background image

2 - 109

KEYENCE PLC • 2

(KZ-A500)

41

41 KEYENCE PLC 

 2

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

CPU modular port of KZ-A500

Link Unit KZ-L10

Set the port with the port setting switch, the terminating resistance with

terminator, and the baud rate/data bit/parity/stop bit with SET B dip switches.

For further information, refer to the communication specifications of KZ-L10.

PLC

Link Unit

Wiring Diagram

KZ-A500

Port 2
 

RS-232C [Wiring Diagram 3]

 

RS-422 [Wiring Diagram 4]

KZ-L10

CPU Modular Port

Port 1
 

RS-232C [Wiring Diagram 2]

Select PLC Type

MITSUBISHI

A series link

KZ-A500

CPU

RS-232C [Wiring Diagram 1]
RS-422   Cable made by KEYENCE [ KZ-C20 ] 
 

+ Cable made by Fuji [ UG200C-M ]

9600bps

Odd

8

ON for RS-422

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Terminal Resistor

Item

Setting of PLC

9600bps

0

Port

0

 Odd

8

1

*

 1

*

1 In case of RS-422, the baud rate is fixed at 9600bps.

Comm. Parameter of POD

19200bps

Even

ON for RS-422

Baud Rate

Parity

Transmission

Code

Data Length

Stop Bit

1

Terminal Resistor

Item

Setting of PLC

19200bps

0

Port

0

 Even

7

1

Comm. Parameter of POD

Summary of Contents for UG220H Series

Page 1: ...FEH352c USER S MANUAL HARDWARE TYPE UG520H x UG420H x UG320H x UG221H x UG220H x FUJI UGx20 SERIES PROGRAMMABLE OPERATION DISPLAY...

Page 2: ...s interface UG Series Manual Describes the procedures forcommunication OPCN 1 Communications FEH358 with PLCs using the optional OPCN 1 interface UG Series Manual Variable Describes the variable name...

Page 3: ...at may threaten human life or to damage the system such as switches to be used in case of emergency Please design the system so that it can cope with malfunction of a touch switch Turn off the power s...

Page 4: ...ive dust salt and metallic particles are present Avoid installing the unit in a location where vibration or physical shock may be transmitted Equipment must be correctly mounted so that the main termi...

Page 5: ...the same time read the manual for the counterpart unit and handle the error correctly Switch resolution of the POD UG20 series is determined by the analog type resistance film Do not press two or more...

Page 6: ...0 Siemens S7 300 400 MPI Modicon Modbus RTU Others contents check November 2002 FEH352b Third edition The following PLC model is added SAIA PCD MOELLER PS4 Telemecanique TSX Micro Automationdirect Dir...

Page 7: ...log RGB Input 1 34 16 Connection 1 37 17 Operation of POD Main Menu 1 42 18 Function Switches 1 59 2 Connection to Link Units 1 FUJI PLC 1 2 1 2 FUJI PLC 2 2 4 3 FUJI PLC 3 2 6 4 FUJI PLC 4 2 8 5 FUJI...

Page 8: ...PLC 2 125 48 YAMATAKE PLC 2 126 49 TAIAN PLC 2 128 50 SAIA PLC 2 130 51 MOELLER PLC 2 132 52 Telemecanique PLC 2 133 53 Automationdirect PLC 2 134 54 VIGOR PLC 2 137 55 DELTA PLC 2 139 56 BALDOR PLC...

Page 9: ...Dimensions and Panel Cut out 6 Mounting Procedure 7 Wiring 8 Specifications 9 Serial Connector CN1 10 Setting of Dip Switches 11 Modular Jack 1 2 12 Bar Code Reader Interface 13 Printer Interface CN2...

Page 10: ...sonal computer It can be used widely in various fields 4 Macro Function With this function UGx20 series can make programs which previously had to be produced by PLC 5 Multi Window Function Up to three...

Page 11: ...nges 4 Avoid direct sunlight 0 to 50 C 50 40 30 20 10 0 YOUZAI Fan Vent 5 Never install POD in a place where impacts or vibrations may be transmitted 6 Avoid any place in which there is the possibilit...

Page 12: ...the unit to strong impacts 3 Tighten mounting screws with the following torques Note Never fasten these screws too tightly otherwise the cover of POD may be deformed 4 Securely fasten and lock every...

Page 13: ...l Computer PC During operation Link communication RS 232C RS 422 Creating screens Universal purpose computer During operation Universal serial communication RS 232C RS 422 Link Unit Transferring scree...

Page 14: ...LCD L Monochrome LCD White mode UG220H Touch Panel Specifications D Matrix sw type None Analog sw type Power requirements 4 24V DC Interface specifications C Serial Link Unit Communication Other inter...

Page 15: ...y Memory card None Standard Outside recorder M Memory card interface Power requirements 1 100 to 200V AC 4 24V DC Interface specifications C Serial Link Unit Communication Other interfaces can be supp...

Page 16: ...ional by User 3 1 Type UG220 UG420H S UG320 UG221 UG520H V UG420H V UG420H T 2 UG00P D4 UG221P D4 UG00P SR UG221P SR Memory Card A SRAM card or FPROM card can be used for the memory card The following...

Page 17: ...mm A 12 1 inch display Peripheral Equipment The following options are available for using UGx20 series more effectively UG00S CWV3 Panel Editor for Windows98 NT4 0 Me 2000 XP Application software for...

Page 18: ...UG00P MSE Memory Card Editor Application software for editing data stored in a memory card For Windows 98 Me NT 4 0 2000 XP UG00P TC Terminal Converter Used for connection between a UGx20 and a PLC a...

Page 19: ...e MITSUBISHI s ACPU QnACPU FXCPU programmer This can improve operability of the ACPU QnACPU FXCPU programmer that is directly connected UGx20P PS x 2 UG220 UG221 3 UG320 4 UG420 5 UG520 Protection She...

Page 20: ...N1 for PLC RS 232C RS 422 7 CN2 for printer 8 Dip switches 9 MJ1 2 for data transfer for temperature controller for bar code reader for UG00P MR and for UG00P U2 option 10 for UG00P D4 option 11 for U...

Page 21: ...ting holes for fixtures 2 Display 3 Function keys Refer to P1 59 4 Power lamp 5 AC power supply DC power supply 6 CN1 for PLC RS 232C RS 422 7 CN2 for printer 8 Dip switches 9 MJ1 2 for data transfer...

Page 22: ...anel Cut out 5 Dimensions of UG220 Panel Cut out of UG220 131 174 0 5 0 0 5 0 Unit mm CN2 CN1 MJ2 MJ1 173 6 182 5 117 2 138 8 88 4 130 8 45 5 Top View Unit mm Rear View Front View Side View 5 Dimensio...

Page 23: ...of UG221 Panel Cut out of UG221 131 174 0 5 0 Unit mm 0 5 0 F1 F5 F4 F3 F2 unless the optional unit is mounted Do not remove this seal CN1 MJ1 MJ2 CN2 24V DC Unit mm 130 8 138 8 182 5 4 47 3 6 Side Vi...

Page 24: ...ensions of UG320 Panel Cut out of UG320 165 5 220 5 Unit mm 0 5 0 0 0 5 CN2 MJ2 MJ1 CN1 TB1 DC24V 220 230 160 175 121 165 60 1 6 Unit mm Top View Rear View Front View Side View 5 Dimensions and Panel...

Page 25: ...211 240 158 215 2 76 3 16 Unit mm Top View Front View Side View Rear View CN2 MJ1 MJ2 CN1 100 240VAC L N NC 216 2 289 Unit mm 0 5 0 0 0 5 Dimensions of UG420 Panel Cut out of UG420 5 Dimensions and P...

Page 26: ...13 Unit mm 0 5 0 0 0 5 Dimensions of UG520 Panel Cut out of UG520 312 334 247 270 185 245 2 79 8 16 Unit mm Front View Side View Rear View Top View CN2 MJ1 MJ2 CN1 100 240VAC L N NC 5 Dimensions and P...

Page 27: ...series 4 pcs 3 The waterproof packing mounted on the UG221 main unit shall come in close contact with the mounting panel so that it is surely caught between the mounting panel and UG221 Mounting panel...

Page 28: ...the display unit is far away from the secondary port of the transformer and noise gets mixed in an isolating transformer becomes unnecessary If any power voltage fluctuation caused by noise is expect...

