En-3

Note :

Router should be needed by the number of 

controlling items in the BMS.

*1. Please do not make the connection like this 

between VRF systems.

Maximum connectable indoor unit 

number per 1 Network Convertor

128

Maximum connectable outdoor unit 

number per 1 Network Convertor

100

Maximum connectable Network 

Convertor number per 1 BMS

4

Maximum connectable Network 

Convertor number per 1 VRF System

1

 

POWER

SUPPLY

L

N

电 源

X1

X2

B1

B2

TRANSMISSION

NO HIGH VOLTAGE

VRF

LON

禁止

信号线

NO HIGH VOLTAGE

NO HIGH VOLTAGE

NO HIGH VOLTAGE

X1 X2

Y1 Y2 Y3

X1 X2

Z1 Z2

H1 H2

X1 X2

Y1 Y2 Y3

1Φ 50/60Hz

208-240V

ELECTRICAL WIRING

General-purpose building control computer

(L

ON

W

ORKS

®

 device)

TRANSMISSION 

CABLE

Router

(Field supplied)

INDOOR UNIT

TRANSMISSION CABLE

OUTDOOR UNIT

MASTER

OR

SLAVE

OUTDOOR

UNIT

INDOOR UNIT

Network Convertor

Power supply cable

Transmission cable to

L

ON

W

ORKS

®

 network 

Transmission cable to

VRF network 

NETWORK CONVERTOR

POWER SUPPLY CABLE

FUSE (3A)

SWITCH (DISCON-

NECT SWITCH)

Note :

Do not bind the power supply cable and transmission 

 

cable to avoid an erroneous operation.

Use shield cable for transmission cable. 

 

The shield metal should be earthed (grounded). 

Do not forget to 

 

earth (ground) the Network Convertor. 

Install the disconnect switch to the easily accessible loca-

 

tion.

Install the fuse (3A) to the L line of power supply cable.

 

Confirm the name of each unit and name of each terminal 

block of the unit and connect the wiring in accordance 

with the directions given in the manual so that there is no 

incorrect wiring. Incorrect wiring will damage the electric 

parts and cause smoke and fire.

When installing the connection cables near a source of 

electromagnetic waves, use shielded cable. 

Otherwise, a breakdown or malfunction could result.
The terminal screws and earth (ground) screws have dif-

ferent shapes. Be sure to install the screws in the correct 

locations. If the screws are installed in the wrong loca-

tions, the circuit board could be damaged.

Wiring method

51 11 

*1

PROPER SYSTEM DIAGRAM

L

ON

W

ORKS

® 

Network

Outdoor unit

Indoor unit

VRF network system 1

Outdoor unit

Indoor unit

VRF network system 2

Lighting

facilities
Security

system

Automatic fire

alarm interface 
Ventilation

system 

General-purpose

building control computer

(L

ON

W

ORKS

®

 device)

Network

Convertor for

L

ON

W

ORKS

®

(UTY-VLGX)

Network

Convertor for

L

ON

W

ORKS

®

(UTY-VLGX)

VRF

Outdoor unit

Indoor unit

Transmission cable

(non-polar

2-conductor) 

Router

(Field supplied)

Summary of Contents for Airstage UTY-VLGX

Page 1: ...ANUAL DE INSTALAÇÃO For authorized service personnel only 只适用于专业维修人员 Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9708436029 NETWORK CONVERTOR CONVERSOR DE REDE CONVERTIDOR DE RED ADAPTATEUR RESEAU 网络转换器 UTY VLGX ...

Page 2: ...such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Do not use the unit for special purposes such as storing food raising animals growing plants or preserving pre cision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sunlight Do not operate this uni...

Page 3: ...d the transmis sion cable together with or parallel to the power supply cable of the indoor and outdoor units It may cause er roneous operation When performing wiring work be careful not to damage the cable or injure yourself Also connect the connectors securely Loose connectors will cause trouble heating fire or electric shock Install the indoor and outdoor units power supply cable transmission c...

Page 4: ...cable The shield metal should be earthed grounded Do not forget to earth ground the Network Convertor Install the disconnect switch to the easily accessible loca tion Install the fuse 3A to the L line of power supply cable Confirm the name of each unit and name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual so that there is no incorr...

Page 5: ...arth Ground Cable Binder Binder Lock nut Cut for Others Remove the 4 screws M4 6 mm and then remove the cover Open the knockout hole and then install dust proof bushing If small animals such as insects and dust enter this unit a short circuit may be caused Make a hole in the center of the dust proof bush ing with the Phillips head screwdriver Pass the power supply cable through the hole of dust pr...

Page 6: ...l for Network Convertor D14 D14 Binding and Commissioning is not executed Normal Mode Ready for operation Others Refer to 11 LED DISPLAY D19 for more detail Network Convertor does not operate during initialization If an error occurs the D9 or D14 LED lights or flashes or the error code is displayed on the right side of the D19 LED display ADDRESS SETTING 888 Setting up more than 1 Network Converto...

Page 7: ...ock in the Network Con vertor and the Network Convertor if register the changed XIF file in according to the Tool for Network Convertor Important Network Convertor will not operate if VRF network system address Indoor Outdoor units ad dress allocation information are not registered to Net work Convertor XIF data information and VRF network system address allocation information must not be same Bin...

Reviews: