background image

En-3

[Example of connecting single split type indoor unit in a parallel arrange-
ment]

Case 1: For non-polar 2 wire

Max. 1 unit

Max. 16 units

NETWORK CONVERTOR

Indoor unit

Transmission 

Cable

Wired 

remote 

controller

Case 2: For polar 3 wire

Max. 16 units

NETWORK CONVERTOR

Indoor unit

Wired remote 

controller

Transmission Cable

Max. 1 unit

*1.  Up to 16 indoor units may be controlled with a single network con-

vertor, however multiple indoor units connected to the network con-
vertor are generally required to have the same operation setting.

*2.  Connect a single multi system to a single network convertor. 2 units 

or more of multi systems cannot be connected. Multi system and 
single split system can also be connected simultaneously.

Multi system

Single 

Split

Ex. 1)   If FAN setting is selected from the control unit, the LED on the 

indoor unit will 

fl

 ash and the unit will enter the operation standby 

condition. Select another operation mode to clear the standby 
condition.

Ex. 2)   If an operation mode that is different from a currently operating 

indoor unit is selected from the control unit, the LED on the in-
door unit will 

fl

 ash and the unit will enter the operation standby 

condition. Select the operation mode of the currently operat-
ing indoor unit to clear the standby condition. Or, if operation 
becomes possible, such as by stopping the other indoor unit, 
the standby condition will be cleared and the indoor unit will 
automatically start operating with the selected mode.

5. 1. 

Wiring method

5. 1. 1.  Setting method when connecting a single split 

indoor unit

Single Split System

VRF 

Outdoor unit

VRF System

Group of Single Split System *1 *2

Multi System

Outdoor unit for 

multi system

Outdoor unit 

for single split 

system

Indoor unit 

for single 

split system

Wired remote 

controller

Transmission cable

(non-polar 2-conductor)

Remote 

controller cable

Network 

convertor

VRF 

Indoor unit

Connectable types of indoor unit and remote controller

 

Connectable remote controllers
5 types of wired remote controller shown in the table below can be 
connected to this unit.
The indoor unit that can be connected is the indoor unit that can con-
nect to following remote controller.

Model name

RC number 

Type

UTY-RNR

*

AR-WEC

**

Non-polar 2 wire

UTY-RLR

*

AR-WFA

**

AR-WFB

**

AR-WFC

**

AR-WFD

**

Non-polar 2 wire

UTB-

*

UD

AR-6TC

**

Polar 3 wire

UTY-RNN

**

AR-WAE

**

Polar 3 wire

UTY-RVN

**

AR-WDC

**

AR-WDD

**

Polar 3 wire

(

*

 arbitrary character)

 

About operation of remote controller for each type to be connected

Operation

Non-polar 

2 wire

Polar 3 wire

Operation of louver from VRF

Operation of louver from wired remote con-
troller

Restriction of wireless remote controller 
from central

Restriction of wired remote controller from 
central

Antifreeze

Setting high and low temperature limit

Indoor unit rotation

Turning off indoor unit external thermostat

Outdoor unit forced stop

Outdoor unit capacity save

Outdoor unit low noise

Electricity distribution

Display model name

System time

Remote setting

Local setting by the wired remote controller

9374707119-01_IM.indb   3

9374707119-01_IM.indb   3

2015/10/27   14:59:43

2015/10/27   14:59:43

Summary of Contents for Airstage UTY-VTGX

Page 1: ...ico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΕΤΑΤΡΟΠΕΑΣ ΔΙΚΤΥΟΥ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO CONVERSOR DE REDE Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ СЕТЕВОЙ КОНВЕРТОР Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU AÐ DÖNÜÞTÜRÜCÜ Yalnızca yetkili servis personeli için 安装说明书 安装说明书 网络信号转换器 仅针对授权的专业维修人员 English Deutsch Français Es...

Page 2: ...ais ing animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may approach the unit take preventive measures so that th...

Page 3: ...oller cable 1 m 40 in away from television and radio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermea sures Otherwise it will cause trouble or electric shock or fire Confirm the name of each unit and name of each terminal block of the ...

Page 4: ...perating with the selected mode 5 1 Wiring method 5 1 1 Setting method when connecting a single split indoor unit Single Split System VRF Outdoor unit VRF System Group of Single Split System 1 2 Multi System Outdoor unit for multi system Outdoor unit for single split system Indoor unit for single split system Wired remote controller Transmission cable non polar 2 conductor Remote controller cable ...

Page 5: ...ic shock could result CAUTION Do not set the DIP switch or rotary switch of this unit except as speci fied in this installation manual or the instruction manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Use an insulated screwdriver to set the DIP switches Before opening the cover of this unit completely discharge static elec trici...

Page 6: ...ection method is dif ferent depending on each model Modify the remote controller cable as per below description and connect it For the details refer to the installation manual of the indoor unit to be used 1 When connecting to the connector Case 1 For non polar 2 wire Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the...

Page 7: ...or unit Terminal block Functional earth ing If necessary Remote controller cable Set to 2WIRE the DIP switch SW1 Indoor unit PC board 8 CIRCUIT BOARD SETTING Set network convertor rotary switch SET1 and DIP switch SET2 SET3 1 Rotary switch SET1 set the refrigerant circuit address A single network convertor is considered as a single refrigerant system irrespective of the number of connected single ...

Page 8: ...n LED in the event of a malfunction 10 LED DISPLAY 10 1 Normal code Normal indications Normal contents LED1 green LED2 orange LED3 red During initialization during initializa tion sequence Normally operating Display mode On Off Flashing 10 2 Error code When error occurs in the remote controller connected to the Network convertor please refer to the installation manual of the remote control ler and...