Page 29: ...r place the communication cable with electric circuits Never bundle these cables together with other wires in ducts or electric boxes using cord locks Although it is tempting to bundle all the cables...

Page 30: ...0 0 5 0 0 5 0 24V DC 24V 10 DC 10ms or less 10W or less 15A 1ms 20W or less 15A 1 5ms DARK GREY PC ABS DARK GREY PC ABS 1 including 4mm the size of boss for communication unit 2 equivalent to the Muns...

Page 31: ...ting oil or no organic solvent to cling to the unit No corrosive gas Vibration frequency 10 to 150Hz Acceleration 9 8m s2 Single amplitude 0 075mm 3 directions of X Y and Z one hour Pulse shape Sine h...

Page 32: ...Cold cathode rectifier which can be exchanged by a user By function switches only in case of STN type Approx 50 000h The lamp is lit when the power is supplied Display Device Resolution W H dots Dot P...

Page 33: ...on Specifications All the UGx20 series 1 4 size 8 8 dots 1 byte 8 16 dots 2 byte 16 16 dots or 32 32 dots Enlarge W 1 to 8 H 1 to 8 Lines line continuous lines box parallelogram polygon Circles circle...

Page 34: ...r of memory settings is limited 3 Set reset momentary alternate to light possible to press a function switch and a display switch at the same time With UG221 2 switches on the display can be pressed a...

Page 35: ...ouch Panel Specifications All the UGx20 series Specifications Analog 1024 W 1024 H Matrix type UG221 20 W 12 H pcs Resistance film form Use of one million times or more Item Serial Interface for conne...

Page 36: ...st to send RS 232C CS clear to send Not used Not used Use prohibited Use prohibited Not used Not used Not used Not used Not used Not used Not used 18 19 CS CS RS 422 CS receive data RS 422 CS receive...

Page 37: ...RD RD SD FG SD SG set to top 4 wire connection UG00P TC CN1 RS 422 In case of RS 422 SD and SD and RD and RD form a pair Use SG if possible Connect the shielded cable to pin No 1 or the connector case...

Page 38: ...ster Temperature controller communication by connection of RS 485 Card Recorder UG00P MR option is used Serial Extension I O UG00P U2 option is used Terminal POD connected with UG Link by connection o...

Page 39: ...are available in the following hardware version or later of POD As for UG220 UG221 any version can be used UG520H V 4 UG520H S 3 UG420H V 5 UG420H T 5 UG420H S 4 UG320H 7 Editor Transferring Use modu...

Page 40: ...In case of using the bar code reader which uses the CTS and RTS control the bar code reader may not work normally without jumping RTS and CTS The output power supply 5V is max 150mA Refer to the previ...

Page 41: ...l panel printer made by CBM Corporation The screen copy cannot be printed out CN2 MJ1 MJ2 CN 1 100 240VAC L N NC to Printer Half pitch 36 pins Centronics 13 Printer Interface CN2 24VDC TB1 CN2 UG220 t...

Page 42: ...V and UG420H T V Video Interface of UGx20 BNC Video Display Specifications Display Color 262 144 colors Input Channel 4 Channels Signal Form NTSC type PAL type Video Input 1 0Vp p 75 ohm unbalance Di...

Page 43: ...long is used to connect between connector CN3 of UG420H TC and the personal computer the screen image may be blurred due to noise To prevent noise it is recommended to mount a ferrite core 1 15 5 6 1...

Page 44: ...Modular dialog box of System Setting When you want to display the symbols for DOS V personal computer on the POD send the coordinate output of the touch panel to the DOS V personal computer via the M...

Page 45: ...ting will take effect when the personal computer is started the next time Notes 1 It is impossible to change over to the Main Menu screen from the Windows screen displayed on the POD 2 The Hardware se...

Page 46: ...radley GE Fanuc TOSHIBA SIEMENS SHINKO SAMSUNG KEYENCE LG FATEK IDEC MODICON TAIAN Models MICREX F series FLEX PC series FLEX PC COM AnA N U series QnA series QnH Q series A Link Net10 FX series A prt...

Page 47: ...er 2002 the PLCs supported are as follows All the PLCs which are usable for 1 1 communi cation will be supported For the I F driver the Multi Link 2 is supported by the version of 1 100 or later scree...

Page 48: ...LG MASTER KxxxS CNET Not provided LG GLOFACNET Not provided FANUC Power Mate Not provided FATEK AUTOMATION FACON FB series Provided IDEC MICRO3 Provided MODICON Modbus RTU Depends on the model YAMATA...

Page 49: ...C series CV series JW series JW100 70H COM Port JW20 30 COM Port HIDIC H MEWNET FA500 FA M3 FA M3R Memobus CP9200SH MP900 TOYOPUC T series S7 200 PPI SELMART SPC series SECNET MASTER K500 K1000 run s...

Page 50: ...C the optional equipment made by Fuji Electric Co Ltd for RS 485 connection Set the dip switch SW1 of UG00P TC as 2 wire connection when the UG00P TC terminal converter is used Short circuit between R...

Page 51: ...nformation Screen Data Information Size Size PLC Type MITSUBISHIAnA N U series Comment Error Stop Time Out 0 50 sec Retry 3 Connection 1 1 Baud Rate 19200 Signal Level RS232C Data Length 7 PLC Stat No...

Page 52: ...i o n P a r a m e t e r M e m o r y C a r d Main Menu Screen Data Size 786432 Error Stop Time out 0 50 sec Retry 3 Editor MJ1 Own Stat No 1 V6 Total 2 Retry 10 Comm Param Comm Param Multi Link Network...

Page 53: ...CN1 MJ1 RS232C RS485 MJ2 SYS F 1 F 2 F 3 F 4 F 5 Main Menu Printer Check Switch Check Serial Test C E D B A Press the I O Test switch 1 2 2 4 3 0 I O T e s t C o m m u n i c a t i o n P a r a m e t e...

Page 54: ...p turns on when the same switch as above is pressed ask the advice of your distributor Test of CTS RTS Check the signals CTS and RTS 1 Jump pins 4 RTS and 5 CTS of CN1 2 The test is OK if the CTS lamp...

Page 55: ...RD 1 Jump each pin 12 and 24 13 and 25 of CN1 2 The test is OK if the OK lamp turns on when the Self Loop Test switch is pressed If the NG lamp turns on when the same switch as above is pressed ask t...

Page 56: ...side of UG00C T to MJ1 or MJ2 ADP25 9 side of UG00C T to CN1 2 The test is OK if the OK lamp turns on when the Self Loop Test switch is pressed If the NG lamp turns on when the same switch as above i...

Page 57: ...essed area changes into white The white color means that the switch reacts to the touch normally Pressing the F4 switch leads to the previous I O Test screen Pressing the F5 switch deletes all the whi...

Page 58: ...F 4 F 5 F 6 F 7 SYS F 1 F 2 F 3 F 5 F 6 F 7 F 4 The test is OK when the F 4 lamp is lit Press the F4 switch SYS F 1 F 2 Main Menu Switch Check Check Main Menu Main Menu System Information System Infor...

Page 59: ...menu of the Memory Card screen on POD The Memory Card screen is displayed Press the Memory Card switch Memory Card I O Test Main Menu Memory Card Transfer Display Card Display Card Display Card Start...

Page 60: ...Display Card Start Cancel Screen Data I F Driver Font Data UG Program Data Selection Modular Jack MJ1 Memory Card Socket Port Selection Sys Program Version Font Data Version I F Driver Version Screen...

Page 61: ...card is not inserted Or in case of trying to write data into a memory card when inserting FLASH ROM type memory card Cannot write the data into a memory card because the data size in POD is larger tha...

Page 62: ...ud Rate 19200 Signal Level RS 232C Data Length 7 PLC Stat No 0 Stop Bit 1 Parity Even Send Delay 0msec Error Stop Time Out 0 50 sec Retry 3 1998 5 5 07 23 30 FONT VER 1 000 01 020 1 000 JAPANESE 32 I...

Page 63: ...ng 2 Horizontal 31180 Hz Vertical 59 Hz Please refer to the manual Hardware BIOS Screen ROM PCI ISA BIOS 2A69KA1E COMS SETUP UTILITY AWARD SOFTWARE INC CPU SOFT MENU II STANDARD CMOS SETUP BIOS FETURE...

Page 64: ...ndows screen displayed adjust with switches F 1 to F 6 When adjustment is completed press the SYSTEM switch to return to the RGB Adjust screen Main Menu RGB Adjust Adjust Adjust Clear Save Setting 1 S...

Page 65: ...s no RGB input when the cable is not connected the mode cannot be changed over to RGB display mode When bit 12 of read area n 1 is set to 1 the mode is changed over to RGB display mode the moment RGB...

Page 66: ...cassette in the present screen data type 2000 6 26 14 38 51 Setting for SRAM cassette When the optional SRAM cassette UG00P SR UG221P SR is installed in the POD main unit it is possible to adjust the...

Page 67: ...SRAM cassette in the present screen data type 2000 6 26 14 38 51 Formatting the SRAM cassette When you changed the setting of SRAM cassette area be sure to format the SRAM cassette SRAM cassette can...

Page 68: ...itches F1 F7 are defined for the purpose of the user The data of these function switches is allocated to the memory area of PLC Function of F1 F5 when the switch menu is displayed F1 Mode This switch...

Page 69: ...WA PLC 1 23 YASKAWA PLC 2 24 TOYOPUC PLC 25 Koyo PLC 26 Allen Bradley PLC 1 27 Allen Bradley PLC 2 28 GE Fanuc PLC 1 29 GE Fanuc PLC 2 30 TOSHIBA PLC 31 TOSHIBA MACHINE PLC 32 SIEMENS PLC 1 33 SIEMENS...

Page 70: ...p Bit 1 Terminal Resistor at Receiver Item Setting of PLC 0 19200bps Even 7 1 Comm Parameter of POD Provided for RS 485 1 Asynchronous non protocol by command fixed 3 Asynchronous non protocol by comm...

Page 71: ...area cannot be specified for switch memory or lamp memory To access the S area use word operation switch Specify the step number to be turned ON by the operational expression for word operation switc...

Page 72: ...is order Example To specify W30 2 Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs Wiring The following is a diagram to s...

Page 73: ...number to assign indirect memory for macro programs To set an indirect memory using a macro specify the CPU No using the extended code Indirect memory setting by macro is not available for input I or...

Page 74: ...luenced by noise attach a ferrite core TDK ZCAT2032 0930 is recommended to both the ends of the cable D sub 25pin Male FG RD RS CS SG 1 3 4 5 7 SD 2 PLC D sub 9pin Male RD SD ER SG DR 2 3 4 5 6 RS CS...

Page 75: ...emory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs To set an indirect memory using a macro specify the CPU No using the extended cod...

Page 76: ...e core is attached to the cable 1 000 V Fully consider the influence of noise on the cable when routing it on the board and in the unit Route the cable apart from the power lines The longer the commun...

Page 77: ...iagram 1 RS 485 Wiring Diagram 2 NJ Series NJ T FLEX PC Series PLC Select PLC Type NB RS1 RS 232C Wiring Diagram 1 RS 485 Wiring Diagram 2 NB Series 1 Wiring Diagram Link Unit Port Transmission Contro...

Page 78: ...l Use TYPE number to assign indirect memory for macro programs Standard Memory TOYOTA Ver TYPE Remarks D data register D 0 W link register R 1 M internal relay M 2 WM as word device L latch relay K 3...

Page 79: ...2C Wiring Diagram 1 RS 485 Wiring Diagram 2 D sub 25pin Male FG RD RS CS SG 1 3 4 5 7 SD RD SD 2 RS CS DR PLC 2 3 4 5 6 SG CD 7 8 D sub 25pin Male POD CN1 Use twist shielded cables D sub 25pin Male FG...

Page 80: ...memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs RS 422 UG200C N FLEX PC Loader Port PLC Select PLC Type FLEX PC CPU NJ B16 RS 2...

Page 81: ...a long distance communication it is recommended to use link units in consideration of the noise influence Dedicated Cable Dedicated cables for direct connection with the N Series loader port is availa...

Page 82: ...422 Wiring Diagram 1 connection of the UG200C N RS 232C Wiring Diagram 2 POD CN1 D sub 25pin Male PLC FG SD SG RD SD RD 1 12 7 25 13 8 24 3 5 2 4 6 8 Use twist shielded cables PLC NJ B16 D sub 25pin...

Page 83: ...ailable PLC Connect to the terminal block of the NJ JM computer link For further information refer to the PLC manual Communication Setting The recommended communication parameter setting of both PLC a...

Page 84: ...OD to PLC RS 422 Wiring Diagram 1 Recommended cable O VCTF SS 2C 0 75 mm 2 made by Chyugoku Densen Memory TYPE Remarks D data register 0 R link register 1 M internal relay 2 WM as word device K latch...

Page 85: ...J71UC24 R4 RS 232C Wiring Diagram 1 RS 422 Wiring Diagram 3 RS 232C Wiring Diagram 1 RS 232C Wiring Diagram 1 RS 422 Wiring Diagram 3 RS 232C Wiring Diagram 1 RS 232C Wiring Diagram 1 RS 232C Wiring D...

Page 86: ...ct MODE8 in case of RS 422 Q series link unit Port Transmission Control Mode RS 232C RS 422 When QnA series link is connected MODE5 Binary Mode fixed When QnH Q series link is connected MC Protocol Ty...

Page 87: ...3 4 5 6 7 8 9 A B C D E F MODE STATION No 1 STATION No 10 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F MODE STATION No 1 STATION No 10 SW11 ON OFF ON...

Page 88: ...ign indirect memory for macro programs Memory TYPE Remarks D data register 0 W link register 1 R file register 2 TN timer current value 3 CN counter current value 4 SPU special unit 5 Unit No 1 M inte...

Page 89: ...Use twist shielded cables Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 Wiring Diagram 2 PLC D sub 25pin Male D sub 25pin Male FG...

Page 90: ...b 25pin Male FG SG 1 7 12 13 24 25 SDA SDB SG RDB RDA POD CN1 SD SD RD RD Use twist shielded cables PLC D sub 25pin Male FG SG 1 7 12 13 24 25 RDA SG RDB 2 7 15 SDB 16 SDA 3 4 5 17 18 20 21 DSRA DTRA...

Page 91: ...the CPU is updated or the specifications are changed there is some possibility that POD cannot be connected to the PLC A2A A3A A2U A3U A4U A2US H A1N A2N A3N A3V A73 A3H A3M A0J2H A1S A1SJ H A2S H A2C...

Page 92: ...TYPE number to assign indirect memory for macro programs Memory TYPE Remarks D data register 0 W link register 1 R file register 2 TN timer current value 3 2 CN counter current value 4 SPU special uni...

Page 93: ...e core improves noise voltage by 650 900V and aids in preventing communication errors Note In case of direct connection with the CPU port of A QnA series be sure to attach the ferrite core to the cabl...

Page 94: ...o eliminate noise Specify the value more than 150 1 5 sec in Time out Time of Comm Parameter in case of connecting POD to a UG00P DI CPU PLC A6GPP A7PHP personal computer etc GD G P P UG200C G Slide s...

Page 95: ...lable PLC When the CPU is updated or the specifications are changed there is some possibility that POD cannot be connected to the PLC 9 PLC Select PLC Type QnH Q series CPU QnH A series CPU Q06H A RS...

Page 96: ...in Male Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 connection of the UG00C Q Memory TYPE Remarks D data register 0 W link regi...

Page 97: ...not be connected to the PLC 10 MITSUBISHI PLC 4 FX1 2 CPU Select PLC Type FX series CPU Wiring Diagram RS 232C UG00C X made by Fuji Electric RS 422 UG200C M made by Fuji Electric or Wiring Diagram 1 F...

Page 98: ...ata and word data are managed as lower half 16 bits data Input 16 upper half bits are ignored Output 0 is written in the 16 upper half bits Set the memory to the extent of the memory range of each PLC...

Page 99: ...sub 25pin Male FG SG 1 7 12 13 14 17 2 7 15 SG 16 4 17 5 18 20 21 3 18 19 24 25 POD CN1 SD SD RTS RTS CTS CTS RD RD RxD TxD DSR DTR RxD TxD DSR DTR Use twist shielded cables According to our noise tes...

Page 100: ...f Comm Parameter in case of connecting POD to a UG00P DI GD G P P 1 2 3 POWER RUN BATT V MELSEC FX2 24MT TRANSISTOR UNIT FX Series CPU A6GPP A7PHP personal computer etc UG200C G POD Slide switch 1 A s...

Page 101: ...RS 232C Wiring Diagram 1 RS 485 Wiring Diagram 3 RS 422 UG00C E made by Fuji Electric RS 232C Wiring Diagram 1 RS 485 Wiring Diagram 3 RS 422 UG00C E made by Fuji Electric RS 232C Wiring Diagram 2 RS...

Page 102: ...er half 16 bits data Input 16 upper half bits are ignored Output 0 is written in the 16 upper half bits Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign ind...

Page 103: ...S 485 Wiring Diagram 3 PLC D sub 25pin Male D sub 25pin Male FG SD RD RS CS SG 1 2 3 4 5 7 SD RD SG 2 3 7 POD CN1 Use twist shielded cables PLC D sub 25pin Male FG SG 1 7 12 13 24 25 RDA SG RDB 2 7 15...

Page 104: ...o 30 To read write the memories of the CPU e g 1 1 of CPU which has the link unit to be connected to the POD Set the CPU No to 31 on the panel editor Response time will be equivalent to the case of 1...

Page 105: ...n this command is used in other kinds of macros Refer to the UGseries Manual Function FEH376 for further information on Macro Also refer to MITSUBISHI s manual for network registration See MITSUBISHI...

Page 106: ...0 CV1000 CV2000 CVM1 C200H LK201 C200H LK201 V1 C200H LK202 C200H LK202 V1 C500 LK203 C120 LK201 V1 C120 LK202 V1 CPU unit with a built in RS 232C port host link port CPU unit with a built in RS 232C...

Page 107: ...and the following when the communication board is used for communication in the memory space corresponding to machine No when the communication unit is used If SYSMAC C is selected at the Select PLC T...

Page 108: ...urrent value 5 C counter current value 6 EMn extensional data memory 7 1 TU timer contact 9 Read only CU counter contact 10 Read only CS1 Memory TYPE Remarks DM data memory 0 CH input output relay 1 H...

Page 109: ...4 5 7 RS SD CS SG 2 4 5 9 D sub 25pin Male SD 2 RD 3 PLC D sub 9pin Male POD CN1 Use twist shielded cables FG RD RS CS SG 1 3 4 5 7 RS SD CS SG 2 4 5 7 D sub 25pin Male SD 2 RD 3 PLC D sub 25pin Male...

Page 110: ...e SG 7 SG 9 POD CN1 SD SD RD RD Use twist shielded cables FG 1 12 13 24 25 SDB RDB RDA SDA 8 2 6 1 PLC D sub 9pin Male D sub 25pin Male SG 7 SG 9 4 5 RS CS POD CN1 SD RD RD SD Use twist shielded cable...

Page 111: ...ndow Select System Setting from Item and click Network Table Edit Network Table is displayed Double click the No The dialog is displayed Register the CS1 on the network 14 OMRON PLC 2 POD CS1 1 1 CS1...

Page 112: ...PLC JW20 JW 31CUH JW70 JW100 JW70H JW100H JW50 JW70 JW100 JW50H JW70H JW100H ZW 10CM JW 10CM CPU communication port JW 21CM JW series JW100 70H COM port JW20 COM port JW20 JW22CU JW20H JW22CU Select P...

Page 113: ...h SW1 SW2 SW3 1 SW3 2 SW3 3 SW3 4 SW4 SW7 4 1 0 OFF ON OFF ON 0 ON Setting Contents Command mode Station address lower half Station address upper half Not used 4 wire system Not used Even parity Baud...

Page 114: ...POD CN1 SD SD RD RD TXD TXD RXD RXD Use twist shielded cables Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 RS 422 Wiring Diagram...

Page 115: ...Port 1 19200bps Even Baud Rate Parity RS 422 Data Length 7 Transmission Control Item Setting of PLC 1 19200bps Even 7 2 2 Stop Bit Error Check Comm Parameter of POD 4 wire system fixed Sumcheck fixed...

Page 116: ...CTS 12 POD CN1 Use twist shielded cables 16 Sharp PLC 2 1To set up Fn file register input File No colon address Set the memory to the extent of the memory range of each PLC model Use TYPE number to a...

Page 117: ...Port Transmission Control Mode RS 232C RS 422 MODE7 MODE9 Protocol 2 w Port Protocol 2 w Port 19200bps Even 7 ASCII Baud Rate Parity Transmission Code Data Length Stop Bit 1 Sumcheck Item Setting of P...

Page 118: ...sign indirect memory for macro programs 1 Switch 2 3 4 5 6 7 8 OFF OFF ON ON ON ON OFF ON Setting Contents Bit length Parity provided Even Stop bit 1 Sumcheck provided Same as POD normally 19200bps 17...

Page 119: ...Wiring Diagram 1 RS 422 Wiring Diagram 2 RD CS 3 5 SD RS D sub 25pin Male SD 2 RD CS FG 1 SG 7 DR PHL SG PV12 2 3 4 5 7 8 9 14 PLC D sub 15pin Male POD CN1 Use twist shielded cables 13 24 25 RxDP TxD...

Page 120: ...iring Diagram 1 RS 232C Wiring Diagram 2 RS 422 Wiring Diagram 3 PLC Link Unit Select PLC Type S10 2 S10 mini ABS HIDIC S10 2alpha HIDIC S10 ABS 18 HITACHI PLC 2 Memory TYPE Remarks FW work register 0...

Page 121: ...rect memory for macro programs Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 18 HITACHI PLC 2 E event register 16 EW as word devi...

Page 122: ...RD SD 50 50 Use twist shielded cables D sub 9pin Female D sub 25pin Male FG SD RD RS CS 1 2 3 4 5 RD SD SG 7 ER SG DR RS CS 2 CD 1 3 4 5 6 7 8 PLC POD CN1 Use twist shielded cables Wiring Diagram 2 R...

Page 123: ...eter of POD 0 for 10 1 for 1 1 Computer link system fixed Invalid fixed FP1 FP0 FP3 FP5 FP10 RS 232C port on a CPU unit RS 232C port on a CPU unit AFP3462 AFP3463 AFP5462 AFP5462 RS 232C tool port on...

Page 124: ...l Use TYPE number to assign indirect memory for macro programs 19 Matsushita PLC Memory TYPE Remarks DT data register 0 X external input relay 1 WX as word device read only Y external output relay 2 W...

Page 125: ...9pin Male FG SD RD RS CS SG 1 2 3 4 5 7 SD SG CD 2 7 8 ER 9 RS 4 CS 5 RD 3 POD CN1 Use twist shielded cables FG 1 12 13 24 25 D sub 25pin Male PLC POD CN1 SD SD RD RD PLC D sub 25pin Male FG SD RD RS...

Page 126: ...Length Stop Bit 1 Sumcheck Terminal Character Item Setting of PLC 1 19200bps Even 7 1 Protection Function Comm Parameter of POD Provided fixed None fixed None fixed FA500 FA500 LC01 0N PLC Link Unit...

Page 127: ...Wiring Diagram 1 RS 422 Wiring Diagram 2 D sub 25pin Male FG SD RD RS CS 1 2 3 4 5 SD RD SG 7 RS CS DR SG ER 2 3 4 5 6 7 20 PLC D sub 25pin Male POD CN1 Use twist shielded cables D sub 25pin Male FG 1...

Page 128: ...rameter dialog of POD because data length 8 is fixed Also specify the CPU Communication Port setting of Configuration in the ladder making tool as follows Personal Computer Link Function Use 19200bps...

Page 129: ...irect memory for macro programs E g 1 D00001 CPU No Memory Type Address 21 YOKOGAWA PLC 2 Memory TYPE Remarks D data register 0 R common register 1 V index register 2 W link register 3 Z special regis...

Page 130: ...Wiring Diagram 1 RS 422 Wiring Diagram 2 D sub 25pin Male FG 1 12 13 24 25 RDB RDA SG 7 SDB SDA SG PLC POD CN1 SD SD RD RD Use twist shielded cables PLC D sub 25pin Male D sub 9pin Male FG SD RD RS C...

Page 131: ...of PLC 19200bps Even 1 Port Delay Timer 1 0 fixed CRC fixed Comm Parameter of POD 8 fixed PLC Type Contents GL60 series PROGIC 8 Type 1 Same as before GL120 130 series Type 2 Standard binary mode Set...

Page 132: ...nge of each PLC model Use TYPE number to assign indirect memory for macro programs Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1...

Page 133: ...es D sub 25pin Male FG 1 12 13 24 25 SG 7 RXDRT SG 2 3 4 6 7 PLC D sub 9pin Male TXRD 8 9 POD CN1 SD SD RD RD TXD RXD RXD TXD Use twist shielded cables D sub 25pin Male FG SD RD RS CS 1 2 3 4 5 TXD RX...

