1 - 19
Electrical Wiring
Connects the cable for power supply to TB1 on the rear side of UGx20.
Wiring
7
Insulation transformer
or
Stabilized transformer
1.25mm
2
Power Supply
twisted
to UG520/UG420
When TB1 is used for wiring, refer to the following table.
The power source used must be within the allowable voltage fluctuation.
Use a power source with low noise between the cables or ground and the cable.
Use as thick a power cable as possible to minimize any drop in voltage.
Keep cables of 100V AC and 24V DC sufficiently away from high-voltage, large-current cables.
Notes on Usage of UG520/UG420 100-200V AC Specifications
Generally, an isolating transformer improves noise resistance. However, if the display unit is far away
from the secondary port of the transformer and noise gets mixed in, an isolating transformer becomes
unnecessary.
If any power voltage fluctuation caused by noise is expected, it is recommended that a voltage stabilizer
be used.
Screw Screw Size
M3.5
Torque (N • m)
Clamp Terminal (Unit : mm)
0.5
7.0MAX
7.0MAX
M3.5
0.5
8.0MAX
8.0MAX
Type
UG320/UG221/UG220
UG520/UG420
24V DC
(
+
)
(-)
TB1
Power supply
24V
±
10% DC
Earth
Power supply
100-200VAC
L
N
NC
TB1
Earth
CN2
C
N
1
MJ2 MJ1
DC24V
(+)
(-)
CN2
MJ1
MJ2
CN
1
100-
240VAC
L
N
NC
24VDC
Power supply
24V
±
10% DC
+
-
NC
TB1
Earth
Type : 100-200V AC
Type : 24V DC
UG320/UG221/UG220
UG520/UG420
7 Wiring
Caution
•
Do not remove the dust-proof seal till you finish wiring in the panel. If the seal is removed, conductor chips or other
foreign matter may enter the device to cause failure.
•
When you finished wiring in the panel, be sure to remove the dust-proof seal.