Error Contents :
Power Supply Error
Symptom :
No display
Details :
Condition of occurrence : Normal power is not supplied. 7 segment indicator is defective.
Release condition : Normal power is supplied. 7 segment indicator is normal.
Cause 1 :
Power supply cable installation is defective or open.
Check following installation and reset the power supply.
(1) Installation of power cable on power supply terminal.
(2) Connection between Power PCB and Terminal.
(3) Connector condition between power PCB and Main PCB.
Error Contents :
Communication Error
Symptom :
Error code does not appear [ _ ]
Communication error occurs at connected equipment side.
Details :
Condition of occurrence : Network cable defective. External noise is applied.
Overlapping of Signal Amplifier address setting. System design mistake.
Release condition : Network cable
is connected. External noise is removed.
Overlapping of Signal Amplifier has been corrected. System design is normal.
OK
Cause 2 : External noise
OK
Cause 4 : System Design mistake
Check following items.(Refer to Installation Manual)
(1) Installation location of Terminal Resistor.
(Only 1 location on NS*)
(2) Cable length. (Within 500m maximum on NS*)
(3) Number of units connected
(Up to 64 units maximum on NS*)
(4) Communication cable specification.
(Use specified type.)
(5) Number of Signal Amplifier installed.
(Up to 8 units max. on system)
(6) Network cable shall not be connected in loop.
*NS : Network Segment
OK
Cause 1 :
Network cable installation is defective or open.
Check Network cable installation.
Cause 3 :
Overlapped address of Signal Amplifier.
Set up address again which does not overlap on system.
After set up again, reset the power supply.
Remove external noise around Signal Amplifier or
Network cable. (Keep enough distance)
2. Signal Amplifier (UTY-VSGX)
Cause 2 : Signal Amplifier is defective.
If normal voltage (Rated Voltage) is applied to power supply
terminal of Signal Amplifier,
there is a possibility of defective
PCB. Proceed as follows.
Replace Signal Amplifier.
OK
AC
Trouble shooting 58
Trouble shooting 59
04-65
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......