Page 134: ...mobus port on a CPU module PLC Link Unit RS 232C Wiring Diagram 1 Select PLC Type CP9200SH MP900 CP9200SH MP920 MP930 CP 217IF 217IF RS 232C Wiring Diagram 1 Wiring Diagram 2 RS 422 Wiring Diagram 3 R...

Page 135: ...LC 2 Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 Wiring Diagram 2 RS 422 Wiring Diagram 3 Wiring Diagram 4 D sub 25pin Male FG...

Page 136: ...Area Data area is common Split Data Area Divide each PLC device into a program file PLC CMP LINK RS 422 Wiring Diagram 1 Select PLC Type TOYOPUC L2 PC2 Series PC3J Wiring Diagram Link Unit 19200bps E...

Page 137: ...relay 8 WL as word device T counter contact 9 WT as word device C counter contact 10 WC as word device U extension data register 11 H extension set value register 12 EN extension current valueregister...

Page 138: ...e twist shielded cables Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 422 Wiring Diagram 1 Screen Editing Memory Input If Split Data Area is selected a...

Page 139: ...rt connector cable made by Koyo S 15CNJ SG 8 SZ 4 PZ3 SU 5 5E 6B 5M 6M U01 DM Port 2 on a CPU unit SU SG SR T SZ 4M Port 2 on a CPU unit RS 232C Program transfer cable made by Koyo S 30JG E Convert co...

Page 140: ...as follows Available Memory SU SG SU SG K Sequence SR 1T SR T K prt Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs Memo...

Page 141: ...Unit No 01 6 OFF 1 N 8 OFF 7 9 OFF OFF Slave 2 OFF Switch Setting U 01DM On line off line switch on line UNIT ADR switch 0 for x 10 1 for x 1 SW4 Dip Switch SW5 Dip Switch G 01DM On line off line swi...

Page 142: ...wist shielded cables D sub 25pin Male PLC D sub 15pin Male Use twist shielded cables 1 High density D sub 15pin FG SD RD RS CS SG 1 2 3 4 5 7 TXD RXD RTS CTS 0V 2 3 4 5 7 POD CN1 1 D sub 25pin Male FG...

Page 143: ...sity D sub 15pin POD CN1 1 25 Koyo PLC Wiring Diagram 5 Wiring Diagram 6 Wiring Diagram 7 Wiring Diagram 8 POD CN1 D sub 25pin Male FG SD SD RD RD 1 12 13 24 25 RXD RXD PLC D sub 25pin Male CTS1 TXD1...

Page 144: ...22 Wiring Diagram 3 1770 KF2 1785 KE RS 232C Wiring Diagram 1 Select PLC Type Wiring Diagram Link Unit Port Transmission Control Mode RS 232C RS 422 Not available with 1785 KE 0 19200bps Even 8 Baud R...

Page 145: ...Handshaking signal ignored 6 ON Diagnosis execution BCC Even no 2 OFF 26 Allen Bradley PLC 1 Memory TYPE Remarks N integer 0 B bit 1 T ACC timer current value 2 T PRE timer set value 3 C ACC counter...

Page 146: ...link transmission speed Adjust the setting according to the network you are using 1 No 3 4 ON ON ON Setting Contents 5 ON 6 ON 2 ON Data highway 57 6k bps Link transmission speed 19 2k bps Local remo...

Page 147: ...FG SD RD RS CS 1 2 3 4 5 TXD RXD PLC D sub 15pin Male RTS CTS 2 3 4 5 6 7 SG DSR SG 7 8 11 13 DCD DTR SG POD CN1 Use twist shielded cables 26 Allen Bradley PLC 1 SW6 asynchronous link transmission sp...

Page 148: ...RD RS CS 1 2 3 4 5 TXD RXD PLC D sub 25pin Female RTS CTS 2 3 4 5 6 DSR SG 7 8 20 DCD DTR SG 7 POD CN1 Use twist shielded cables D sub 25pin Male FG 1 12 13 24 25 RTS CTS PLC D sub 25pin Female DSR D...

Page 149: ...pe SLC500 Micro Logix 1000 Micro Logix 1000 Port on a CPU RS 232C program transfer cable made by Allen Bradley RS 232C Wiring Diagram 3 Link Unit Wiring Diagram Port Transmission Control Mode RS 232C...

Page 150: ...purpose Baud Rate 19200 Duplicate Detect ON ACK Timeout 20 ms 20 Control Line NO HANDSHAKING Parity EVEN Error Detect BCC NAK Retries 3 ENQ Retries 3 Embedded Responses AUTO DETECT Memory TYPE Remark...

Page 151: ...nstant Carrier Detect Disabled Message Timeout 400 Hardware Handshaking Disabled Embedded Response Detect Auto Detect ACK Timeout 5ms 90 ENQuiry Retries 3 NAK Received Retries 3 Wiring The following i...

Page 152: ...6 7 8 DSR RTS CTS POD CN1 Use twist shielded cables POD CN1 PLC D sub 25pin Male D sub 9pin Male FG SD RD RS CS SG 1 2 3 4 5 7 RD SD RS 2 CD 1 3 4 GND 5 DR 6 RS 7 CS 8 Use twist shielded cables AB RS...

Page 153: ...s 28 Port 19200bps Odd 8 Baud Rate Parity Transmission Code Data Length Stop Bit 1 Function Response Delay Time Time out ASCII HEX Item Setting of PLC 1 19200bps Odd 8 1 Comm Parameter of POD 01 0 for...

Page 154: ...RS 485 Wiring Diagram 2 D sub 25pin Male FG SD RD RS CS SD PLC D sub 25pin Male RD RS 2 3 4 5 CS SG 7 GND 2 1 3 4 5 7 POD CN1 Use twist shielded cables D sub 25pin Male FG SG 1 7 12 13 24 0V PLC D sub...

Page 155: ...Baud Rate Parity Transmission Code Data Length Stop Bit 1 Function Item Setting of PLC 19200bps Odd 8 1 Comm Parameter of POD SNP X fixed RS 485 Wiring Diagram 1 Series 90 micro CPU port Series 90 30...

Page 156: ...show the wiring of the cable which connects POD to PLC RS 485 Wiring Diagram 1 D sub 25pin Male FG SG 1 7 12 13 24 RTS A PLC D sub 15pin Male 0V CTS B 6 7 8 9 RT 25 10 11 12 RD A RD B SD A SD B RTS B...

Page 157: ...the T series PLC use a T series programmer and enter the following data in the system information 7 COMPUTER LINK Station No 1 Baud rate 19200 BPS Parity Odd Data bit 8 bit Stop bit 1 bit TOSHIBA PLC...

Page 158: ...C D sub 15pin Male 3 4 RXA TXA CTSA RTSA 5 SG 7 7 1 12 13 24 25 10 11 12 13 RXB TXB CTSB RTSB R R 120 1 2W POD CN1 SD SD RD RD Use twist shielded cables Memory TYPE Remarks D data register 0 X input r...

Page 159: ...bps Baud Rate Item Setting of PLC 1 9600bps Comm Parameter of POD 31 TOSHIBA MACHINE PLC Memory TYPE Remarks D register 1 0 B register 2 1 X input relay 2 XW as word device Y output relay 5 YW as word...

Page 160: ...ing is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 D sub 25pin Male FG SD RD RS CS 1 2 3 4 5 TXD RXD PLC D sub 9pin Female DTR GND 2 3 4 5 DSR CTS 6 7...

Page 161: ...00 Block No Address No PLC S5 90U S5 95U S5 100U S5 95U RS 232C Wiring Diagram 1 6ES5 734 1BD20 cable made by SIEMENS RS 232C Wiring Diagram 2 CP 521SI 3964R Transmission Protocol Second serial interf...

Page 162: ...ring Diagram 1 Wiring Diagram 2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 F0000210 F0000217 Memory setting of UG400 or UG200 Memories to be accessed to PLC by UG400 or UG200 F0000200 F0000207 15 14 13 12...

Page 163: ...Address No Colon S7 DB003000 Block No Address No E g S5 S5 UG400 PLC Link Unit Wiring Diagram S5 115U S5 135U S5 155U RS 232C Wiring Diagram 1 RS 422 Wiring Diagram 3 RS 232C Wiring Diagram 2 RS 422 W...

Page 164: ...11 10 9 8 7 6 5 4 3 2 1 0 F0000210 F0000217 Memory setting of UG400 or UG200 Memories to be accessed to PLC by UG400 or UG200 F0000200 F0000207 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 F0000210 F0000217...

Page 165: ...g DB003000 Block No Address No PLC Select PLC Type S5 PG Port Programing port on a CPU unit 6ES5 734 1BD20 cable made by SIEMENS RS 232C Wiring Diagram 1 S5 series Wiring Diagram Link Unit 33 SIEMENS...

Page 166: ...600bps 2 Even fixed Baud Rate Port Parity Item Setting of PLC 9600bps 2 Comm Parameter of POD Memory TYPE Remarks V data register 0 VW as word device I input relay 1 IW as word device Possible to writ...

Page 167: ...ip switch 7 8 of POD to OFF Connect terminal registance to the POD serial connector CN1 as follows If terminal registance is not connected the communication error may occur PLC D sub 25pin Male FG SG...

Page 168: ...ble Memory 1 In case of using DCP drum count set value set the drum step No 1 to 16 The assigned memory is indicated while editing the screen as illustrated Set the memory to the extent of the memory...

Page 169: ...LC type is automatically selected as TI500 505 UG400 In UG400 or UG200 the order of words is reversed when the double words Wiring The following is a diagram to show the wiring of the cable which conn...

Page 170: ...Transmission Code Data Length Stop Bit Item Setting of PLC HMI ADP 38400bps fixed None fixed 8 fixed 1 fixed PC ADP 38400bps 2 2 Comm Parameter of POD Local No PLC station No CPU Wiring Diagram S7 30...

Page 171: ...Diagram 1 Wiring Diagram 2 E g DB0001 0000 Block No Address No D sub 25pin Male HMI Adapter PC Adapter D sub 9pin Female Use twist shielded cables FG SD RD RS CS SG 2 1 3 4 5 7 RD SD SG RTS CTS 6 5 8...

Page 172: ...00S CW Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs 19200bps Even 7 ASCII Baud Rate Parity Transmission Code Data Len...

Page 173: ...diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 D sub 25pin Male FG SD RD RS CS SD PLC D sub 25pin Male RD RS 2 3 4 SG 2 1 3 4 5 7 CS 5 SG 7 POD CN1 Use twis...

Page 174: ...am 2 Select PLC Type Wiring Diagram Available PLC Communication Setting The recommended communication parameter setting of both PLC and POD is as follows Available Memory Set the memory to the extent...

Page 175: ...LC RS 232C Wiring Diagram 1 RS 422 Wiring Diagram 2 D sub 25pin Male FG SD RD RS CS TXD PLC D sub 9pin Male RXD 2 3 SG 2 1 3 4 5 7 5 GND POD CN1 Use twist shielded cables D sub 25pin Male FG PLC D sub...

Page 176: ...dip switches Available Memory Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect memory for macro programs PLC KZ300 KZ350 Port 2 RS 232C Wiring Diag...

Page 177: ...iagram 3 D sub 25pin Male FG SD RD RS CS SD PLC D sub 25pin Male RD 2 3 SG 2 1 3 4 5 7 4 RS CS SG 5 7 POD CN1 Use twist shielded cables D sub 25pin Male PLC Use twist shielded cables FG SD RD RS CS SG...

Page 178: ...m KZ A500 Port 2 RS 232C Wiring Diagram 3 RS 422 Wiring Diagram 4 KZ L10 CPU Modular Port Port 1 RS 232C Wiring Diagram 2 Select PLC Type MITSUBISHI A series link KZ A500 CPU RS 232C Wiring Diagram 1...

Page 179: ...g Diagram 1 41 KEYENCE PLC 2 POD CN1 D sub 25pin Male Modular Connector 6pin FG SD RD SD CS PLC SG 2 1 3 RS 4 CS 5 RD RS 3 1 4 5 6 SG 7 Use twist shielded cables 123456 Memory TYPE Remarks D data regi...

Page 180: ...D sub 25pin Male D sub 25pin Male FG SD RD RS CS SG 1 2 3 4 5 7 RD SD RS CS DR SG CD 3 2 4 5 6 7 8 POD CN1 D sub 25pin Male PLC Use twist shielded cables FG SD RD RS CS SG 2 1 3 4 5 7 SD RD SG POD CN...

Page 181: ...s 8 1 Comm Parameter of POD 38400bps 1 Even Baud Rate Parity Transmission Code Data Length Stop Bit Item Setting of PLC 0 Port 0 57600bps 8 1 Comm Parameter of POD 57600bps 1 Available PLC When using...

Page 182: ...PLC model Use TYPE number to assign indirect memory for macro programs Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 Memory TYPE...

Page 183: ...Code Data Length Stop Bit 1 fixed Item Setting of PLC 19200bps Comm Parameter of POD 1 PLC Wiring Diagram K10 60 200 RS 232C Wiring Diagram 1 K500 1000 RS 232C Wiring Diagram 2 RS 422 Wiring Diagram 6...

Page 184: ...ks D data register 0 M auxiliary relay 1 P input output relay 2 Input Read only K keep relay 3 TC timer current value 4 CC counter current value 5 TS timer set value 6 CS counter set value 7 Memory TY...

Page 185: ...p relay 3 KW as word device F special relay 4 Read only FW as word device T timer current value 5 C counter set value 6 D data register 7 TC time cortact 9 CC counter contact 10 Memory TYPE Remarks M...

Page 186: ...The following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 Wiring Diagram 2 Wiring Diagram 3 Wiring Diagram 4 D sub 25pin Male FG SD RD RS CS RxD D...

Page 187: ...t shielded cables RDA RDB PLC FG SD SD RD RD 1 12 13 24 25 POD CN1 D sub 25pin Male Use twist shielded cables SDA SDB SG 7 SG Wiring Diagram 5 RS 422 Wiring Diagram 6 Wiring Diagram 7 POD CN1 D sub 25...

Page 188: ...2 Wiring Diagram 3 Power Mate i Model H D Wiring Diagram Available PLC Communication Setting The recommended communication parameter setting of both PLC and POD is as follows Available Memory Set the...

Page 189: ...9 17 SG 2 1 3 4 5 7 18 0V Use twist shielded cables 1 Half pitch 20 pins 1 POD CN1 D sub 25pin Male FG SG SD PLC RDB 7 1 12 RDA SD 13 SDB 1 3 RD RD 24 25 2 4 11 SDA 0V RDB RDA 1 2 R JD15 R 120 1 2W PO...

Page 190: ...ta Length Stop Bit Item Setting of PLC 9600bps 7 fixed 1 fixed Transmission Code Comm Parameter of POD 9600bps RS 232C FACON FB series FACON FB series PLC Select PLC Type Wiring Diagram RS 232C Wiring...

Page 191: ...am 3 D sub 25pin Male FG RD RS CS SG SD 1 3 4 5 7 2 RTS1 RXD1 CTS1 GND TXD1 1 3 4 6 2 PLC D sub 15pin Male POD CN1 Use twist shielded cables Use twist shielded cables D sub 25pin Male FG RD RS CS SG S...

Page 192: ...RS 232C Cable made by IDEC FC2A KC1 or Cable made by IDEC FC2A KC2 RS 232C Wiring Diagram 1 PLC Wiring Diagram Selet PLC Type MICRO3 MICRO Smart RS 232C Cable made by IDEC FC2A KC4C RS 232C Wiring Di...

Page 193: ...is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 D sub 25pin Male FG SD RD RS CS CD PLC D sub 9pin Male SD RD 1 2 3 SG 2 1 3 4 5 7 ER 4 GND 5 DR RS CS 6...

Page 194: ...f the cable which connects POD to PLC RS 232C Wiring Diagram 1 PLC Modbus RTU RS 232C Wiring Diagram 1 Select PLC Type Modbus RTU Wiring Diagram 9600bps 1 Even Even 1 Port Baud Rate Parity Data Length...

Page 195: ...programs PLC MX200 MX50 RS 232C Wiring Diagram 1 Select PLC Type MX Series Wiring Diagram 9600bps 1 Even Even 1 Port Baud Rate Parity Data Length Stop Bit Item Setting of PLC 9600bps 8 8 1 1 Transmis...

Page 196: ...following is a diagram to show the wiring of the cable which connects POD to PLC RS 232C Wiring Diagram 1 PLC D sub 25pin Male D sub 25pin Male FG SD RD RS CS SG 1 2 3 4 5 7 SD RD RS 2 3 4 CS 5 SG 7 U...

