14
Copyright© 2010, 2011 Fujitsu General Limited. All rights reserved.
Installation
Hardware Installation (Transmission Adaptor)
5-2
55555
Transmission Adaptor Installation
UTY-ABGX
BACnet
®
Gateway
Transmission Adaptor
(U10 USB Network Interface)
VRF System (
VRF System 2
VRF System 1
VRF System 0
USB cable
The BACnet
®
Gateway can connect up to 4 VRF Systems. Since 1 Transmission Adaptor connects to
1 system, up to 4 Transmission Adaptors are connected.
Following chart shows the detail of the U10 USB Network Interface Adaptor. These adaptors are not includ-
ed in the BACnet
®
Gateway product and must be procured in advance.
Name & Shapes
Q’ty
Remark
Transmission Adaptor (U10 USB Network Interface
-TP/FT-10 Channel)
(Field Supply)
Procure the necessary number
in accordance with the number
of connection systems.
Model : 75010R
(Echelon
®
Corporation)
It is necessity that set Transmission adaptor respectively because of the S/V series and V-II/J-II series can
not be connected to the same communication line.