Check Point 1 : Check connections
Check connection of connector.
AJ*A36, 45, 54LALH
>> CN107
(Loose connector or open cable)
Check Point 3 : Check Voltage from Controller PCB
Remove connector and check the voltage (Rated AC voltage).
>> If the voltage does not appear, replace Controller PCB.
Check Point 2 : Check Solenoid Coil
Remove connector and check if coil is open.
(Normal resistance value of each coil: 1495 ± 7% )
>> If Resistance value is abnormal, replace Solenoid Coil.
SERVICE PARTS INFORMATION 11
Outdoor Unit Solenoid Valve
(SV2)
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
AC
AC
SOLENOIDE COIL
SOLENOIDE COIL
Normal Operation
Pipe (In) TEMP. Hi,
Pipe (Out) TEMP.Normal
Protection Function
Pipe (In) TEMP. = Pipe (Out) TEMP.
OPEN
CLOSE
Check Point 4 : Check opening & closing operation of Valve
Depending on either during operation or protection control, check if Valve is operating normally.
(When Valve opens, there is no temperature difference between Inlet and Outlet.)
(1)
(2)
If the valve closes by removing the connector of the valve
which does not close, it is considered to be Controller PCB
failure. Replace Controller PCB.
If it does not close by removing connector, there is a
possibility of (1) clogging by dirt, or (2) deformation by
the heat at the time of Solenoid Valve installation.
In this case, replace Solenoid Valve.
C
N
10
7
1
2
1
2
SV2
BLUE
BLUE
AC
04-95
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......