Page 197: ...RS 422 Wiring Diagram 1 RS 422 Wiring Diagram 2 Select PLC Type TP02 Communication Port T R T R MMI Port 9pin 4 5 Short Computer Link Mode PORT Wiring Diagram 19200bps 1 None None 1 Port Baud Rate Par...

Page 198: ...ts POD to PLC RS 422 Wiring Diagram 1 Wiring Diagram 2 D sub 25pin Male FG SG SD SD RD 1 7 12 13 24 T R T R PLC SHLD RD 25 Use twist shielded cables POD CN1 D sub 25pin Male FG SG SD SD RD 1 7 12 13 2...

Page 199: ...e Select PLC Type Wiring Diagram RS 232C Wiring Diagram 1 RS 232C Wiring Diagram 2 RS 485 Wiring Diagram 3 PGU port PCD7 F120 PCD4 F110 Set the memory to the extent of the memory range of each PLC mod...

Page 200: ...G 1 3 2 7 TX RX GND POD CN1 D sub 25pin Male PLC Use twist shielded cables 12 11 10 PCD7 F120 RS 485 Wiring Diagram 3 FG SD SG SD RD RD 1 12 7 13 24 25 T R T R POD CN1 D sub 25pin Male PLC Use twist s...

Page 201: ...201 MM1 PRG port PS4 PLC Select PLC Type Wiring Diagram RS 232C Wiring Diagram 1 ZB4 303 KB1 Cable made by MOELLER Set the memory to the extent of the memory range of each PLC model Use TYPE number to...

Page 202: ...t 1 Item Setting of PLC Multi Link fixed 9600bps Odd 8 1 Comm Parameter of POD Available Memory Set the memory to the extent of the memory range of each PLC model Use TYPE number to assign indirect me...

Page 203: ...it Direct LOGIC K Sequence D2 250 Port 2 on a CPU unit RS 232C Wiring Diagram 3 D4 430 D4 440 Port 3 on a CPU unit Port 0 on a CPU unit Port 2 on a CPU unit Port 1 on a CPU unit RS 232C Wiring Diagram...

Page 204: ...ing Diagram 1 53 Automationdirect PLC Memory TYPE Remarks V data register 0 X input relay 1 Y output relay 2 C internal relay 3 S stage 4 GX global inputs 5 GY global outputs 6 T timer contact 7 CT co...

Page 205: ...b 25pin Male FG SD RD RS CS 1 2 3 4 5 TXD RXD PLC D sub 15pin Male 0V 2 3 13 SG 7 Use twist shielded cables POD CN1 D sub 25pin Male FG SD SD RD RD 1 12 13 24 25 RXD RXD PLC D sub 25pin Male CTS1 TXD1...

Page 206: ...data display graph sampling the data is managed as double word data Both bit data and word data are managed as lower half 16 bits data Input 16 upper half bits are ignored Output 0 is written in the...

Page 207: ...o PLC RS 232C Wiring Diagram 1 FG SD RD 1 2 3 SG 7 RXD TXD SG RTS 2 3 5 7 CTS 8 POD CN1 D sub 25pin Male PLC D sub 9pin Male Use twist shielded cables RS 485 Wiring Diagram 2 FG SD SD RD 1 SG 7 12 13...

Page 208: ...indirect memory for macro programs DVP series PLC Link Unit Wiring Diagram RS 485 Wiring Diagram 1 RS 485 Communication port Select PLC Type DVP series Port 1 9600bps Even 7 Baud Rate Parity Transmiss...

Page 209: ...ing The following is a diagram to show the wiring of the cable which connects POD to PLC RS 485 Wiring Diagram 1 POD CN1 FG SD SD RD 1 12 13 24 PLC RD 25 D sub 25pin Male Use twist shielded cables 55...

Page 210: ...model Use TYPE number to assign indirect memory for macro programs Mint Controller Wiring Diagram RS 232C Wiring Diagram 1 Select PLC Type NextMove Comms Data Array Optimum Comms Data Array Port 0 960...

Page 211: ...LC RXD TXD DTR SG 2 3 4 5 DSR RTS CTS 6 7 8 D sub 25pin Male D sub 9pin Female Use twist shielded cables Wiring The following is a diagram to show the wiring of the cable which connects POD to PLC RS...

Page 212: ...macro specify the CPU No using the extended code Indirect memory setting by macro is not available for input I or output Q memory Standard Memory TYPE Remarks I input memory O output memory M standard...

Page 213: ...e attach a ferrite core TDK ZCAT2032 0930 is recommended to both the ends of the cable D sub 25pin Male FG RD RS CS SG 1 3 4 5 7 SD 2 PLC D sub 9pin Male RD SD ER SG DR 2 3 4 5 6 RS CS 7 8 POD CN1 Use...

Page 214: ...Connecting the UG00P U1 2 Connecting the UG00P U2 3 Connecting the Memory Card Recorder 4 Connecting the Memory Extension Unit 5 Connecting Communication Interface 6 Connecting Dual Port Interface 7...

Page 215: ...used with the UG00P U2 simultaneously For assignment in the memory or how to use UG00P U1 refer to the User s Manual Function FEH376 Warning Turn OFF the power before mounting dismounting wiring maint...

Page 216: ...s shown in the figure on the right Mount the extension I O unit then secure it using the three screws Set the DI DO connector attached to the package to the extension I O unit connector then secure it...

Page 217: ...ratic operation or troubles might occur Caution The serial connection I O unit uses a link Therefore do not use the unit in places where high speed operations urgent operations or dangerous operations...

Page 218: ...ecifications Item Specifications Rated voltage 24V DC 10 Power supply Consumption current 60 mA max Inrush current 1 5 A 200 s max Operating temperature 0 to 50 deg C Physical Storage temperature 10 t...

Page 219: ...or less Residual voltage 1 7V Leak current when Up to 0 1 mA turned off Insulation type Insulation using photocoupler OUT7 OUT0 COM1 Internal circuit 22 22 OUT15 OUT8 COM2 22 22 12 to 24V DC Load Load...

Page 220: ...memory manager for the memory card For the UG400 210 Series use the UG200P MR or UG400P MR Caution Do not bundle the control line communication cable with the power cables or route it close to the pow...

Page 221: ...every side Assembling the Recorder 1 Cut the cover panel maximum thickness 5 mm so that the attachment cover can be set then insert the attachment cover into the cover panel 2 Secure the attachment c...

Page 222: ...Jack 2 for Memory Card MJ2 takes priority and data transmission from MJ1 is prohibited For how to transfer POD screen data to the memory card or how to transfer screen data recorded in the memory car...

Page 223: ...ating instructions and the manual when mounting the product If mounting is improper the product might drop or develop problems or erratic operations Warning Turn OFF the power before mounting dismount...

Page 224: ...r is also necessary With the UG screen development software UG00S CW set items in the Memory Expansion dialog box on the Unit Setting window under System Setting How to Use the UGxxP SR The following...

Page 225: ...p set the battery in the socket of the SRAM cassette To set the battery insert the battery first in the plus side of the SRAM cassette and then insert it also in the minus side while pushing toward th...

Page 226: ...Caution Follow the directions of the operating instructions and the manual when mounting the product If mounting is improper the product might drop or develop problems or erratic operations External D...

Page 227: ...POD UG220 UG320 UG520 UG420 UG221 312 11 5 114 5 141 5 I F unit 334 270 245 2 95 8 16 288 310 240 215 2 92 3 16 I F unit 8 110 126 220 230 175 165 66 1 25 6 I F unit 85 85 POWER F1 F5 F4 F3 F2 SYSTEM...

Page 228: ...ions I F unit Notch Tightening screws for fixing a unit See the table below for how to tighten the screw for fixing a unit Type of screw Screw size Tightening torque N m Unit mounting screw M3 0 3 to...

Page 229: ...the CPU of the PLC Warning Turn OFF the power before mounting dismounting wiring maintaining or checking otherwise electric shock erratic operation or troubles might occur Caution Follow the direction...

Page 230: ...200C G sold separately When connecting to FX1 2 series CPU use UG200C G sold separately When connecting to FX0N 2N series CPU use the conversion cable FX 20P CADP supplied from Mitsubishi Mitsubishi A...

Page 231: ...ned on with the console connected to the UG00P DI communication time out error occurs on the console before the initialization of UG00P DI is completed In such case disconnect once the cable from the...

Page 232: ...is selected for transfer the Select program file dialog box is displayed In this dialog select a program that you want to transfer Comments related to communication condition are displayed in text bo...

Page 233: ...n or clothes wash it off using soap or detergent Do not remove any parts other than those indicated in the manual Otherwise the body or unit may become faulty Caution Replace the unit in an environmen...

Page 234: ...ding humans at the same electric potential Use an anti static wristband or mat to prevent static electricity 1 Turn the POD over and remove the packing 2 Remove the 6 screws from the rear external cas...

Page 235: ...and remove the LCD module connector by pulling it up Hold the connector and pull it out Do not twist or yank on the cable then Screws Screws Front external case Inside case LCD module connector Cord b...

Page 236: ...cemented with an adhesive Remove only the portion on the backlight unit CFL unit cover 14 Remove the screw fixing the backlight unit CFL unit cover Since the screw is small use a precision screwdriver...

Page 237: ...the bag do not twist or yank on the cable 18 Attach the cover Insert the cover in a slanting direction as shown with arrow 1 and slide it to the direction of arrow 2 until it is hooked on claws 19 At...

Page 238: ...t cable 22 Attach the 4 screws to fix the LCD module LCD module Screws Inside case 23 After attaching the LCD module to the inside case place it with the display panel side down Place it on a cloth et...

Page 239: ...on cables Inside case CPU board connector Cord band Ferrite core LCD module connector 28 Attach the LCD module connector Secure the ferrite core using a cord band Do not twist or yank on the cable of...

Page 240: ...at the same electric potential Use an anti static wristband or mat to prevent static electricity 1 Turn the POD over and remove the packing 2 Remove the 6 screws from the rear external case Place it...

Page 241: ...ble connector Lock Ribbon cable 6 Remove the 6 screws fixing the inside case Screws Front external case Inside case 7 Remove the inside case from the front external case Take care not leave scratches...

Page 242: ...tches LCD module rear Inside case 11 Hold down the claw and pull the backlight unit CFL unit out horizontally to the left Claw Backlight unit CFL unit 12 Attach a new backlight unit CFL unit Hold down...

Page 243: ...ule Be careful not to drop the fiber cable Screws Inside case Fiber cable 15 After attaching the LCD module to the inside case place it with the display panel side down Place it on a cloth etc to prot...

Page 244: ...bon cables Backlight unit CFL unit connector Inside case Front external case CPU board connector Visually check that all connectors and ribbon cables are connected se curely 20 Attach the rear externa...

Page 245: ...at the same electric potential Use an anti static wristband or mat to prevent static electricity 1 Turn the POD over and remove the packing 2 Remove the 6 screws from the rear external case Place it...

Page 246: ...ble connector Lock Ribbon cable 6 Remove the 6 screws fixing the inside case Screws Screws Front external case Inside case 7 Remove the inside case from the front external case Take care not leave scr...

Page 247: ...tches LCD module rear Inside case 11 Hold down the claw and pull the backlight unit CFL unit out horizontally to the left Claw Backlight unit CFL unit 12 Attach a new backlight unit CFL unit Hold down...

Page 248: ...rounding terminal together Be careful not to drop the fiber cable Screws Inside case Fiber cable Grounding terminal 15 After attaching the LCD module to the inside case place it with the display panel...

Page 249: ...board connector Ribbon cables Inside case Front external case Backlight unit CFL unit connector Visually check that all connectors and ribbon cables are connected se curely 20 Attach the rear externa...

Page 250: ...or for the backlight unit CFL unit 4 Remove connector A 5 Remove connector B Holding the connector carefully remove it without pulling on the cable Properly mark connectors B and C so that they can be...

Page 251: ...at fix the LCD module 11 Remove the LCD module from the inside case 12 Put the LCD module on the table with the display panel down Put a cloth or other protective material under the product so as not...

Page 252: ...nit until it locks completely 15 Put the LCD module on the table with the display panel up 16 Mount the LCD module on the inside case Pass the cables through the inside case Lock Backlight unit CFL un...

Page 253: ...roduct so as not to damage the display panel 19 Mount the inside case on the front outside case Be careful not to allow dust or other foreign matter to enter the gap between the inside case and the fr...

Page 254: ...se After fitting the rear outside case firmly press the entire case body to fit the internal POWER board connector into the CPU board connector 26 Mount the 6 screws on the rear outside panel LCD modu...

Page 255: ...tband or mat to prevent static electricity 1 Turn the POD over and remove the 4 external screws Place it on a cloth etc to protect the display panel from scratches 2 Remove the rear external case Scre...

Page 256: ...ed with the backlight unit CFL unit connectors 9 Remove the two ribbon cables Backlight unit CFL unit connectors Front external case Ribbon cables Rear external case Screw PC board Screw Ribbon cable...

Page 257: ...ase from the front external case 12 Place the inside case with the display panel side up Take care not leave scratches fingerprints or dirt on the display panel 13 Remove the 4 screws fixing the LCD m...

Page 258: ...e rear Lock Lock 17 Attach a new backlight unit CFL unit Make sure that the lock is secured When taking a new backlight unit out of the bag do not twist or yank on the cable Backlight units CFL units...

Page 259: ...e it on a cloth etc to protect the display panel from scratches 22 Attach the inside case to the front external case Do not allow the entry of dust or particles to the area between the inside case and...

Page 260: ...backlight unit CFL unit connectors 26 Attach the backlight unit CFL unit connector Screw Screw Front external case Rear external case Ribbon cables Backlight unit CFL unit connectors 27 Attach the 2...

Page 261: ...ly board connector Connector A Connector B Visually check that all connectors and ribbon cables are connected se curely 31 Attach the rear external case to the front external case Fit the rear externa...

Page 262: ...n anti static wristband or mat to prevent static electricity 1 Turn the POD over and remove the 9 external screws Place it on a cloth etc to protect the display panel from scratches Screws Rear extern...

Page 263: ...connector and the lock are not removable 5 Remove the 4 screws fixing the CPU board Screws CPU board 6 Raise the CPU board vertically until it is removed Take necessary measures to protect the CPU bo...

Page 264: ...FL unit Remove the unit by pulling it up Lock Lock 12 Attach a new backlight unit CFL unit Make sure that the lock is secured When taking a new backlight unit out of the bag do not twist or yank on th...

Page 265: ...8 Attach the 4 screws to fix the CPU board Tighten one screw at the bottom right with an earth cable terminal Screws Earth cable 19 Attach the 3 ribbon cables Ribbon cable connector Insert the ribbon...

Page 266: ...connectors with their marks 21 Visually check that all connectors and ribbon cables are connected securely 22 Attach the rear external case to the front external case 23 Attach the external 9 screws...

Page 267: ...s Place it on a cloth etc to protect the display panel from scratches 2 Remove the rear external case 3 Disconnect the backlight unit CFL unit connector Hold the connector and pull it out Do not twist...

Page 268: ...yank on the cable 6 Attach a new backlight unit CFL unit When taking a new backlight unit out of the bag do not twist or yank on the cable 7 Attach the screw to fix the backlight unit CFL unit 8 Conn...

Page 269: ...in position Press the case entirely so as to fit the power supply board connector with the CPU board connector inside Do not allow the cable to be caught in the area between the cases Power supply bo...

Page 270: ...Appendix Ladder Transfer Function...

Page 271: ...drop multi link and multi link2 communication The following types are unavailable for this function UG220 UG320HD Version and Main Menu Screen Available versions are as follows The information can be...

Page 272: ...one COM port for both purposes at the same time Stop using both software for communications 1 1 communication cable MITSUBISHI QnH FX series MELSEC CN1 CPU port Computer PC RESET disc GPPW UG00S CW C...

Page 273: ...ed for Modular Jack 1 even when the Main Menu screen is displayed on the POD communications with the PLC programming software continue so that communications with the UG00S CW editor are not available...

Page 274: ...ing There will be no problem if the setting for Baud Rate in the Comm Parameter dialog of the UG00S CW editor is not consistent with the baud rate setting on the PLC programming software The baud rate...

Page 275: ...ty Ohsaki East Tower 11 2 Osaki 1 chome Shinagawa ku Tokyo 141 0032 Japan Phone 81 3 5435 7135 7136 7137 7138 Fax 81 3 5435 7456 7457 7458 7459 URL http www fujielectric co jp kiki Information in this...

Reviews: