background image

En-3

Energy-saving combination

Combination (HP)

8

10

12

14

16

18

20

22

24

26

28

Outdoor Unit 1 (HP)

8

14

8

10

12

Outdoor Unit 2 (HP)

8

8

8

8

8

Outdoor Unit 3 (HP)

8

8

8

Maximum Connectable 
Indoor Unit

*

*

*

*

30

*

*

33

36

39

42

Combination (HP)

30

32

34

36

38

40

42

44

46

48

Outdoor Unit 1 (HP)

14

12

14

14

14

14

16

Outdoor Unit 2 (HP)

8

12

12

14

14

14

14

Outdoor Unit 3 (HP)

8

8

8

8

12

14

14

Maximum Connectable 
Indoor Unit

45

48

48

48

*

48

48

48

*

*

* Means that the energy-saving combination is unavailable.
When connecting outdoor units, install the outdoor unit with the largest nominal system capac-
ity nearest to the refrigerant pipe and indoor unit, followed by those with lesser nominal system 
capacities. (Outdoor unit 1 

 Outdoor unit 2 

 Outdoor unit 3)

Optional parts

2. 5. 

CAUTION

The following parts are optional parts speci

fi

 c to R410A refrigerant.

Do not use parts other than those listed below.

Outdoor unit branch kit

2. 5. 1. 

Model

Total cooling capacity of indoor unit   (kW)

UTP-CX567A, UTR-CP567X

ALL

Separation tube

2. 5. 2. 

Model

Total cooling capacity of indoor unit   (kW)

UTP-AX090A , UTR-BP090X

28.0 or less

UTP-AX180A , UTR-BP180X

28.1 to 56.0

UTP-AX567A , UTR-BP567X

56.1 or more

Header

2. 5. 3. 

3-6 branches

3-8 branches

Total cooling capacity of indoor unit   (kW)

UTR-H0906L

UTR-H0908L

28.0 or less

UTR-H1806L

UTR-H1808L

28.1 to 56.0

INSTALLATION WORK

3. 

Please obtain the approval of the customer when selecting the location of installation 
and installing the main unit.

Selecting an installation location

3. 1. 

WARNING

Install the unit in a location that can withstand its weight, and where it will not topple 
or fall.

Calculate the proper refrigerant concentration if you will be installing it in an en-
closed location.

 

 

Total amount of replenished refrigerant in refrigerant facility (kg)

    

 

 

Refrigerant concentration (kg/m

3

)

 

Capacity of smallest room where unit is installed (m

3

 

(0.3kg/m

3

)

If the results of the calculation exceed the concentration limit, increase the room 
surface area or install a ventilation duct.

CAUTION

Select an installation location by observing the following precautions:

Install the unit level. (Within 3 degrees)

Install this unit in a location with good ventilation.

If the unit must be installed in an area within easy reach of the general public, install 

as necessary a protective fence or the like to prevent their access.

Install the unit in an area that would not inconvenience your neighbors, as they could 

be affected by the air

fl

 ow coming out from the outlet, noise, or vibration.

If it must be installed in proximity to your neighbors, be sure to obtain their approval.

If the unit is installed in a cold region that is affected by snow accumulation, snow fall, 

or freezing, take appropriate measures to protect it from those elements. 

To ensure a stable operation, install inlet and outlet ducts.

Install the unit in an area that would not cause problems even if the drain water is 

discharged from the unit. Otherwise, provide drainage that would not affect people or 

objects.

CAUTION

Install the unit in an area that has no heat sources, vapors, or the risk of the leakage 

of 

fl

 ammable gas in the vicinity.

Install the unit in an area that is away from the exhaust or vent ports that discharge 

vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, transmission cable and 

remote control cable at least 1 meter away from a television or radio. 

The purpose of this is to prevent TV reception interference or radio noise. (Even if 

they are installed more than 1 meter apart, you could still receive noise under some 

signal conditions.)

Keep the length of the piping of the indoor and outdoor units within the allowable 

range.

For maintenance purposes, do not bury the piping.

Drain processing

3. 2. 

The drain water is discharged from the bottom of the equipment. Construct a drain 

• 

ditch around the base and discharge the drain water properly.

When installing on a roof, perform 

fl

 oor waterproo

fi

 ng properly.

• 

Drain processing:

The drain water from the base of the outdoor unit may generate during operations.

• 

 

Perform drain processing, as necessary.

When you want to prevent the drain water from leaking at the perimeter, construct 

• 

a ditch for the drain water as shown in the 

fi

 gure.

Provide a central drain pan, as necessary.

• 

Outdoor unit

10mm or more

50mm or 

more

Installation dimensions

3. 3. 

CAUTION

When installing the outdoor unit, pay attention to the following items.

Provide suf

fi

 cient installation space, such as transportation route, maintenance 

space, ventilation space, refrigerant piping space, and passageways.

Pay attention to the speci

fi

 cations of the installation space as shown in the 

fi

 gure. 

If the unit is not installed according to speci

fi

 cations, it may cause short circuit or 

poor performance. The unit may be prone to lapse into non-operation due to high 
pressure protection.

Do not place obstructions in the air 

fl

 ow outlet direction. If there is an obstruction in 

the outlet direction, install an outlet duct.

When there is a wall in front of the unit, provide a space of 500mm or more as 
maintenance space.
When there is a wall at the left side of the unit, provide a space of 30mm or more 
as maintenance space.

An outdoor temperature of 35 degrees in air-conditioned operation is assumed for 
the installation space in this item. If the outdoor temperature exceeds 35 degrees 
and the outdoor unit is operating at a load exceeding its rated ability, provide a 
larger inlet space.

If you are installing more outdoor units than indicated here, please ensure suf

fi

 cient 

space or consult your distributing agent as it may affect the performance due to 
short circuit and other problems.

When install near by limited height wall

3. 3. 1. 

Single and multiple installations

(1) 

There are no restrictions on the height of the side wall.

• 

Provide installation spaces L1 and L2 in accordance with the table below according 

• 

to the wall height (front side, rear side) conditions.
Provide installation spaces other than L1 and L2 in accordance with the conditions 

• 

shown in the 

fi

 gure below.

Ventilation resistance can be ignorable when the distance from a wall or product, 

• 

etc. is larger than 2m.

Wall height condition

Necessary installation space

When H1 is 1500 (mm) or less 

L1 

 500 (mm) 

When H1 is 1500 (mm) or more 

L1 

 500+h1÷2 (mm)

When H2 is 500 (mm) or less 

L2 

 100 (mm) 

When H2 is 500 (mm) or more 

L2 

 100+h2÷2 (mm)

9378945104-01_IM.indb   Sec1:3

9378945104-01_IM.indb   Sec1:3

2013-3-12   14:08:13

2013-3-12   14:08:13

Summary of Contents for Airstage AJH108LALH

Page 1: ...or authorized service personnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para téc...

Page 2: ...s exposed to fire it will create a hazardous gas Electrical work must be performed in accordance with this Installation manual by a person certified under the national or regional regulations Be sure to use a dedi cated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fire For wiring use the pres...

Page 3: ...tion Especially when replacing a conventional refrigerant other than R410A model with a new refrigerant R410A model always replace the conventional piping and flare nuts with the R410A piping and flare nuts Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with R22 R407C and for safety Therefore check beforehand The charging port thread ...

Page 4: ... of the leakage of flammable gas in the vicinity Install the unit in an area that is away from the exhaust or vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they a...

Page 5: ...5 2 mm 4 Fig J J Side view Front Rear Wall Wall 5 Fig L5 L5 500 h5 500 h5 H5 H5 Front view Wall Wall 6 Fig Top view 800mm or more 800mm or more 20mm or more 20mm or more L4 L3 L5 L5 7 Fig Top view 500mm or more 1000mm or more 20mm or more 20mm or more L4 L3 L5 L5 When install near unlimited height wall 3 3 2 Single and multiple installations 1 There are no restrictions on the height of the wall Th...

Page 6: ...re is the air flow resistance that includes 1 the discharge duct resistance the other additional resistance like discharge grill and so on Refer to the section on Push Switch Setting in Chapter 7 Field Setting 2 Transportation the outdoor unit 3 4 Product mass kg AJ A72LALH 220 AJ A90LALH 220 AJ 108LALH 275 AJ 126LALH 303 AJ 144LALH 303 Hoisting method When hanging the outdoor unit and conveying i...

Page 7: ...ation 4 1 CAUTION When connecting multiple outdoor units set the nearest outdoor unit to the indoor unit on the refrigerant pipe as the master unit When connecting multiple outdoor units install the outdoor unit with the largest nominal system capacity nearest to the indoor unit on the refrigerant pipe fol lowed by those with less nominal system capacities Capacity Master Slave Always keep to the ...

Page 8: ...a lent COPPER 2 JIS H3300 C1220T H or equivalent Allowable tensile stress 33 N mm 1 2 Allowable tensile stress 61 N mm 2 2 Endurance pressure of the pipes 4 2MPa 3 Please select the pipe size in accordance with local rules A Between outdoor unit and outdoor unit branch kit Table HP Outdoor unit cooling capacity kW Outside diameter mm Branch kit 4 Liquid pipe Gas pipe 8 22 4 12 70 1 2 22 22 7 8 UTP...

Page 9: ...igerant piping system due to deterioration of refrigerant oil For brazing material use phosphor copper that does not require flux Indoor unit pipe connections 5 2 CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B A B B A GOOD Horizontal Vertical Horizontal line or 15 A Outdoor unit or Refrigerant branch kit B Indoor unit or Refrigerant branch kit PROH...

Page 10: ...damage do not make sharp bends Bend the pipe at a radius of 70mm or greater Do not bent pipe many times at same part to prevent break After completing all the pipe connection by brazing perform the indoor unit pipe con nection with a flare joint When removing the pinch pipe or brazing the joint pipe carry out the work while cooling down the 3 way valve sufficiently Braze the joint pipe onto the 3 ...

Page 11: ...e 3 Master unit Slave unit1 Slave unit2 Example 2 Master unit Slave unit1 Slave unit2 CAUTION To prevent the oil from settling in the stopped unit install the pipes between the outdoor units so that they are level or are tilted upward to the outdoor units Examples of multiple unit installation are shown below 1 Installable patterns a GOOD GOOD GOOD Master unit Slave unit 1 Slave unit 2 Master unit...

Page 12: ...f the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is installed outdoors ...

Page 13: ...nit 400 m 2 Length of transmission cable between 1 network segment NS EF EG GH HJ HK 500 m Fig 2 KL 400 m Fig 2 3 Length of transmission cable between outdoor units in a refrigerant system MN 18 m NP 18 m Left view Front view Unit mm Ø 50 Ø 34 5 Ø 43 7 Ø 22 2 Ø 50 Ø 34 5 Ø 43 7 Ø 22 2 Selecting power supply cable and breaker 6 4 CAUTION Obtain the distribution network operator s agreement about th...

Page 14: ...nt system 1 Refrigerant system 2 Refrigerant system 3 Transmission line Transmission line Transmission line Wiring procedure 6 6 Remove the cover of the electrical compartment and follow the terminal plate to con nect the electric cables to the terminal After connecting the cables secure them with the cable ties Connect the cables without applying excessive tension Cable routing Secure with a bind...

Page 15: ...be damaged Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of sealed cable to earth Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables RB IN Cable clip Cable tie Accessory 40 mm or more 8 to 10 mm External input and external output 6 7 Terminal position 6 7 1 Output 2 CN137 Blu...

Page 16: ...ut indicates the outdoor unit and connected indoor unit s Normal or Error status Operation status Master unit only This output indicates the outdoor unit s Operation status Connector Output voltage Status CN136 Black 0 V Normal DC 12 to 24 V Error CN137 Blue 0 V Stop DC 12 to 24 V Operation 1 2 5 6 7 P C B CN136 Black or CN137 Blue DC power supply External 12 to 24 V Connected load Operation Indic...

Page 17: ...or of a signal amplifier refer to the installation manual of the signal amplifier When settin g multiple terminal resistors take note of the following items How many network segments are there in a VRF system Where will you set the terminal resistors in a network segment Condition for 1 segment Total number of outdoor and indoor units and signal amplifiers is less than 64 or the total length of th...

Page 18: ...tection fan mode 0 1 This mode operates the fans of outdoor units in order to prevent the units from stop ping operation when they are covered by snow 23 Interval setting for snow falling protection fan mode 1 Standard 30 minutes 2 3 0 0 Short 1 5 minutes 0 1 Short 2 10 minutes 0 2 Short 3 20 minutes 0 3 When the snow falling protection fan mode is set the operation interval of the fans of outdoor...

Page 19: ... to the procedures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button Press the ENTER button for more than 3 seconds MODE EXIT SELECT ENTER ENTER 1 FUNCTION Setting 7 segment LED indicator LED105 LED104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT butto...

Page 20: ...1 Signal amplifier wiring example 2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below 2 12 8 21 4 1 26 3 3 1 4 25 6 8 17 11 28 12 18 1 10 23 4 22 8 9 2 3 4 Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit 1 Signal amplifier 1 Signal amplifier NOTE The automatic address function can be use...

Page 21: ...ess all operations are complete Do not block the walls and the ceiling until the sealing test and charging of the refrigerant gas have been completed After connecting the pipes perform a sealing test Recheck that the spindle of the 3 way valve are closed before performing a sealing test Fig B Pour nitrogen gas through both the liquid pipe and the gas pipe Pressurize nitrogen gas to 4 2 MPa to perf...

Page 22: ... value to 2 dec imal places Model HP d Factory charged amount kg a Additional amount for outdoor unit kg AJ A72LALH 8HP 11 20 0 AJ A90LALH 10HP 11 20 0 AJ 108LALH 12HP 11 80 1 20 AJ 126LALH 14HP 11 80 3 30 AJ 144LALH 16HP 11 80 3 30 Diameter of liquid pipe mm b Additional amount for pipe length kg m Ø6 35 0 021 Ø9 52 0 058 Ø12 70 0 114 Ø15 88 0 178 Ø19 05 0 268 Calculation of additional amount for...

Page 23: ...tdoor units it may take several minutes for the system to start operating after settings for the test run are complete After the test run settings are complete all the outdoor units and the connected indoor units will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor sto...

Page 24: ...eration E 6 9 1 Outdoor unit transmission PCB parallel communication error Outdoor unit sensor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 1 2 Outdoor unit discharge temp thermistor 2 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 2 2 Outdoor unit compressor temp thermistor 2 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air...

Page 25: ...tion is max cooling condition refer to item 16 Air circulation 9 Air circulation Noise level 10 Noise level Refrigerant 11 Refrigerant type and initial charging amount Max pressure HP LP 12 Means pressure of High Pressure side Low Pressure side Protection 13 Protection level against dust and water Working temperature 14 Working temperature Condition of cooling heating 15 Dry bulb temperature and w...

Reviews: