BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
32/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5.3.10 Batch_RC_Prohibition_Setting (Multistate Output Object Type)
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Multistate Output, 2)
R
R
Object_Name
CharacterString
“Batch_RC_Prohibition_Setting”
R
R
Object_Type
BACnetObjectType
MULTISTATE_OUTPUT (14)
R
R
Present_Value
Unsigned
1 ~ 65
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
65
R
R
State_Text
BACnetArray[N] of
CharacterString
table
(section 12.2)
O
R
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
1
R
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Feedback_Value
Unsigned
-
O
W
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured