background image

En-13

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

fl

 ow switching, and other remote control unit operations.

(2)  Air 

fi

 lter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

16. ERROR CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output er-
ror codes by way of blinking patterns. If you use a wired remote controller, error codes will 
appear on the remote controller display. See the lamp blinking patterns and error codes in 
the table. An error display is displayed only during operation.

Error display

Wired

remote

controller

Error code

Description

OPERATION

lamp

(green)

TIMER

lamp

(orange)

ECONOMY

lamp

(green)

(1)

(1)

Serial communication error

(1)

(2)

Wired remote controller 
communication  error

(1)

(5)

Check run unfinished

(2)

(1)

Unit number or Refrigerant circuit 
address setting error [Simultane-
ous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

•  Connection unit number error 

(indoor slave unit) [Simultane-
ous Multi]

•  Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(7)

Master unit, slave unit set-up 
error [Simultaneous Multi]

(3)

(2)

Indoor unit PCB model 
information error

(3)

(5)

Manual auto switch error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit Heat Ex. Middle temp. 
sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error

(5)

(8)

Intake grille error

(5)

(15)

Indoor unit error

(6)

(2)

Outdoor unit main PCB model 
information error or 
communication error

(6)

(3)

Inverter  error 

(6)

(4)

Active filter error, PFC circuit er-
ror 

(6)

(5)

Trip terminal L error

(6)

(10)

Display PCB microcomputers 
communication error  

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid 
temp. sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

(7)

(6)

2-way valve temp. sensor error

• 

3-way valve temp. sensor error

• 

(7)

(7)

Heat sink temp. sensor error

(8)

(2)

Sub-cool Heat Ex. gas inlet 

• 

temp. sensor error

Sub-cool Heat Ex. gas outlet 

• 

temp. sensor error

(8)

(3)

Liquid pipe temp. sensor error

(8)

(4)

Current sensor error

(8)

(6)

Discharge pressure sensor 

• 

error

Suction pressure sensor error

• 

High pressure switch error

• 

(9)

(4)

Trip detection

(9)

(5)

Compressor rotor position 
detection error

(9)

(7)

Outdoor unit fan motor error

(9)

(9)

4-way valve error

(10)

(1)

Discharge temp. error

(10)

(3)

Compressor temp. error

(10)

(4)

High pressure error

(10)

(5)

Low pressure error

(13)

(2)

Branch boxes error
[Flexible Multi]

Display mode 

 : 0.5s ON / 0.5s OFF

 : 0.1s ON / 0.1s OFF

( ) : Number of flashing

[Troubleshooting with the indoor unit display]

OPERATION indicator lamp (green)

TIMER indicator lamp (orange)

ECONOMY indicator lamp (green)

[Troubleshooting with the wired remote controller display (Option)]

If an error occurs, the following display will be shown. (“Er” will appear in the set room 
temperature display.)

Error code

9319357041_IM.indb   13

9319357041_IM.indb   13

11/30/2011   1:33:20 PM

11/30/2011   1:33:20 PM

Summary of Contents for 9319357041

Page 1: ...çais Español INSTALLATION MANUAL MANUEL D INSTALLATION MANUAL DE INSTALACIÓN For authorized service personnel only Pour le personnel agréé uniquement Solo para personal autorizado PART NO 9319357041 AIR CONDITIONER ...

Page 2: ... runs as short as possible Use the flare method for connecting tubing Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before opening the refrigerant valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit ...

Page 3: ...ket 1 Tapping screw big 5 Name and Shape Q ty Name and Shape Q ty Remote controller 1 Tapping screw small 2 Battery 2 Air cleaning filter 2 Seal A It is used when the diameter of gas pipe is Ø12 70 or more It is necessary when using AS15 1 The following items are necessary to install this air conditioner The items are not includ ed with the air conditioner and must be purchased separately Name Q t...

Page 4: ...such as storing food raising animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the danger of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit branch...

Page 5: ... the outside with decorative tape For Left rear piping Left piping Interchange the drain cap and the drain hose CAUTION Insert drain hose and drain cap securely Drain should slope down to avoid water leakage When inserting be sure not to attach any material besides water If any other material is attached it will cause deterioration and water leakage After removing drain hose be sure not to forget ...

Page 6: ...an indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm in 6 35 1 4 17 21 32 9 52 3 8 22 7 8 12 70 1 2 26 1 1 32 15 88 5 8 29 1 5 32 19 05 3 4 36 1 13 32 6 9 2 Bending pipes If pipes are shaped by hand be careful not to collapse th...

Page 7: ...rminal block 5 Fasten the connection cable with a cable clamp Attach the 1 screw Insert the wire cover tab into the square hole of the indoor unit and fasten with a screw Cable clamp Connection cable Screw Screw Wire cover Connection cable Terminal block Cable clamp Connection cable Screw Screw Wire cover Earth Ground wire Earth Ground screw Indoor unit terminal block Disconnect switch Please conn...

Page 8: ...Connection cable Left piping For connection from the left rear PROHIBITED Pipe Connection pipe heat insulation Bind the pipes together so that there is no gap Indoor unit pipe heat insulation 7 4 How to connect wiring to the terminals Caution when wiring cable When stripping off the insulation of a lead wire always use a special tool such as a wire stripper If there is no special tool available ca...

Page 9: ... Center hooks 2 position Top hooks 2 position Top holes 2 position Indoor unit Front panel Bottom hooks 2 position Bottom hooks 2 position Front panel 2 Attach the 4 screws 3 Attach the wire cover Attach the 1 screw 4 Attach the intake grille CAUTION Install the Front panel and Intake grille securely If installation is imperfect the Front panel or Intake grille may fall off and cause injury 10 TES...

Page 10: ...controller holder installation Install the remote controller a maximum distance of 6 m from the remote control signal receiver However when installing the remote controller check that it operates cor rectly Install the remote controller holder to a wall pillar etc with the tapping screw Remote controller holder fixing Remote controller mounting Remote controller holder Tapping screw small 1 Set Re...

Page 11: ...ART STOP button until only the clock is displayed on the remote controller display 2 Press the MODE button for at least 5 seconds to display the current signal code initially set to 3 Press the SET TEMP buttons to change the signal code between Match the code on the display to the air conditioner signal code 4 Press the MODE button again to return to the clock display The signal code will be chang...

Page 12: ... to the installation conditions Incorrect settings can cause the indoor unit to malfunction After the power is turned on perform the FUNCTION SETTING according to the installation conditions using the remote controller The settings may be selected between the following two Function Number or Setting Value Settings will not be changed if invalid numbers or setting values are selected Refer to the i...

Page 13: ...nsor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit er ror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discha...