3.3.  Installation  dimensions

Provide a service access for inspection purposes.

Do not place any wiring or illumination in the service space, as they will impede service.

3.3.1.  Installation  dimensions

Front view

Service 

space

Ceiling board

150 or more

Strong and durable ceiling

400 or more

5 to 10

20 or more

Cassette grille (optional parts)

Unit: mm

Service access 

 

(recommend)

Floor

Maximum height from floor to ceiling

• Standard mode: 1800 to 2700

• High Ceiling mode: 1800 to 3200

Be sure to make the function settings with 

the remote controller according to the 

installed ceiling height.

1000 or 

more

Obstruction

Unit: mm

Right side view

Air

Air

5 or more

Cassette grille (optional parts)

150 or more

Unit: mm

3.4. Installing the unit

 WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 

location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.

• You can use the accessory template to help you install the indoor unit. 

• The template helps you determine the appropriate locations for suspension bolts and 

pipe openings (drain pipe and connection cable).

3.4.1.  Indoor unit dimensions

Top view

Unit: mm

A

 (Hanger bolt pitch)

C

 (Ceiling opening)

D

 (Cassette grille size)

590 (Ceiling opening)

295 (Hanger bolt pitch)

620 (Cassette grille size)

B

 (Indoor unit size)

570 (Indoor unit size)

Model

AUXV004/007/009/012

AUXV014/018/024

Dimensions

A:

752

1152

B:

785

1190

C:

920

1330

D:

950

1360

Right side view

276

43

43

43

176

133

440

570

Ceiling board

Cassette grille (optional parts)

Unit: mm

Liquid pipe port

Gas pipe port

Drain port

3.4.2.  Fix the unit

 CAUTION

Fasten the unit securely with nuts A and B.

(1)  Hang the unit

Hanger bolt

Nut A 

 

(locally pur

-

chased)

Nut B 

 

(locally purchased)

Washer 

 

(accessories)

Hanger

Hanger bolt

Nut A 

 

(locally purchased)

Washer 

 

(accessories)

Nut B 

 

(locally purchased)

Unit

Hanger

If the length of hanger bolt is over 20 mm, it will be not convenient for following works:

• The opening and closing of control box cover

• Replacement of drain pump

20 or less

20 or less

Control box cover 

Drain pump cover

Unit: mm

(2)  Leveling
Base horizontal direction leveling on top of the unit.

Front view

Give a slight tilt to the drain port side. The tilt should be in the range of 0 mm to 10 mm.

Ceiling

Level

10 or less

Drain port

Drain port

GOOD

PROHIBITED

Unit: mm

9384723017_IM.indb   3

14-Oct-20   13:29:48

Summary of Contents for Airstage AUXV004GLEH

Page 1: ...a cassetta flusso a 1 via A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος κασέτας ροής 1 δρόμου Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 1 via Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙМОДУЛЬ 1 стороннийкассетноготипасвоздушны...

Page 2: ...g consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture ...

Page 3: ...te metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes...

Page 4: ...lp you install the indoor unit The template helps you determine the appropriate locations for suspension bolts and pipe openings drain pipe and connection cable 3 4 1 Indoor unit dimensions Top view Unit mm A Hanger bolt pitch C Ceiling opening D Cassette grille size 590 Ceiling opening 295 Hanger bolt pitch 620 Cassette grille size B Indoor unit size 570 Indoor unit size Model AUXV004 007 009 012...

Page 5: ...and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units or RB unit respectiv...

Page 6: ... accessories around the gas pipe and liquid pipe of indoor side After installing the coupler heat insula tion wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation accessories Cover this portion with he...

Page 7: ...AUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable togeth...

Page 8: ...iring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal s...

Page 9: ...n Fast flashing every 0 1 second There is a fault with the communication board or the main board Blinking repeat 3 seconds ON and 1 second OFF The indoor unit is turned off and power is supplied from the External power supply unit optional to the indoor unit PCB 6 5 3 Connection methods Wire modification for External input output wire 1 Remove insulation from wire at tached to wire kit connector 2...

Page 10: ...t DC 12 V DC 1 mA or less d The wiring is different from apply voltage terminals Be sufficiently careful when wir ing When connected to dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor unit Indoor unit Indoor unit Input device 2 Input device 1 K1 ...

Page 11: ...al for detailed setting informa tion Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing the field setting 7 1 Setting the address 7 1 1 Manual address setting method If the receiver unit is attached the indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the DIP s...

Page 12: ...aise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage 01 Disable Cool Air Prevention 43 00 Super low Restrain the cold airflow with making the airflow lower when starting heat ing operation To correspond to the ventilation set to 01 01 Follow the setting on the remote controller Exte...

Page 13: ...vice No operation After installation is completed has the proper operation and handling been explained to the user 12 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns Refer to the following table for lamp blink ...

Reviews: