En-3

Optional parts

2. 4. 

CAUTION

The following parts are optional parts speci

fi

 c to R410A refrigerant.

Do not use parts other than those listed below.

Separation tube kit

2. 4. 1. 

Separation tube uses the following parts.

Separation tube

Total cooling capacity of indoor unit (kw)

UTP-AX090A

ALL

Header

2. 4. 2. 

Header uses the following parts. A header is used for connecting the indoor units.

Header

Total cooling capacity of 

indoor unit (kw)

3-6 Branches

3-8 Branches

UTR-H0906L

UTR-H0908L

ALL

INSTALLATION WORK

3. 

Please obtain the approval of the customer when selecting the location of installation 
and installing the main unit.

Selecting an installation location

3. 1. 

WARNING

Install the unit in a location that can withstand its weight, and where it will not topple 
or fall.

Calculate the proper refrigerant concentration if you will be installing it in an 

• 

enclosed location.

Total amount of replenished 
refrigerant in refrigerant facility (kg)  
Capacity of smallest room where unit is installed (m

3

Refrigerant 
concentration (kg/m

3

)

(0.3kg/m

3

)

If the results of the calculation exceed the concentration limit, increase the room surface 

• 

area or install a ventilation duct.

CAUTION

Please install the outdoor unit without slant. (within 3 degrees)

Install this unit in a location with good ventilation.

If the unit must be installed in an area within easy reach of the general public, install 
as necessary a protective fence or the like to prevent their access.

Install the unit in an area that would not inconvenience your neighbors, as they could 
be affected by the air

fl

 ow coming out from the outlet, noise, or vibration.

If it must be installed in proximity to your neighbors, be sure to obtain their approval.

If the unit is installed in a cold region that is affected by snow accumulation, snow fall, 
or freezing, take appropriate measures to protect it from those elements. 
To ensure a stable operation, install inlet and outlet ducts.

Install the unit in an area that would not cause problems even if the drain water is 
discharged from the unit. Otherwise, provide drainage that would not affect people or 
objects.

Install the unit in an area that has no heat sources, vapors, or the risk of the leakage 
of 

fl

 ammable gas in the vicinity.

Install the unit in an area that is away from the exhaust or vent ports that discharge 
vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, transmission cable and 
remote control cable at least 1 meter away from a television or radio. 
The purpose of this is to prevent TV reception interference or radio noise. (Even if 
they are installed more than 1 meter apart, you could still receive noise under some 
signal conditions.)

Keep the length of the piping of the indoor and outdoor units within the allowable 
range.

For maintenance purposes, do not bury the piping.

Drain processing

3. 2. 

CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain water 
is properly drained. If the drain work is not carried out correctly, water may drip down 
from the unit, wetting the furniture.

When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe 
may freeze in extremely cold weather.

As the drain water 

fl

 ows out of the outdoor unit during heating operation, install the 

• 

drain pipe and connect it to a commercial 16mm hose.
When installing the drain pipe, plug all the holes other than the drain pipe mounting 

• 

hole in the bottom of the outdoor unit with putty so there is no water leakage. 

341

305

321

227

438

278

50

622

Drain cap mounting hole ×3

(Unit: mm)

Drain pipe mounting 
 hole ×1

Base

Drain pipe

Drain pipe mounting hole

Installation dimensions

3. 3. 

CAUTION

Provide suf

fi

 cient installation space, such as transportation route, maintenance space, 

ventilation space, refrigerant piping space, and passageways.

Pay attention to the speci

fi

 cations of the installation space as shown in the 

fi

 gure. If 

the unit is not installed according to speci

fi

 cations, it may cause short circuit or poor 

performance. The unit may be prone to lapse into non-operation due to high pressure 
protection.

When there is a wall in front of the unit, provide a space of 500mm or more as main-
tenance space.
When there is a wall at the right side of the unit, provide a space of 25mm or more as 
maintenance space.

An outdoor temperature of 35 °C (DB) in air-conditioned operation is assumed for 
the installation space in this item. If the outdoor temperature exceeds 35 °C (DB) and 
the outdoor unit is operating at a load exceeding its rated ability, provide a larger inlet 
space.

If you are installing more outdoor units than indicated here, please ensure suf

fi

 cient 

space or consult your distributing agent as it may affect the performance due to short 
circuit and other problems.

Consider the transportation route, installation space, maintenance space, and access, 
and install the unit in a location with suf

fi

 cient space for the refrigerant piping.

Observe the installation space speci

fi

 cations that are shown in the 

fi

 gures.

Keep the same space at rear air intake.
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the speci

fi

 cations, it could cause a 

short circuit and result in a lack of operating performance. As a result, the outdoor unit 
might easily be stopped by high-pressure protection.

Air intake

Rear view

<

=

9380545026-02_IM.indb   3

9380545026-02_IM.indb   3

19/08/2013   17:19:16

19/08/2013   17:19:16

Summary of Contents for AJHA36LALH

Page 1: ...ΙΚΉ ΜΟΝΆΔΑ UNIDADE EXTERIOR ВНЕШНИЙ МОДУЛЬ DIŞ ÜNİTE For authorized service personnel only Nur für autorisiertes Fachpersonal Uniquement réservé aux techniciens agréés Sólo para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Apenas para técnicos de assistência autorizados Только для авторизованного обслуживающего персона...

Page 2: ...performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as over heating the terminals electric shock or fire Securely install the electr...

Page 3: ...pe lightning rod or a telephone ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is improperly installed water may drip down from the unit wet ting the furniture Do not touch the fins with bare hands Be sure not to start or stop the operation of air conditioni...

Page 4: ...part you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Drain processing 3 2 CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down f...

Page 5: ... the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3 Obstacles at front and rear only 500 1500 or more When an obstruction is present also in the upward area Unit mm Obstacles at rear and above only 1500 500 Max 300 1500 3 3 3 Outdoor units installation in multi row Unit mm The following settings are not recommended in case of ...

Page 6: ...5 Use reducer to change the diameter of connection pipe Installation the unit 3 5 Please install the outdoor unit without slant within 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a...

Page 7: ...g nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the compres sor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For brazing material use phosph...

Page 8: ...g with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 Width across flats Bending pipes 5 4 2 CAUTION To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 100mm or more If the pipe ...

Page 9: ...es Use a hexagon wrench size 4mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap inst...

Page 10: ...urr on the edges to prevent snapping of cables It is recommended to apply rust proof paint on the edges to prevent rust Knockout holes are provided for wiring Fig A Knockout holes are provided 2 each in the same size in front lateral and rear sides Fig B Fig A Service panel Fig B Front connection Rear connection Lateral connection Selecting power supply cable and breaker 6 3 CAUTION Regulation of ...

Page 11: ...etwork Convertor etc 1 Fig Transmission line Outdoor unit Indoor unit System Controller Touch Panel Controller Terminal resistor When AB BC BD 500m Signal Amplifier is required A B C D 2 Fig Do not use loop wiring NOTE This may lead to parts damage and erroneous operation Outdoor unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal...

Page 12: ...re to connect to the terminal block 2 Securely clamp the crimp type terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw he...

Page 13: ... ON Outdoor unit operation peak control Input4 CN134 Red OFF Normal operation ON Batch stop or Emergency stop operation 2 3 Input5 CN135 Orange 4 No pulse No information from electricity meter Pulse Power usage information from electricity meter The operations of each input terminal and the selection of function are set with the push button on the PC board of outdoor unit About the setting please ...

Page 14: ...it printed circuit board DIP switch Terminating resistor setting 7 2 2 CAUTION Be sure to set the terminal resistor according to specifications Set the terminal resistor for every network segment NS If terminal resistor is set in multiple devices the overall communication system may be damaged If terminal resistor is not set in a device abnormal communication may occur Be sure to set 1 terminal re...

Page 15: ...rbidden 2 2 0 0 Factory default 23 Forbidden 2 3 0 0 Factory default 24 Forbidden 2 4 0 0 Factory default 25 Forbidden 2 5 0 0 Factory default 26 Forbidden 2 6 0 0 Factory default 27 Forbidden 2 7 0 0 Factory default 28 Forbidden 2 8 0 0 Factory default 29 Forbidden 2 9 0 0 Factory default 30 Outdoor unit capacity save setting Level 1 stop 3 0 0 0 The capacity limit can be selected by the external...

Page 16: ...play LED105 LED104 Flashing When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed Use the MODE EXIT SELECT and ENTER buttons to configure settings according to the procedures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button 2 Setting the first 2 digits 3 Setting the la...

Page 17: ...operating manual When setting with a remote control refer to the remote control operating manual Automatic setting Check that the wiring is as shown in the figure below Operate using the outdoor master unit of each refrigerant system Wiring example for automatic address setting Fig 1 Signal amplifier wiring example 2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same r...

Page 18: ...re of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the processing End 1 4 4 ﻸ ﻮ ﻮ ﻮ ﻮ ﻺ ﻶ First 2 digits Last 2 digits Press the SELECT button until 11 is displayed Press the ENTER button for more than 3 seconds Automatic address setting for indoor units The number...

Page 19: ...nt in the liquid state If the refrigerant cylinder is equipped with a siphon it is not necessary to place the cylinder upright Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon Set the cylinder vertical and fill with the liquid Liquid can be filled without turn...

Page 20: ...Insulation Fig A TEST OPERATION 9 Indoor unit connection check 9 1 Normal operation will not be possible without performing the Indoor unit connection check Things to confirm before starting the Indoor unit 9 1 1 connection check To ensure safety check that the following work inspections and operations have been completed Check Item Check Column 1 Check that all work on the wiring connecting the o...

Page 21: ...gerant Is the refrigerant circuit address correct Is a breaker installed at the power supply cable of outdoor unit Are the cable connected to the terminals without looseness and in accordance with the specifications Are the initial settings of the switches of the outdoor unit correctly configured Is the 3 way valve of the outdoor unit open Gas pipe and liquid pipe Is power supplied to the crank ca...

Page 22: ...r 5 seconds Press the ENTER button for more than 3 seconds This will be displayed when the cooling operation mode is canceled This will be displayed after 5 seconds This will be displayed after 5 seconds This will be displayed when the heat ing operation mode is canceled Press the ENTER button for more than 3 seconds This will be displayed after 5 seconds Settings for stopping test run operation S...

Page 23: ...rror permanent stop E 8 6 1 Outdoor unit discharge pressure sensor error E 8 6 3 Outdoor unit suction pressure sensor error E 8 6 4 Outdoor unit high pressure switch 1 error Outdoor unit actuator error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchro nization E 9 7 1 Outdoor unit fan motor 1 lock error...

Reviews: