En-5
8 Single
installation
Fig.
<Top view>
<Front>
<Rear>
200mm
or more
100mm
or more
9 M
Fig. ultiple
installations
<Top view>
<Front>
<Rear>
200mm
or more
B
L6
B
Example :
When B is made 200mm
L6
≥
200+(400-200)×3=800mm
200mm
or more
200mm
200mm
800mm
or more
When installing with the FRONT of the outdoor unit facing the wall side
10
Fig.
<Top view>
500mm
or more
200mm or more
Wall
Wall
11
Fig.
<Top view>
<Front>
<Rear>
500mm
or more
200mm
or more
20mm or
more
20mm or
more
Wall
Wall
Concentrated Installation
(2)
The wall (without height restrictions) must not exist on the both sides (left / right) of
•
outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
Ventilation resistance can be ignorable when the distance from a wall or product,
•
etc. is larger than 2m.
12
Fig.
<Top view>
1000mm
or more
400mm
or more
400mm
or more
400mm
or more
800mm
or more
800mm
or more
13
Fig.
<Top view>
1000mm
or more
400mm
or more
400mm
or more
400mm
or more
500mm
or more
1000mm
or more
When there are obstacles above the product
3. 3. 3.
When there are obstacles above the product, keep the
minimum installation height as shown in the
fi
gure and
install the outlet duct.
When installing the outlet duct, you must set the high
static pressure mode with the push-button switch.
(Similar when installing anti-snow hood)
Setting high static pressure mode
Follow the instructions in the table below to set the high
static pressure mode.
Condition
High static pressure mode
setting
*2
Static Pressure (SP)
*1
:
0
≤
SP
≤
30 (Pa)
Set to Mode 1
Static Pressure (SP)
*1
:
30 < SP
≤
80 (Pa)
Set to Mode 2
Static pressure is the air
fl
ow resistance that includes
*1.
the discharge duct resistance & the other additional resistance like discharge grill
and so on.
Refer to the section on Push Switch Setting in “Chapter 7 Field Setting”.
*2.
Transportation the outdoor unit
3. 4.
Product mass (kg)
AJ
□
A72GALH
262
AJ
□
A90GALH
262
AJ
□
108GALH
262
Hoisting method
When hanging the outdoor unit and conveying it to installation location, hang the
•
unit with rope by passing through the 4 opening holes on bottom of front and rear
side as shown in
fi
gure.
Use 2 ropes at least 8m long. If used shorter length, it may cause to damage to the
•
unit.
Use the suf
fi
ciently strong rope to bear the unit’s weight.
•
Place the protective board or
fi
ller cloth at the place where the cabinet may come
•
into contact with rope to prevent from damages. Without using them, cabinet may
cause to damage or deform.
During the hanging unit, make sure to keep the unit level to prevent from falling.
•
To prevent an unit swing accident or falling down of the unit, do not apply any
•
impact to the unit when it is hanging.
opening space
protective boards
500mm
or more
Outlet duct
9378945074_IM.indb Sec1:5
9378945074_IM.indb Sec1:5
2012-7-19 16:44:28
2012-7-19 16:44:28
Summary of Contents for AirStage AJH108GALH
Page 236: ......