02-12
Protective Function Detect Parts
Operating Condition
Operation
Low Pressure
Protection 4
Low Pressure
Sensor
COOL HEAT
High Pressure
Protection Stop 1
High Pressure
Sensor
<Pattern starting condition>
High-pressure 4.00MPa
<Pattern reset condition>
5 minutes have elapsed and high-pressure 3.50MPa
Compressor stopped
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition>
Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition>
5 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
High Pressure
Protection Stop 2
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
Error display
<Starting conditions>
Low-pressure 0.20MPa
<Reset conditions>
5 minutes have elapsed and low-pressure 0.30MPa
SV2 ON
Low Pressure
Protection 1
Low Pressure
Sensor
<Starting conditions>
Low-pressure 0.10MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.17MPa
SV2 ON
<Starting conditions>
3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly
(450pls)
Abnormal Low
Pressure Protection
Control
Low Pressure
Sensor
<starting condition>
Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure
Protection Stop
Low Pressure
Sensor
<Pattern starting condition>
Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition>
3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition>
Pattern generated 5 times within 180 minutes.
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor stopped
(permanent stop)
Error display
Low Pressure
Sensor
Low Pressure
Protection 2
<reset condition>
3 minutes have elapsed and
low-pressure 0.18MPa
Compressor stopped
DISPLAY
Compressor Temp
Protection Stop
Compressor
Temp
Thermistor
<Pattern starting condition>
Compressor temperature fixed value (110°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
Compressor stopped
Compressor stopped
(permanent stop)
Error display
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
P2
EA41
EA31
EA42
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
P2
Compressor stopped
Summary of Contents for Airstage J-II
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL ...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN ...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION ...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING ...
Page 73: ......
Page 170: ......
Page 171: ...5 APPENDING DATA UNIT ...
Page 172: ......
Page 174: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 175: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 03 ...
Page 176: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 04 ...
Page 177: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 05 ...
Page 178: ...MODEL ARXB45 05 06 ...
Page 179: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 07 ...
Page 180: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 08 ...
Page 181: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 09 ...
Page 182: ...MODELS AB A12 AB A14 AB A18 AB A24 05 10 ...
Page 183: ...MODELS AB A12LBTH AB A14LBTH 05 11 AB A18LBTH AB A24LBTH ...
Page 184: ...05 12 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 185: ...05 13 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 186: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 187: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 188: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 189: ...05 17 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 190: ...05 18 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit ...
Page 195: ...6 DISASSEMBLY PROCESS ...
Page 196: ......