BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
34/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
5.3.12 IU_rr_uu_SpaceTemp_Status (Analog Input Object Type)
Indoor unit surrounding temperature status can be monitored.
Property Identifier
Property Datatype
Value
ASHRAE UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 11rruu)
R
R
Object_Name
CharacterString
“IU_rr_uu_SpaceTemp_Status”
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
V-II/J-II/VR-II Series
Suction Temperature is obtained.
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
Degrees Celsius (62) // Fahrenheit (64)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
High_Limit
REAL
-
O
R*
Low_Limit
REAL
-
O
R*
Deadband
REAL
-
O
R*
Limit_Enable
BACnetLimitEnable
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured