1-7 Field Setting / Function Setting for Indoor unit
Indoor unitfield setting
setting by
remote controller
Setting Mode
ITEM
CODE No.
ITEM
CODE No.
Setting Function
Default
Classification
01
Address
Indoor unit address
00~63
00~63
02
Refrigerant circuit address
00~99
00~99
11
Filter indicator Interval
00
01
Default
Longer
02
Shorter
Filter
13
Filter sign display
00
Enable
01
Disable
02
Display only on central remote control
Airflow
20
Ceiling airflow
00
Default
01
High ceiling
23
Vertical airflow direction
00
Default
01
Raise
24
Horizontal swing airflow direction
00
Default
01
Left half
02
Right half
26 *1
00
01
02
03
04
05
06
07
08
09
31
Static Pressure setting
- Slim Duct type -
The Range of static pressure is
different from one model to other.
SP mode 00 [ 0 in.WG ( 0 Pa) ]
SP mode 01 [ 0.04 in.WG (10 Pa) ]
SP mode 02 [ 0.08 in.WG (20 Pa) ]
SP mode 03 [ 0.12 in.WG (30 Pa) ]
SP mode 04 [ 0.16 in.WG (40 Pa) ]
SP mode 05 [ 0.20 in.WG (50 Pa) ]
SP mode 06 [ 0.24 in.WG (60 Pa) ]
SP mode 07 [ 0.28 in.WG (70 Pa) ]
SP mode 08 [ 0.32 in.WG (80 Pa) ]
SP mode 09 [ 0.36 in.WG (90 Pa) ]
Normal SP [ 0.10 in.WG (25 Pa) ]
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
31
SP mode 00 [ 0 in.WG ( 0 Pa) ]
SP mode 01 [ 0.04 in.WG (10 Pa) ]
SP mode 02 [ 0.08 in.WG ( 20 Pa) ]
SP mode 03 [ 0.12 in.WG ( 30 Pa) ]
SP mode 04 [ 0.16 in.WG ( 40 Pa) ]
SP mode 05 [ 0.20 in.WG ( 50 Pa) ]
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
Normal SP [ 0.16 in.WG ( 40 Pa) ]
Static Pressure setting *2*3
- Duct (middle pressure) type -
The Range of static pressure is
different from one model to other.
Static Pressure setting *4*5
- Duct (high pressure) type -
The Range of static pressure is
different from one model to other.
04
05
06
07
08
09
10
11
12
13
14
31
SP mode 04 [ 0.16 in.WG ( 40 Pa) ]
SP mode 05 [ 0.20 in.WG ( 50 Pa) ]
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
Normal SP [ 0.60 in.WG ( 150 Pa) ]
30
SP mode 30 [ 1.20 in.WG ( 300 Pa) ]
15
16
17
18
19
20
21
22
23
24
25
SP mode 15 [ 0.60 in.WG ( 150 Pa) ]
SP mode 16 [ 0.64 in.WG ( 160 Pa) ]
SP mode 17 [ 0.68 in.WG ( 170 Pa) ]
SP mode 18 [ 0.72 in.WG ( 180 Pa) ]
SP mode 19 [ 0.76 in.WG ( 190 Pa) ]
SP mode 20 [ 0.80 in.WG ( 200 Pa) ]
SP mode 21 [ 0.84 in.WG ( 210 Pa) ]
SP mode 22 [ 0.88 in.WG ( 220 Pa) ]
SP mode 23 [ 0.92 in.WG ( 230 Pa) ]
SP mode 24 [ 0.96 in.WG ( 240 Pa) ]
SP mode 25 [ 1.00 in.WG ( 250 Pa) ]
26
27
28
29
SP mode 26 [ 1.04 in.WG ( 260 Pa) ]
SP mode 27 [ 1.08 in.WG ( 270 Pa) ]
SP mode 28 [ 1.12 in.WG ( 280 Pa) ]
SP mode 29 [ 1.16 in.WG ( 290 Pa) ]
*5: ARUH72TLAV : 04 (SP mode 04) - 27 (SP mode 27) and 31 (Normal SP)
ARUH96TLAV , ARUH72TLAV1 : 05 (SP mode 05) - 30 (SP mode 30) and 31 (Normal SP)
00
00
*1: Please refer to FAN PERFORMANCE CURVE within Design and Technical manual for the features of each setting.
*4: If the Setting Number in ARUH96TLAV is configured to “30”, the operation is the same as that in “29 (SP mode 29)”.
*2: If the Setting Number in ARUM30TLAV is configured to “12 to 14”, the operation is the same as that in “11 (SP mode 11)”.
*3: If the Setting Number in ARUM36TLAV is configured to “10 to 14”, the operation is the same as that in “09 (SP mode 09)”.
(Cassette type only)
(Cassette type only)
models)
(For horizontal swing equipped
01-25
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......