re start the controller to begin soft start When the soft start function is turned on the lower display will alternate show ing SoFT and SV Note Do not use auto tuning at the same time 1 Display the setup menu SET h 6 2 Display FALT output 1 set value FLo1 and set the output value For dual control set FL...

Page 17: ...alue 1 Display the operation menu oPE Ch1 2 Display the selected PID number PLn1 and choose the PID No 3 Press the key to set the value 1 Display the palette menu PLT Ch 3 2 Display max selected PID number PL1M and set the PID number by choosing it with the user key 3 Display the user key function setting UKEy and set it to PID selection function 4 On the PV SV display pressing the user key will s...

Page 18: ... 7 and STbY is ON Normal control The controller does not have to be restarted Parameters may not be displayed q Check the settings of dP01 to dP30 w Check the password function Normal control The controller does not have to be restarted Input type Measurement range C Measurement range F Smallest input increment C Input code Resistance bulb JIS IEC Pt 100Ω 0 to 150 32 to 302 0 1 1 0 to 300 32 to 57...

Page 19: ...thout hold alarm may turn ON when starting up Caution When alarm action code is changed alarm set value may also become dif ferent from previous settings When alarm action type code is changed turn off the power once and then re start the controller before starting control Aln AL1 to AL5 show the alarm set values ALnh AL1h to AL5h show the alarm set values ALnL AL1L to AL5L show the alarm set valu...

Page 20: ... mV input voltage input current input 0 3 FS 1digit Indication resolution 0 3 FS or less Digital Output Relay contact output DO1 to DO3 1a contact 220V AC 30V DC 3A resistance load Transistor Output DO4 DO5 Open collector 30V DC 100mA max 2 contacts Judged ON 1V DC or less Digital input Contact or Transistor type Max 5 inputs 30V DC 3mA 1 input Judged ON 1kΩ or less contact or 5V DC or less transi...

Reviews: