background image

En-7

6.1. Electrical 

requirement

• Select the power cable type and size 

in accordance with relevant local and 
national regulations.

Voltage rating

208/230 V

Operating range

187 to 253 V

• Specifications for local wiring power cord and branch wiring are in compliance with local 

code

• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform 
the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR 

(Fuse capacity)

• MCA: Minimum Circuit Ampacity
• MAX. CKT. BKR : Maximum Circuit 

Breaker

ASUB18TLAV1

0.53 A

15 A

ASUB24TLAV1

0.65 A

When the power crossover wiring is done, make it so that the total of the MCA of the con-
nected RB units and indoor units does not exceed the 11 A. For RB unit MCA, refer to the 
RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Earth leakage breaker requirements

Breaker capacity

Maximum connect-
able “indoor units” 

or “indoor units + 

RB units” (*1)

*1:  Heat pump type: indoor units, 

Heat recovery type: indoor units 
and RB units.

*2:  If the 100 mA capacity breaker is 

not provided, split the quantity of 
the indoor units into small groups 
of 9 units or less and provide a 
breaker with capacity of 30 mA for 
each group.

30 mA, 0.1 sec or less

36 or less

100 mA, 0.1 sec or less

37 to 121 (*2)

6.1.1 Cable speci

fi

 cations

Cable size

Cable type

Remarks

Transmission 
cable

22 AWG
(0.33 mm²)

LEVEL 4 (NEMA) non-polar 
2 core, twisted pair solid core 
diameter 0.026 in (0.65mm)

LONWORKS ® 
compatible cable

Remote con-
troller cable 
(2-wire type)

22 AWG to 16 AWG 
(0.33 to 1.25 mm²)

Sheathed PVC cable

Non polar 2 core, 
twisted pair

18AWG

Thermostat cable 2 core

Use sheathed non 
twisted pair cable

Remote con-
troller cable 
(3-wire type)

22 AWG
(0.33 mm²)

Sheathed PVC cable

Polar 3 core

6.2. Wiring 

method

Example

*2

*2

*2

 

Outdoor unit or RB unit *1

Breaker 1:  Ground Fault Equipment 

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker 

(MAX. CKT. BKR)

Transmission

Transmission

Indoor unit

Remote controller 

(Master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 
 control

Breaker 2

Breaker 2

Breaker 2

Breaker 1

Breaker 1

Breaker 1

Remote controller 

(Slave)

Remote 

controller

*1: When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
*3: When connecting the 2-wire type remote controller, Y3 is not used.

(Crossover wiring of power supply)

Indoor unit

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Breaker 2

Breaker 1

Power supply

: Disconnect switch

6.3. Unit 

wiring

• Before attaching the cable to terminal block.

6.3.1. Power supply cable

6-7/8 in (175 mm)

6-1/2 in (165 mm)

Conduit connector

Conduit holder

Earth 
(ground) cable

A.

 

For solid core wiring

(1) To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2) Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3) Use an appropriate screwdriver to tighten the terminal screws.
 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-
aged and prevent the screws from being properly tightened.

(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 1 in 
(25 mm)

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Loop

Terminal block

Cable end (Loop)

Cable

Cable

9373370444_IM.indb   7

9373370444_IM.indb   7

29/11/2017   AM 11:48:43

29/11/2017   AM 11:48:43

Summary of Contents for Airstage ASUB18TLAV1

Page 1: ...Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado PART No 9373370444 9373370444_IM indb 1 9373370444_IM indb 1 29 11 2017 AM 11 48 42 29 11 2017 AM 11 48 42 ...

Page 2: ...aker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical c...

Page 3: ...ump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of 5 Torr 755 mm Hg 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or othe...

Page 4: ... install the unit where it will be exposed to direct sunlight 3 2 Installation dimension For the drain hose exten sion use a drain hose with a 5 8 in 16 mm inside diameter 71 in 1800 mm or more 60 in 1500 mm or more Right side 8 in 200 mm or more 3 in 60 mm or more Left side 2 in 50 mm or more Wall hook bracket 3 3 Installing the unit WARNING Install the air conditioner in a location which can wit...

Page 5: ...f copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Wall hook bracket Tapping screw big 3 3 2 Cutting the hole in the wall for the connecting piping WARNING If the wall pipe is not used the cable may touch metal and cause electric leakage 1 Cut a 3 1 8 in 80 mm diameter hole in the wall ...

Page 6: ...A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter in mm Width across flats of Flare nut in mm 1 4 6 35 11 16 17 3 8 9 52 7 8 22 1 2 12 70 1 26 5 8 15 88 1 1 8 29 3 4 19 05 1 7 16 36 4 3 2 Bending pipes The pipes are shaped by your hands or pipe bender Be carefu...

Page 7: ...nd positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable ...

Page 8: ...WORKS compatible cable Remote con troller cable 2 wire type 22 AWG to 16 AWG 0 33 to 1 25 mm Sheathed PVC cable Non polar 2 core twisted pair 18AWG Thermostat cable 2 core Use sheathed non twisted pair cable Remote con troller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method Example 2 2 2 Outdoor unit or RB unit 1 Breaker 1 Ground Fault Equipment Breaker GFEB Brea...

Page 9: ...loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be dam aged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break...

Page 10: ...al parts 6 6 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 49...

Page 11: ... Connected unit c Select very low current use contacts usable at DC 12 V DC 1 mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor ...

Page 12: ...ing when turning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting OFF For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Please set by either of the methods...

Page 13: ...lt in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Setting Setting range Type of switch Remote controller ad dress 0 to 15 Setting example 0 RC AD Example If 4 indoor units are connected Remote controller Indoor unit Indoor unit In...

Page 14: ...t Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is performed from an external controller all refrigerant sys tems will be disabled If forced stop is set indoor unit stops by the input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced Stop Error report target 47 00 All ...

Page 15: ... Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON...

Page 16: ...e used for the test run 9 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When the air conditioner is being test run the OPERATION and TIMER indicator lamp flash slowly at the same time 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is...

Page 17: ...1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circula tion 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RNKU ...

Reviews: