BACnet
®
Gateway for VRF System
INSTRUCTION MANUAL r1.3.2 eng
42/103
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
Notes on the set temperature value
A set point entered from the BMS must be taken from the Celsius column in the following table. Any entered values
not from the table will be ignored, rounded or translated to other values.
A. Halcyon System through the single network convertor
Cool/Dry/Auto
: 18-30degC (64-88 degF)
Heat
: 16-30 degC (60-88 degF)
Setting the value exceeding the upper lor lower limit of the unit will be rounded to the nearest limit.
If Fahrenheit units are
used, the remote
controller will display the
following:
Centigrade
If Fahrenheit units are
used, the remote
controller will display the
following:
Centigrade
60
16
64
18
62
17
66
19
68
20
70
21
72
22
74
23
76
24
78
25
80
26
82
27
84
28
86
29
88
30
B. Airstage VRF System
Setting the value exceeding the upper or lower value limit of the unit will be rounded to the nearest limit.
V-II/J-II/VR-II/J-IIS Series: Value obtained by scanning
If Fahrenheit units are
used, the remote
controller will display the
following:
Centigrade
If Fahrenheit units are
used, the remote
controller will display the
following:
Centigrade
48
10
64
18
49
10.5
65
18.5
50
11
66
19
51
11.5
67
19.5
52
12
68
20
53
12.5
69
20.5
54
13
70
21
55
13.5
71
21.5
56
14
72
22
57
14.5
73
22.5
58
15
74
23
59
15.5
75
23.5
60
16
76
24
61
16.5
77
24.5
62
17
78
25
63
17.5
79
25.5
80
26
81
26.5
82
27
83
27.5
84
28
85
28.5
86
29
87
29.5
88
30