SPECIFICATIONS
1.
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Type
INVERTER HEATPUMP
Model name
AO
A30LBTL
AO
A36LBTL
Power source
230V ~ 50Hz
Available voltage range
198-264V ~ 50Hz
Starting current
A
15.0
15.0
Fan
Airflow
rate
Cooling
m
3
/h
3600
4000
Heating
3800
3800
Type × Q'ty
Propeller × 1
Motor output
W
103
103
Sound pressure level
Cooling
dB(A)
53
54
Heating
55
55
Heat exchanger type
Dimensions (H × W × D)
mm
798 × 900 × 36.4
798 × 900 × 36.4
Fin pitch
1.30
1.30
Rows x Stages
2 × 38
2 × 38
Pipe type
Copper
Fin type
Aluminium
Compressor
Type × Q'ty
Twin Rotary × 1
Motor output
W
1700
Refrigerant
Type
R410A
Charge
g
2100
Refrigerant oil
Type
PVE
Enclosure
Material
Steel sheet
Colour
BEIGE
Approximate colour of MUNSELL 10YR 7.5/1.0
Dimensions
( H×W×D)
Net
mm
830 × 900 × 330
Gross
970 × 1050 × 445
Weight
Net
kg (lb.)
62 ( 136 )
Gross
70 ( 154 )
Connection
pipe
Size
Liquid
mm
Ø 9.52 (Ø 3/8 in.)
Gas
Ø 15.88 (Ø 5/8 in.)
Method
Flare
Max. length
m
50(chargeless:20)
50(chargeless:20)
Max. height difference
30
30
Operation range
Cooling
˚C
-15 to 46
Heating
-15 to 24
Summary of Contents for AO*A30LBTL Series
Page 2: ...1 INDOOR UNIT D2D_AU034E 04 2010 07 07 CASSETTE TYPE AU A30LBLU AU A36LBLU ...
Page 44: ... 02 05 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF AO A36LF ...