background image

En-10

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

*a

*b

*1

CNA01

CNA03

*a

*a

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 
resistance

Load 
resistance

Load 
resistance

DC power supply
12 to 24V

Connected unit

P.C.B

*1: Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample 

surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.

*a: The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)

Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).

*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

CNA01

CNA01

CNA01

DC power supply 
12 to 24V

Connected unit

Load 
resistance

P.C.B

P.C.B

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 
resistance

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

CNA02

*c

*c

*c

*d

CNA04

P.C.B

GND

Ch 1

Ch 3

Ch 2

Connected unit

*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.

K1

CNA02

CNA02

CNA02

K2

K3

K4

K5

K6

P

o

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

P.C.B

P.C.B

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

 Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.

Pulse

Edge

The width of pulse must be 
longer than 200 msec.

DIP switch [SET2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

 When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Operation

ON 

 OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

 When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates.

9373370444_IM.indb   10

9373370444_IM.indb   10

29/11/2017   AM 11:48:43

29/11/2017   AM 11:48:43

Summary of Contents for Airstage ASUB18TLAV1

Page 1: ...Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado PART No 9373370444 9373370444_IM indb 1 9373370444_IM indb 1 29 11 2017 AM 11 48 42 29 11 2017 AM 11 48 42 ...

Page 2: ...aker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical c...

Page 3: ...ump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of 5 Torr 755 mm Hg 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or othe...

Page 4: ... install the unit where it will be exposed to direct sunlight 3 2 Installation dimension For the drain hose exten sion use a drain hose with a 5 8 in 16 mm inside diameter 71 in 1800 mm or more 60 in 1500 mm or more Right side 8 in 200 mm or more 3 in 60 mm or more Left side 2 in 50 mm or more Wall hook bracket 3 3 Installing the unit WARNING Install the air conditioner in a location which can wit...

Page 5: ...f copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Wall hook bracket Tapping screw big 3 3 2 Cutting the hole in the wall for the connecting piping WARNING If the wall pipe is not used the cable may touch metal and cause electric leakage 1 Cut a 3 1 8 in 80 mm diameter hole in the wall ...

Page 6: ...A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter in mm Width across flats of Flare nut in mm 1 4 6 35 11 16 17 3 8 9 52 7 8 22 1 2 12 70 1 26 5 8 15 88 1 1 8 29 3 4 19 05 1 7 16 36 4 3 2 Bending pipes The pipes are shaped by your hands or pipe bender Be carefu...

Page 7: ...nd positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable ...

Page 8: ...WORKS compatible cable Remote con troller cable 2 wire type 22 AWG to 16 AWG 0 33 to 1 25 mm Sheathed PVC cable Non polar 2 core twisted pair 18AWG Thermostat cable 2 core Use sheathed non twisted pair cable Remote con troller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method Example 2 2 2 Outdoor unit or RB unit 1 Breaker 1 Ground Fault Equipment Breaker GFEB Brea...

Page 9: ...loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be dam aged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break...

Page 10: ...al parts 6 6 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 49...

Page 11: ... Connected unit c Select very low current use contacts usable at DC 12 V DC 1 mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor ...

Page 12: ...ing when turning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting OFF For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Please set by either of the methods...

Page 13: ...lt in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Setting Setting range Type of switch Remote controller ad dress 0 to 15 Setting example 0 RC AD Example If 4 indoor units are connected Remote controller Indoor unit Indoor unit In...

Page 14: ...t Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is performed from an external controller all refrigerant sys tems will be disabled If forced stop is set indoor unit stops by the input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced Stop Error report target 47 00 All ...

Page 15: ... Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON...

Page 16: ...e used for the test run 9 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When the air conditioner is being test run the OPERATION and TIMER indicator lamp flash slowly at the same time 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is...

Page 17: ...1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circula tion 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RNKU ...

Reviews: