En-16
(1) Calculation of additional amount for pipe length
A =
Total length of ø 12.70
mm liquid pipe
a
× 0.114
(kg/m)
+
Total length of ø 9.52
mm liquid pipe
a
× 0.058
(kg/m)
m
m
kg
kg
+
Total length of ø 6.35
mm liquid pipe
a
× 0.0218
(kg/m)
=
Total
kg
m
kg
(Round up A to 2 decimal place)
(2) Calculation of total refrigerant amount
C = A+B =
kg
(B : Factory charged amount)
NOTES:
Check the total refrigerant amount under the following conditions
Condition
Computational formula
Total amount of refrigerant
C
≤
20.0 kg
<Calculation>
Outdoor unit: AJ*072LELAH
(1) Calculation of additional amount for outdoor unit
If liquid pipe piping length is the following
Ø 12.70 mm: 50 m, Ø 9.52 mm: 25 m, Ø 6.35 mm: 15 m
Additional charge volume:
A = 50 m × 0.114 kg/m + 25 m × 0.058 kg/m +15 m × 0.021 kg/m = 7.465 kg
≈
7.47 kg
(2) Check the total amount of refrigerant
C = A + B = 7.47 kg + 7.0 kg = 14.47 kg
≤
20.0 kg
→
No problem if the above condition is satisfied.
8.4. Installing
insulation
• Install insulation material after conducting the “8.1 Sealing test”.
• To prevent condensation and water droplets, install insulation material on the refrigerant
pipe.
• Refer to the table to determine the thickness of the insulation material.
• If the outdoor unit is installed at a level that is higher than the indoor unit, the water that
has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit.
Therefore, use putty in the space between the pipe and the insulation to prevent the
entry of water.
Table. Selection of insulation
(Use an insulation material with equal heat transmission rate or below 0.040
W/(m·k))
Insulation material minimum thickness (mm)
Relative humidity
≤
70%
≤
75%
≤
80%
≤
85%
Pipe diameter
(mm)
6.35
8
10
13
17
9.52
9
11
14
18
12.70
10
12
15
19
15.88
10
12
16
20
19.05
10
13
16
21
22.22
11
13
17
22
28.58
11
14
18
23
* When an ambient temperature and relative humidity exceed 32 °C, please strengthen
heat insulation of refrigerant pipe.
8.5. Filling with putty
WARNING
Putty
Insulation
Fig. A
Fill the piping holes and wiring holes with putty
(locally purchased) to avoid any gap (Fig A). If
small animals such as insects enter the external
unit, a short circuit may be caused near electrical
components in the service panel.
If the outdoor unit is installed at a level that is higher
than the indoor unit, the water that has condensed
in the 3-way valve of the outdoor unit could travel
to the indoor unit. Therefore, use putty in the space
between the pipe and the insulation to prevent the
entry of water to the indoor units.
9. TEST
RUN
9.1. Indoor unit connection check
Normal operation will not be possible without performing the Indoor unit connection check.
9.1.1 Things to con
fi
rm before starting the Indoor unit connection
check
To ensure safety, check that the following work, inspections and operations have been
completed.
Check Item
Check Column
1
Check that all work on the wiring connecting the outdoor
unit and indoor units has been completed.
2
Is a breaker installed at the power supply cable of out-
door unit and every indoor units?
3
Are the cables connected to the terminals without loose-
ness, and in accordance with the specifications?
4
Are all the indoor units stopped? Indoor unit connection
check can not be performed if any unit is operating.
5
Is the connection to Service tool (UTY-ASGX) and Web
monitoring tool (UTY-AMGX) stopped?
9.1.2 Operating procedure for Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
The Indoor unit connection check can be completed within several minutes.
Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press
the “SELECT” button until [F3] is displayed.)
Press the “SELECT” button until “12” is displayed.
When indoor unit connection
check can not be performed
Turn on the power of indoor
unit and outdoor unit.
Press the “ENTER” button for more than 3 seconds.
This will be displayed when the Indoor unit connection
check starts.
: Press the “MODE/EXIT” button
: Press the “SELECT” button
: Press the “ENTER” button.
: Press the “ENTER” button for
more than 3 seconds.
(*1) The number of connected indoor units
Ex.) When 8 units are connected
(*2) Volume ratio of the indoor units connection
Ex.) When the ratio is 120%
Please refer to the following “Error displays”
for details.
When it finishes normally, nothing will be displayed on
7 segment display.
When error occurs
Confirm the number of connected indoor units and the
volume ratio of the indoor units connection.
Exit indoor unit connection check mode.
9380545200-03_IM.indb 16
9380545200-03_IM.indb 16
4/6/2017 3:20:35 PM
4/6/2017 3:20:35 PM