background image

En-4

3. Clean the air 

fi

 lters.

Remove the dust from the air 

fi

 lters by vacuuming or washing them. After 

washing, allow the air 

fi

 lters to dry thoroughly in an area protected from 

sunlight.
•  Dust can be cleaned from the air 

fi

 lter either with a vacuum cleaner, 

or by washing the 

fi

 lter in a solution of mild detergent and warm water. 

If you wash the 

fi

 lter, be sure to allow it to dry thoroughly in a shady 

place before reinstalling.

•  If dirt is allowed to accumulate on the air 

fi

 lter, air 

fl

 ow will be reduced, 

lowering operating ef

fi

 ciency and increasing noise.

4. Re-attach the air 

fi

 lters to the intake grille.

(1) Replace the air 

fi

 lter into its holder.

(2) Make sure that the air 

fi

 lter makes 

contact with the 

fi

 lter stopper when it 

is replaced into its holder.

5. Close the intake grille and push the intake grille’s 

hooks outward.

 

Dust can be cleaned from the air 

fi

 lter either with a vacuum cleaner, 

or by washing the 

fi

 lter in a solution of mild detergent and warm water. 

If you wash the 

fi

 lter, be sure to allow it to dry thoroughly in a shady 

place before reinstalling.

 

If dirt is allowed to accumulate on the air 

fi

 lter, air

fl

 ow will be reduced, 

lowering operating ef

fi

 ciency and increasing noise.

 

After turning the power on, press the 

fi

 lter button on the remote control 

to turn off the 

fi

 lter lamp. (Refer to the operation manual packed with 

remote control unit for details.)

Cleaning the body

Wash the body with warm water, and then dry with a clean and soft cloth.

When not using for an extended period

Leave the breaker on for at least 12 hours before starting operation when 
it is to be used again.

TROUBLESHOOTING

The following conditions are not breakdowns or op-
eration failures.

Doesn’t operate immediately:

 

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent fuse 
blowouts.

 

Whenever the electrical breaker is turned off then on again, the protec-
tion circuit will operate for about 3 minutes, preventing unit operation 
during that period.

Air

fl

 ow is weak or stops:

 

When Heating operation is started, indoor unit’s fan may temporarily 
stop, to allow internal parts to warm up.

 

During Heating operation, if the room temperature rises above the 
thermostat setting, the outdoor unit will stop, and the indoor unit’s fan 
will stop. If you wish to warm the room further, set the thermostat for a 
higher setting.

 

During oil recovery operation, the air

fl

 ow may stop for approximately 

10 minutes. (See page 2)

 

During Heating operation, the unit will temporarily stop operation (be-
tween 4 and 15 minutes) as the Automatic Defrosting mode operates. 
(See page 2)

 

The fan may operate at low speed during Dry operation or when the 
unit is monitoring the room’s temperature.

 

In the monitor AUTO operation, the fan will operate at low speed.

Flashing lamps:

 

The OPERATION indicator lamp (green) 

fl

 ashes:

An oil recovery operation is being performed. (See page 2)

 

The OPERATION indicator lamp (green) 

fl

 ashes:

An automatic defrosting operation is being per formed. (See page 2)

 

The OPERATION indicator lamp (green) and TIMER indicator lamp 
(orange) are 

fl

 ashing alternately:

It has recovered from a power outage. 

 

The OPERATION indicator lamp (green) and TIMER indicator lamp 
(orange) are 

fl

 ashing simultaneously:

It is operating in trial operation mode. Ask a manager as there may be 
maintenance being conducted.

 

The OPERATION indicator lamp (green) lights up and the TIMER 
indicator lamp (orange) 

fl

 ashes:

This is the standby state. (See page 2)

Noise is heard:

 

In the following conditions there are sounds of water 

fl

 owing from the 

indoor unit and the operation sound becomes loud. These are the 
sounds of the 

fl

 owing of refrigerant.

    When operation starts 

When oil recovery operation 

fi

 nishes 

When automatic defrosting operation 

fi

 nishes

 

During operation, a slight squeaking sound may be heard. This is the 
result of minute expansion and contraction of the panel due to tem-
perature changes.

 

During Heating operation, a sizzling sound may be heard occasionally. 
This sound is produced by the Automatic Defrosting operation. (See 
page 2)

Smells:

 

Some smell may be emitted from the indoor unit. This smell is the 
result of room smells (furniture, tobacco, etc.) which have been taken 
into the air conditioner.

Fog comes out of the indoor unit:

 

During Cooling operation, a thin mist may be seen emitted from the 
indoor unit. This results from the sudden Cooling of room air by the air 
emitted from the air conditioner, resulting in condensation and misting.

Steam comes out of the indoor unit:

 

During Heating operation, the outdoor unit’s fan may stop, and steam 
may be seen rising from the unit. This is due to the Automatic Defrost-
ing operation. (See page 2)

Water is produced from the outdoor unit:

 

During Heating operation, water may be produced from the outdoor 
unit due to the Automatic Defrosting operation.

The following conditions may not be breakdowns so 
check again.

Doesn’t operate at all:

 

Has there been a power failure?

 

Has a fuse blown out, or a circuit breaker been tripped?

 

Is the main power switch set to the OFF position?

 

Are you trying to engage in an operation different from the priority 
state? (See page 3)

 

Is it in standby state? (See page 3)

 

Is the Auto off operation of the Human sensor setting active? (See 
page 2)

The operation mode cannot be changed:

 

Are you trying to change to an operation different from the priority 
conditions? (See page 3)

Poor Cooling (or Heating) performance:

 

Did you adjust the room temperature settings (thermostat) correctly?

 

Is the air 

fi

 lter dirty? (See page 3)

 

Are the air conditioner’s inlet port or outlet port blocked?

 

Is there a window or door open?

 

In the case of Cooling operation, is a window allowing bright sunlight to 
enter? (Close the curtains.)

9369313332_OM.indb   4

9369313332_OM.indb   4

12/19/2018   2:47:18 PM

12/19/2018   2:47:18 PM

Summary of Contents for Airstage AUXM018GLEH

Page 1: ...L DE FUNCIONAMENTO UNIDADE INTERIOR Tipo cassete Guarde este manual para consulta futura РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ВНУТРЕННИЙ МОДУЛЬ кассетного типа Сохраните данное руководство для последующего использования KULLANIM KILAVUZU İÇ ÜNİTE Kaset tipi Bu kılavuzu ileride başvurmak üzere saklayın MODE D EMPLOI UNITÉ INTÉRIEURE Type cassette Conservez ce manuel pour pour toute référence ultérieure Deut...

Page 2: ...and for damage Operate only with air filters installed Do not drink the water drained from the air conditioner Do not apply any heavy pressure to radiator fins Do not use inflammable gases near the air conditioner Do not touch the piping during operation Ensure that any electronic equipment is at least 1 m away from either the indoor or outdoor units This appliance is not intended for use by perso...

Page 3: ... done in the remote control ler of the following UTY RNR Z wired remote controller Refer to the operating manual of the remote controller HUMAN SENSOR Optional About the human sensor The Human sensor detects whether there are people in the room by looking for movement by people in the room Limited to only when Human censor kit is attached Setting of Human sensor can be done in the remote controlle...

Page 4: ...ove for a long period of time When someone is hidden behind a sofa other furniture glass or in similar situations When someone is wearing extremely thick clothing and has their back facing the sensor Situations in which the sensor will incorrectly detect people in the room even when there is no one there When there is a dog or a cat moving around in the room When the wind is making curtains or pla...

Page 5: ...eed Flashing lamps The OPERATION indicator lamp green flashes An oil recovery operation is being performed See page 2 The OPERATION indicator lamp green flashes An automatic defrosting operation is being per formed See page 2 The OPERATION indicator lamp green and TIMER indicator lamp orange are flashing alternately It has recovered from a power outage The OPERATION indicator lamp green and TIMER ...

Page 6: ...3 8 0 BTU h 21 500 27 300 34 100 21 500 27 300 INPUT POWER W 20 25 49 40 40 CURRENT A 0 20 0 24 0 41 0 34 0 34 SOUND PRESSURE LEVEL HIGH dB A 33 35 40 38 38 MED HIGH dB A 32 33 36 37 37 MED dB A 31 32 34 36 36 MED LOW dB A 30 31 32 35 35 LOW dB A 29 30 31 34 34 QUIET dB A 28 28 28 33 33 DIMENSIONS WEIGHT HEIGHT mm 246 288 WIDTH mm 840 DEPTH mm 840 WEIGHT kg 24 24 5 26 5 MODEL AUXK 030GLEH AUXK 034...

Page 7: ...9369313332_OM indb 6 9369313332_OM indb 6 12 19 2018 2 47 18 PM 12 19 2018 2 47 18 PM ...

Page 8: ...9369313332_OM_AR indd 7 9369313332_OM_AR indd 7 12 19 2018 2 37 17 PM 12 19 2018 2 37 17 PM ...

Reviews: