Indoor unit field setting
setting by
remote controller
Setting Mode
ITEM
CODE No.
ITEM
CODE No.
Setting Function
Default
Classification
30
Correction
01
00
Cool air temperature trigger
02
Default 0
°F(0°C)
Temperature overshoot setting
+4°F(
+2
°C)
Temperature undershoot setting
-4°F(
-2
°C)
Default 0
°F(0°C)
Temperature undershoot setting
-11°F(
-6
°C)
Temperature slightly unbdershoot setting
-7°F(
-4
°C)
Temperature overshoot setting
+7°F(
+4
°C)
31
Heat air temperature trigger
00
01
02
03
40
Auto restart *1
00
Enable
01
Disable
43
Cool air prevention
00
Super low
01
Follow the setting on the remote controller
46
External control
00
Start / Stop
01
Emergency stop
47
Error report target
00
All
01
Display only for central remote control
02
Forced stop (Start/Stop by RC is restricted)
49
FAN Setting when cooling thermo-
stat OFF *2
01
00
Follow the setting on the remote controller
Forced stop
60
Switching functions for external
inputs and external outputs
terminals
00
01
02
04
05
03
07
08
06
Mode 0
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
Mode 7
Mode 8
61
Control switching of external
heaters
(Except Compact wall mounted
and Wall mounted )
62
Operating temperature switching of
external heaters
(Except Compact wall mounted
and Wall mounted )
00
01
02
04
00
03
02
03
04
05
01
Auxiliary heater control 1
Auxiliary heater control 2
Heat pump prohibition control
Heater selection control using outdoor temperature 1
Heater selection control using outdoor temperature 2
Setting 0
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
Change of
function 1
Change of
function 2
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
01-26
Summary of Contents for Airstage UTP-RU01AH
Page 1: ...SERVICE MANUAL 208 230V 60Hz ...
Page 5: ...1 TEST RUN ...
Page 6: ......
Page 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 59: ...3 INDOOR UNIT OPERATION ...
Page 60: ......
Page 82: ......
Page 83: ...4 TROUBLE SHOOTING ...
Page 84: ......
Page 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Page 208: ...5 APPENDING DATA UNIT ...
Page 209: ......
Page 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Page 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Page 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Page 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Page 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Page 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Page 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Page 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Page 225: ...MODEL UTP RU01CH 05 16 ...
Page 226: ...MODEL UTP RU04BH 05 17 ...
Page 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Page 228: ...MODELS AAUA96TLAV 05 19 ...
Page 230: ...6 DISASSEMBLY PROCESS ...
Page 245: ......