1 - 41
Signal
UG00P-DI
UG port
FG
+SD
-SD
+RD
-RD
SG
*
Use twist shielded cable.
Signal
Pin No.
+RxD
+TxD
+DSR
+DTR
1
2
3
4
5
SG
7
-RxD
15
-TxD
16
-DSR
17
-DTR
18
20
21
Signal
FG
+SD
-SD
+RD
-RD
SG
RD terminal resistance
(ON)
RD/SD terminal resistance
(ON)
RD/SD terminal resistance
(ON)
Signal
FG
+SD
-SD
+RD
-RD
SG
POD + UG00P-TC
POD + UG00P-TC
POD + UG00P-TC
Signal
FG
+SD
-SD
+RD
-RD
SG
RD terminal resistance
(ON)
RD/SD terminal resistance
(ON)
Signal
FG
+RxD
-RxD
+TxD
-TxD
SG
Link unit
Signal
FG
+SD
-SD
+RD
-RD
SG
RD/SD terminal resistance
(ON)
Signal
FG
+SD
-SD
+RD
-RD
SG
*
Use twist shielded cable.
POD + UG00P-TC
POD + UG00P-TC
POD + UG00P-TC
16 Connection
When multiple POD are connected to a link unit of PLC, use the terminal converter (UG00P-TC), the
optional equipment made by Fuji Electric. Co., Ltd. for RS-485 connection.
•
Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.
•
Short-circuit bRD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.
When multiple POD are connected directly to MITSUBISHI’s QnA CPU port, the optional equipment,
UG00P-DI is required. Also, the use of the optional cable, MB-CPUQT which is to connect UG00P-TC on
POD side to UG00P-DI on QnA CPU port side, is recommended.
•
Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.
•
Short-circuit bRD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.
*
An n-to-1 system can be also configured using optional interface units (UG03I (02I)-S, -T, -J, -E(2), -C, or -P).
For the details, refer to the User’s Manual of each optional interface unit.
Summary of Contents for UG220H Series
Page 270: ...Appendix Ladder Transfer Function...